19
NOTE
: The distance between the dryer single ducts being connected to the main common duct
must
be
a minimum of 31-1/2 inches (the dryers width).
NOTE
: The duct work
should be
laid out in such a manner where allowances are made at the rear
area of the dryer for removal of rear service panels/guards.
IMPORTANT
:
Individual ducts being added to the main common vent must enter the main common
vent duct work at an angle not more than 45º in the direction of the airflow.
The above illustration
[MAN2172]
shows the minimum cross-section area for multiple (common) dryer venting.
The maximum length of venting from the last dryer to where it exhausts is the following:
VERTICAL
----------venting run
must not
exceed eight (8) feet.
HORIZONTAL
-----venting run
must not
exceed fifteen (15) feet.