background image

 

Platinum 1050

  11-HD15D1-5-EN 29

10. Troubleshooting

SYMPTOM

POSSIBLE CAUSES

ACTION

1050 Control displays an alert on 
the screen.

A critical or major alert is present.

Navigate to the Diagnostic screen on the 1050 Control 
for a Problem Description and Possible Cause.

Display will not come on

Loss of 24VAC between R & B at the 1050 
Control.

1) Check wiring between R & B
2) Check transformer for 24VAC output.
3) Check for broken or shorted thermostat wire.

Indoor temperature display is 
incorrect.

1) Indoor temperature display needs calibration. 
2) Surrounding air flow affecting sensed 
temperature of the 1050 Control

Calibrate temperature sensor from 1050 Control’s 
menu.

Indoor humidity display is incor-
rect.

Indoor humidity display needs calibration.

Calibrate humidity sensor from the 1050 Control’s 
menu.

Room temperature overshoots 
when the Heat/Cool setting is 
changed more than 2°.

1) Oversized heating/cooling equipment under 
current conditions.  1050 Control cannot re-
spond fast enough to prevent overshooting.
2) Improper location of 1050 Control.

1) Compare heat load calculation to equipment chosen.
2) Relocate 1050 Control (or use remote sensor)

Heating will not come on.

1) System mode is not set to Heat/Auto or set-
point is set too low.
2) Minimum off time delay is being enforced.
3) Heating system may require service.

1) Set mode to heat and raise the setpoint above the 
room temperature.
2) Wait for 5 minutes and recheck heating equipment.
3) Check/repair system.

Cooling will not come on.

1) System mode is not set to Cool/Auto or the 
setpoint is too high.
2) Minimum off time delay is being enforced.
3) Cooling system may require service.

1) Set mode to cool and lower the setpoint below the 
room temperature.
2) Wait for 5 minutes and recheck cooling equipment.
3) Check/repair system.

Heating or Cooling is displayed, 
but no warm or cool air is coming 
from the registers.

1) There is a fan delay as the heating or cooling 
equipment turns on.
2) Equipment is not working properly.

1) Wait a minute for blower delays and recheck regis-
ters.
2) Check/repair system.

Fan runs all the time

1) Fan mode is set to On, Circulate or Clean 
mode
2) There is a failure in the indoor unit 

1) Check 1050 Control settings to see if fan is set to 
On, Circulate or Clean mode.
2) Check indoor unit for failures (such as tripped heat-
ing limit).

“+” symbol appears on Home 
Screen beneath Indoor 
Temperature readout

Both compressor heat and indoor heat are being 
called simultaneously

 

No action required, symbol is for informational purposes 
only

Fan is set to ON but not running.

1) Smart Continuous Fan feature has been  is 
engaged.  
2) Blower motor is not functioning.

1) If indoor humidity is higher than desired setpoint, 
the blower will cycle off with the equipment. A humidity 
icon will be displayed on the Fan Mode button when 
the blower operation is being inhibited due too high 
humidity.
2) Check/repair system.

Cooling or Heating cycles too 
fast or too slow (narrow or wide 
temperature swings).

1) Check the location of the 1050 Control for 
drafts.
2) Cycles per hour or aggressive recovery is 
improperly set.

1) Seal air leaks behind 1050 Control.  Relocate 1050 
Control or apply remote indoor temperature sensor.
2) Adjust cycle rates and aggressive recovery features 
in the advanced installer set up.

Heat pump is not turning on; only 
furnace or electric heat strips are 
running.

1) Outdoor temperature is below compressor 
lockout temperature setting.
2) Compressor heating lockout is enabled and 
outdoor temp sensor is out of calibration or 
failed.
3) The outdoor unit is not reporting (Err.126.00)

1) Adjust the compressor lockout temperature setting 
if desired.
2) Check/repair outdoor sensor or wiring. 
3) Check communication status of outdoor unit.

Содержание AZON1050AC52ZA

Страница 1: ...property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation Should furth...

Страница 2: ...rk Connections 4 4 3 Mounting 4 4 4 Wiring 5 4 5 Field Wiring Connection Diagrams 6 5 System Setup 8 5 1 Power Up Sequence 8 5 2 Guided Setup Wizards 8 5 3 Installer Setup Screens 8 5 3 1 Group 1 Stan...

Страница 3: ...minutes Indoor Heat 1 minute On every application 24VAC loads should be reviewed to be sure the indoor unit control power transformer is adequately sized 2 Product Specifications 3 General Information...

Страница 4: ...from the Internet router Tips to Help Maximize Signal Strength Mount the 1050 Control within 30 feet of wireless router Install 1050 Control with no more than three interior walls between it and the...

Страница 5: ...ires extend through the Sub base See Figure 3 4 4 Wiring 1 Adjust the length and position of each wire to reach the proper terminal on the connector block of the Sub base Strip 1 4 of insulation from...

Страница 6: ...nel B C R D ODT ODT RS RS R B D R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL INDOOR UNIT 1050 COMFORT CONTROL Heat Pump Multi Stage AC Caution Do not run Outdoor Remote sensor wire...

Страница 7: ...unicating Controls w S9V2 Furnace and Comm Outdoor B C R D ODT ODT RS RS R B D Optional Outdoor Sensor Optional Remote Sensor RELAY PANEL S9V2 FURNACE OUTDOOR UNIT 1050 COMFORT CONTROL Caution Do not...

Страница 8: ...ower Type Non Variable Variable Select the indoor blower type Constant Torque motors are considered non variable speed All Group 1 settings will be auto configured for fully communicating systems 5 Sy...

Страница 9: ...when a voting zone is also requesting capacity Indoor Heating Airflow Offset above and below cooling airflow 1 50 50 0 The air flow offset is the difference between the design cooling air flow CFM per...

Страница 10: ...a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A g g re s s iv e L e s s A g g re s s iv e N o rm a l M o re A...

Страница 11: ...uring 1st stage indoor heat operation 2nd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 Select of cycles per hour during 2nd stage indoor heat operation 3rd Stage Indoor Heat Cycles Per Hour 2 6 Cph 5 S...

Страница 12: ...lect whether an outdoor temperature override is allowed Outdoor temperature sensor must be connected and enabled to allow this setting to be selected Ventilator Fan Action Ventilate with Blower Ventil...

Страница 13: ...r cooling mode with a setpoint change greater than 2 Heating Aggressive Recovery 2 by Outdoor Temperature Enable Disable Select whether the 10 minute staging inhibit is disabled during heating mode wh...

Страница 14: ...ower On Delay for variable speed blowers only 1 minute at 50 7 5 minutes at 80 then 100 Non VS Blower On Delay Comp Htg No Delay 15 Seconds 30 Seconds Select the blower on delay for compressor heating...

Страница 15: ...Disable Enable Enable defrost heater balance point for W3 only applicable when indoor heat is electric or hydronic Defrost Heater Balance Point W3 Setting 5 F 45 F Select an outdoor temperature to di...

Страница 16: ...ler Code When an 1050 Control is connected to Nexia a Dealer Code can be entered to auto populate the dealer s contact information and logo The code is the dealer s registered phone number listed on A...

Страница 17: ...Stage Gas Oil Heat LOAD VALUE RANGE COOLING 0 100 Single Stage Compressor 0 200 Two Stage VSPD Compressor A Load Value of 50 represents a request of 50 demand for single stage cooling units Y or 50 de...

Страница 18: ...AGE 3 AUX WET HEAT STAGING THRESHOLDS 100 125 100 125 200 215 200 215 Compressor to W1 Compressor to W1 W1 to W2 W1 to W2 6 6 Stage Inhibits When the stage threshold is exceeded a stage inhibit is app...

Страница 19: ...igured to only limit Day operation only limit Night operation or limit Day and Night operation to different demands Night mode affects operation from 10 PM until 9 AM at which point Day settings for Q...

Страница 20: ...ort Settings Smart Continuous Fan settings 7 3 Dehumidifier Operation The 1050 Control has the ability to control a Whole House Dehumidifier through the normally open dry AUX Contacts on the optional...

Страница 21: ...SETTINGS TO BE AVAILABLE Lockouts can be enabled in Installer Setup Lockout Settings Auxiliary Heat Lockout Once enabled select an outdoor temperature which disables auxiliary heat anytime the outdoo...

Страница 22: ...ilation only The ventilation run time per hour can be adjusted to meet ASHRAE 62 2 standards A temperature override can be set to prevent ventilation operation when the outdoor temperature exceeds the...

Страница 23: ...default setting Trane or American Standard manufactured indoor unit with a variable speed blower branded Geothermal package units and oil furnaces are not supported Field supplied 24 volt transformer...

Страница 24: ...on for each same mode calling zone follows the calculation below Zone LV System LV damper position The minimum opening position is always 25 to reduce air whistling from a partially opened damper Zone...

Страница 25: ...odels If the 1050 Control still calculates excess air then the excess will be relieved following the rules below Relief Strategy 1 Divide the excess air evenly between the zones which are calling but...

Страница 26: ...rect compressor speed and associated indoor blower speed to set verify sytem charge Use sub cooling tables in the outdoor unit Service Facts to determine correct charge levels Outdoor temperature must...

Страница 27: ...ll is not immediately required Alert messages are not displayed on the home screen NORMAL Functionality may be lost but should recover or the information is for diagnostic purposes performance monitor...

Страница 28: ...or speed currently operating Cool Current cooling set point per zone Load Value Numerical value used to determine how much capacity is required to meet set point For more information see 6 2 Load Valu...

Страница 29: ...uipment 3 Check repair system Heating or Cooling is displayed but no warm or cool air is coming from the registers 1 There is a fan delay as the heating or cooling equipment turns on 2 Equipment is no...

Страница 30: ...time of inactivity Screen Saver mode set to Black which turns of screen back light after a user selected time of inactivity Normal operation User may change screen saver from Black to Indoor Temperat...

Страница 31: ...l interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following me...

Страница 32: ...D1 5 EN The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice Representative only illustrations...

Отзывы: