25
AD-530HS
E
LECTRICAL
S
ERVICE
S
PECIFICATIONS
(
PER POCKET
)
IMPORTANT
: 208 VAC and 230/240 VAC
ARE NOT THE SAME
.
When ordering, specify
exact voltage
.
NOTES
:
A. Fuse ratings are dual-element, time-delay, current limiting, class RK1 or RK5
ONLY
.
B. Circuit breakers are thermal magnetic (industrial) type
ONLY
. For others, calculate/verify
correct breaker size according to appliance amp draw rating and type of breaker used.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
MINIMUM
WIRE SIZE*
FUSING
CIRCUIT
BREAKER
Duel Element
Time Delay
120
1ø
2
9
14
15
15
208
1ø
2
7
14
12
15
230
1ø
2
5
14
8
15
* AWG Stranded Wire Type...for individual lengths less than 100 feet.
NOTE
:
ADC
reserves the right to make changes in specifications at any time, without notice or
obligation.
G. Gas Information
It is your responsibility to have
ALL
plumbing connections made by a qualified professional to assure that the gas
plumbing installation is adequate and conforms with local and state regulations or codes. In the absence of codes,
all plumbing connections, material, and workmanship
must conform
to the applicable requirements of the
NATIONAL FUEL GAS CODE ANSI Z223.1-LATEST EDITION, or in Canada, the CANADIAN INSTAL-
LATION CODES CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P. Gas) or LATEST
EDITION.
IMPORTANT
: Failure to comply with these codes or ordinances, and/or the requirements
stipulated in this manual can result in personal injury and improper operation of the
dryer.
The dryer and it’s individual shut-off valves
must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The dryer
must be
isolated from the gas supply piping system by closing its individual manual shut-off valves
during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5
kPa).