NAIL STRAPPING
IN PLACE
(FOUR PLACES)

NAIL THROUGH
SLOTS (FOUR
PLACES)

with Support Bracket is used. (See Fig. 9.) This provides
relief for linear thermal expansion. The adjustable length
section should be positioned directly under the Vent Pipe
section which is being supported. (NOTE: When installed
with the entire vent in a vertical position as shown in Fig.
9
, the bottom end of the adjustable length sections should
not be secured with the clamp or screws provided. This
will allow movement to compensate for expansion. See
section titled “Adjustable Length Sections” on Page 7.)

Round Support Plates

The Round Support Plate (RSP) Support is designed for
use with 9 inch diameter and larger Type B Gas Vent.
Each support is designed to support up to 30 feet of Vent
Pipe when installed as follows:

1. It is recommended that the Vent Pipe be supported at
least every other floor. The distance between supports
must not, in any case exceed 30 feet.

2. The circular cutout in the Round Support Plate is
designed to engage the uppermost recess in the female
end of the Vent Pipe. (See Fig. 10.)

3. Surround the Vent Pipe with the two identical Support
Plate halves. (See Fig. 11.) Engage the plate edges in the
uppermost pipe recess as described in Step 2. Use two
pair of bolts and nuts to hold the plate halves together.
(Four predrilled tabs are provided for this purpose.)

4. Pass Ameri-Vent Type B Gas Vent through opening in
Firestop Support (FSP).

5. NOTE: If used as a support, install Support Bracket
(SB) as shown in Fig. 6. Clamp bracket securely to pipe
section using the pair of bolts and nuts provided.

For installations with multiple supports, an adjustable
length section of Type B Gas Vent should be installed
between each pair of locations where a Firestop Support

FIG. 9

FIRESTOP SUPPORT

WITH SUPPORT BRACKET

20 FEET

MAXIMUM

20 FEET

MAXIMUM

APPLIANCE
DRAFT HOOD

ADJUSTABLE LENGTH

SECTION

FIRESTOP SUPPORT

WITH SUPPORT BRACKET

ADJUSTABLE LENGTH

SECTION

FIRESTOP SUPPORT

WITH SUPPORT BRACKET

ADJUSTABLE LENGTH

SECTION

Содержание AMERI-VENT E

Страница 1: ...NT AND ACCES SORIES ARE NOT TO BE USED WITH INCINERATORS OR WITH APPLIANCES BURNING SOLID OR LIQUID FUELS Vent sizing and installation are to be made in accordance with all applicable local building c...

Страница 2: ...eginning any lateral runs Lateral venting should be kept to a minimum to avoid vent resistance Horizontal runs to vents should either be in accordance with the appropriate tables in NFPA 54 or should...

Страница 3: ...rews Each joint of the singlewall system must be connected with three 3 sheet metal screws Singlewall connector must not penetrate any walls or ceilings or be used in any cold or non routinely inspect...

Страница 4: ...he bucket Attach the mounting tabs with sheet metal screws 3 Provide additional strapping or hangers for connector offsets Firestop Supports The Firestop Support FSP and Support Bracket SB are designe...

Страница 5: ...ports must not in any case exceed 30 feet 2 The circular cutout in the Round Support Plate is designed to engage the uppermost recess in the female end of the Vent Pipe See Fig 10 3 Surround the Vent...

Страница 6: ...sition at each opening where a support is to be used The Adjustable Length Section also provides relief for linear thermal expansion The Adjustable Length Section should be positioned directly under t...

Страница 7: ...e outer wall of the Vent Pipe and the hole cut in the structure In attics the Firestop should be placed on top of the framed ceiling opening to pre vent insulation and debris from coming into contact...

Страница 8: ...thTwo 45 Vent Elbows One One One One One One One Size A B ONLY 6 Length 12 Length 18 Length 24 Length 3 Length 4 Length 5 Length 3 3 2 3 4 3 1 4 6 3 4 11 15 1 4 19 1 2 28 36 1 2 45 4 3 7 8 3 1 16 3 1...

Страница 9: ...for the following applications and clearances to combustibles as shown in Table 5 Type B Oval Gas Vent Type B Oval Gas Vent is available in sizes 4 5 and 6 inch and requires a 1 inch clearance to com...

Страница 10: ...Shield In some areas the building code requires the use of an attic insulation shield AVS on single story Type B W installations Termination of Vent Structure The Ameri Vent Gas Vent is available for...

Страница 11: ...gin venting action Hold a lighted match along the rim of the draft hood relief opening of the appliance Proper venting will draw the flame up or into the draft hood Improper venting indicated by escap...

Страница 12: ...together until couplers SNAP LOCK 3 Pipes are now firmly connected FORM NO 100571D BVERO II COPYRIGHT 1999 AMERICAN METAL PRODUCTS Model O Model E and R 1 Place female coupler over preceding male coup...

Отзывы: