20
These figures
must be
increased in proportion if the main duct run from the last dryer has numerous elbows or is
unusually long. For extended runs or where more elbows are added, the cross-sectional area of the duct can only
be increased to an extent and a professional HVAC firm
should be
consulted for proper venting information.
IMPORTANT
:
Exhaust back pressure measure by a manometer at the dryer exhaust duct
must
not
exceed 0.3 inches of water column when both baskets (tumblers) are operating.
NOTE
:
Inspection doors
should be
installed at strategic points in the exhaust duct work for periodic
inspection and cleaning.
b. Multiple Dryer Venting -
where tumblers of each dryer “Y” together.
With multiple venting where the top basket (tumbler) and bottom basket (tumbler) are connected or “Y” together
as described in
Section E1
(page 12 through page 14), the minimum diameter size at the “Y” (point of connec-
tion) and main common duct is 10-inches in diameter (80 square inches cross-sectional). This duct run
cannot
exceed eight (8) feet in length.