background image

10

Installation of Type B-W Gas Vent

1. Cut out the ceiling plate at the floor level above the
heater flush with studs in space where Vent is to be
installed.

2. Nail one Ameri-Vent Plate Spacer (40PS), (A), across
cut out area in ceiling plate - see Fig. 16.

3. Snap Hold Down Plate (4OHD), (B), onto bottom end
of Ameri-Vent pipe as shown in Fig. 16. Install Vent
Section in position. Use two No. 8 binder head sheet
metal screws to attach Hold Down Plate firmly to Furnace
header plate through pre-punched holes.

4. Nail second Ameri-Vent Plate Spacer across cutout
ceiling plate as shown in Fig. 16.

5. If the Vent is to continue additional stories within a 2x4
stud space, install Firestop Spacers at the second and
subsequent ceiling levels as shown in Fig. 17.

6. After passing through the last Firestop Spacer, the Vent
may be finished with either round or oval Ameri-Vent
fittings, flashings and Ameri-Cap. (Round pipe, fittings,
flashings and vent caps cost less than corresponding oval
parts.)

Attic Insulation Shield

In some areas the building code requires the use of an
attic insulation shield (AVS) on single story Type B-W
installations.

Termination of Vent Structure

The Ameri-Vent Gas Vent is available for most Models
and sizes in two styles of Termination Tops, Ameri-Cap
and Universal Cap. The Ameri-Cap is a lock neck design
with the same lock as the female end of the Vent sections.
The Universal Cap is designed to fit inside the inner wall
of the vent sections.

American Metal Products 12" and smaller Gas Venting
Systems using either the Ameri-Cap or the Universal
Cap, may terminate in accordance with Table 6 and
Figs. 18 & 20.

Multi-Story

Type B-W

Installations

AT SECOND AND
SUBSEQUENT CEILING LEVELS
USE 40FS FIRESTOP SPACERS.

AT FIRST CEILING LEVEL
USE 40PS CEILING
PLATE SPACERS.

A

B

Type B-W

Installation

Roof Pitch

Minimum Height

Flat to 

7/12

1.0  feet

over 

7/12 to 8/12

1.5  feet

over 

8/12 to 9/12

2.0  feet

over 9/12 

to 

10/12

2.5 

feet

over 

10/12 to 11/12

3.25  feet

over 

11/12 to 12/12

4.0  feet

over 

12/12 to 14/12

5.0  feet

over 

16/12 to 18/12

6.0  feet

over 

18/12 to 20/12

7.0  feet

over 

20/12 to 21/12

8.0  feet

Table 6

Ameri-Cap 12" and Smaller

Gas Vent Termination Table

FIG. 17

FIG. 16

Содержание AMERI-VENT E

Страница 1: ...NT AND ACCES SORIES ARE NOT TO BE USED WITH INCINERATORS OR WITH APPLIANCES BURNING SOLID OR LIQUID FUELS Vent sizing and installation are to be made in accordance with all applicable local building c...

Страница 2: ...eginning any lateral runs Lateral venting should be kept to a minimum to avoid vent resistance Horizontal runs to vents should either be in accordance with the appropriate tables in NFPA 54 or should...

Страница 3: ...rews Each joint of the singlewall system must be connected with three 3 sheet metal screws Singlewall connector must not penetrate any walls or ceilings or be used in any cold or non routinely inspect...

Страница 4: ...he bucket Attach the mounting tabs with sheet metal screws 3 Provide additional strapping or hangers for connector offsets Firestop Supports The Firestop Support FSP and Support Bracket SB are designe...

Страница 5: ...ports must not in any case exceed 30 feet 2 The circular cutout in the Round Support Plate is designed to engage the uppermost recess in the female end of the Vent Pipe See Fig 10 3 Surround the Vent...

Страница 6: ...sition at each opening where a support is to be used The Adjustable Length Section also provides relief for linear thermal expansion The Adjustable Length Section should be positioned directly under t...

Страница 7: ...e outer wall of the Vent Pipe and the hole cut in the structure In attics the Firestop should be placed on top of the framed ceiling opening to pre vent insulation and debris from coming into contact...

Страница 8: ...thTwo 45 Vent Elbows One One One One One One One Size A B ONLY 6 Length 12 Length 18 Length 24 Length 3 Length 4 Length 5 Length 3 3 2 3 4 3 1 4 6 3 4 11 15 1 4 19 1 2 28 36 1 2 45 4 3 7 8 3 1 16 3 1...

Страница 9: ...for the following applications and clearances to combustibles as shown in Table 5 Type B Oval Gas Vent Type B Oval Gas Vent is available in sizes 4 5 and 6 inch and requires a 1 inch clearance to com...

Страница 10: ...Shield In some areas the building code requires the use of an attic insulation shield AVS on single story Type B W installations Termination of Vent Structure The Ameri Vent Gas Vent is available for...

Страница 11: ...gin venting action Hold a lighted match along the rim of the draft hood relief opening of the appliance Proper venting will draw the flame up or into the draft hood Improper venting indicated by escap...

Страница 12: ...together until couplers SNAP LOCK 3 Pipes are now firmly connected FORM NO 100571D BVERO II COPYRIGHT 1999 AMERICAN METAL PRODUCTS Model O Model E and R 1 Place female coupler over preceding male coup...

Отзывы: