American Flame: E-Stop Gas Timer
REV. 12-28-17
FOR TECHNICAL
U.S.
INQUIRIES
CANADIAN
INQUIRIES
SERVICE:
(855) 498-8324 or (260) 459-1703
(877) 472-3923
For Sales: (888) 672-8929
Website: www.skytechpg.com
Limited Warranty
Skytech Products Group (American Flame) warrants the E-Stop Gas Timer for 12 months from the date of purchase or installation to
the original purchaser to be free from defects in materials and workmanship. It is designed for INDOOR OR OUTDOOR USE.
Damage to the E-Stop Gas Timer caused by accident, misuse, abuse, or installation error, whether per formed by a
contractor, Service Company, or owner, is not covered by this warranty. American Flame will not be responsible for labor charges
and/or damage incurred in installation, repair, replacement, or for incidental or consequential damage. Some states, provinces, and
nations do not allow exclusion or limitations of incidental or consequential damages, so the above limitations or exclusions may not
apply. This warranty gives you specific legal rights. You may also have other rights that vary by state, province, or nation.
American Flame
9230 Conservation Way
Fort Wayne, IN 46809
(260) 459-1703
Symptom
Remedy
No gas flow
1. Rotate dial beyond the "turn past" position.
2. Ensure red knob is protruding outward in ON position.
3. Has time has expired on timer? If so re-start timer again.
4. Ensure primary gas supply is turned ON.
5. Ensure the gas timer is plumbed properly.
6. Look for any physical damage.
7. Ensure other gas valves before or after the timer are operating.
8. Check inlet mesh screen for debris blockage.
Gas flow won't stop 1. Timer plumbed backwards? Check inlets and outlets on timer.
2. Excessive gas pressure exceeding the
½”
PSI maximum pressure.
3. Plumbed into both inlet lines and not one of the outlets.
4. Look for any physical damage. If so, replace timer.
Red Knob Down = Gas OFF
Red Knob Up = Gas ON
Side View
Side View
Fig. 5
E-Stop Gas Timer red knob positions
TROUBLESHOOTING