background image

AmeriVent Model HS/HSS All-Fuel Chimney

Installation Instructions

3. Firestop Assembly Cat. No. 6, 8 HS-FSA

NOTE:

Firestop assemblies are required in dwellings
wherever the chimney passes through floors above
the ceiling support.  A ceiling support is used only
in the ceiling directly above the appliance, and
firestop assemblies must be used at all other floor
levels.  Firestop assemblies maintain proper
clearances between chimney and combustible
material.  Prepare an opening in the ceiling
according to the chart in Table 1.  This opening
must be framed on all four sides.  Assemble
chimney sections up to firestop opening.

a. For all floor levels above ceiling support, with the exception

of attic, guide firestop assembly over chimney section
below with spacer flange toward joist (see Figure 5).
Complete assembly of pipe through joist.  Push firestop up
against bottom of ceiling with spacer into joist opening.
Nail firestop in place with three (3) nails on each side.

b. On attics where chimneys are enclosed or where the attic

insulation shield is used (see Section 4), the firestop must
be installed on the top of joist in the same manner
described in Section a.

4. Attic Insulation Shield Cat. No. 6, 8 HS-AIS

If the chimney passes through an attic space, one of the
following methods must be used to prevent building insulation
from infringing on the required 2-inch airspace to combustibles.

NOTE:

On new construction, the chimney should be
enclosed (or insulation shield installed) before
installing insulation.

a. Completely enclose the chimney where it passes

through the attic space, maintaining at least 2 inches of
airspace clearance (see Figure 6) after installing firestop
assembly as in Section 3.b.

b. Install an attic insulation shield on the top of the joist

(see Figure 7).

NOTE:

Attic shield is 18 inches high; therefore, if there is 18
inches or less clearance from roof in the area where
chimney is located, the chimney must be totally
enclosed instead of using attic insulation shield.

1) Slide the double-wall attic insulation shield down around

the chimney, with the flat plate sitting either directly on the
joist above the ceiling support or on firestop assembly.

2) Position attic shield collar around pipe tightly, and push

down onto double-wall attic insulation shield to prevent
loose insulation from entering the 2-inch airspace.

3

Содержание AMERIVENT HS

Страница 1: ...is galvanized steel This chimney is listed UL 103 TYPE HT for venting flue gases not exceeding 1000 F under continuous operating conditions In addition UL has conducted additional tests at 1400 F for...

Страница 2: ...ey installation requirements AmeriVent Model HS all fuel chimneys may be connected directly to a masonry fireplace by using an AmeriVent anchor plate instead of a standard support IMPROPER INSTALLATIO...

Страница 3: ...irestop must be installed on the top of joist in the same manner described in Section a 4 Attic Insulation Shield Cat No 6 8 HS AIS If the chimney passes through an attic space one of the following me...

Страница 4: ...upport Bracket Assembly see Figure 10 You may need to temporarily support the offset during assembly The offsets use the same locking system as the pipe sections described in Section A 2 Page 2 6 Chim...

Страница 5: ...ing is completed nail through all four sides of roof support into framework installed in Step b Use a minimum of sixteen 16 8d nails f Install the single wall adapter furnished with the support by pus...

Страница 6: ...o 6 8 HS WTP a Install the wall thimble through opening in wall with the black painted surface on the inside wall see Figure 22 Screw each trim plate in place through the four 4 prepunched holes on ea...

Страница 7: ...ssage of the chimney is obstructed it is necessary to cut a hole in the overhang Leave a minimum of 2 inch clearance and install the flashing and storm collar per Section A 6 a e Page 4 see Figure 14...

Страница 8: ...vapors which combine with expelled moisture to form creosote The creosote vapors condense in the relatively cool chimney flue of a slow burning fire As a result creosote residue accumulates on the flu...

Отзывы: