PURE 2.0 OPERATING INSTRUCTIONS

 

08/21/19 

4211-1430 

Page 4 of 4 

Mounting the Control 

 

Install the PURE 2.0 control inside or outside the steam room using the control cable previously  

installed If mounting to a smooth, flat wall, the adhesive pad provided will work well to mount the  

control and seal the cable hole. 

The adhesive will stick to the wall quickly so be sure to accurately  

place  

and level the control before attaching it to the wall!

  

 

If the surface is uneven or has grout lines, we recommend using a small amount of silicone 

to mount the PURE 2.0 control. If using silicone, run a bead around the control’s cable end  

and another bead around the back of the control as shown here. Then tape in place 

on the wall until the silicone has set up.  

 

Connect the cable to the control’s cable end, slide the cable  

into the wall, and mount the control.  

 

 

Be sure to carefully level the control while mounting!  

 
 

Troubleshooting 

 

The PURE 2.0 has error displays to assist with troubleshooting. If an error should occur in the steamer or other 

equipment (PURE 2.0 control, temperature sensor, etc.) an error message will be shown using LED indicators. 

The indicator LEDs will flash while one LED on the 1-10 scale is continuously lit or flashing. The lit 1-10 LED 

indicates the error: steady = #1 -10, flashing indicates #11-20. 

Some errors are not applicable to steam and are 

not listed here.

 

 

Error messages: 

   

1

 Temperature sensor not connected or faulty. 

Check the sensor and sensor cable for loose/bad

 

connections or 

      damage.

 

   

3

 Steamer circuit board overheated 

   

6

 Contact between heater and control lost.

 Check the control cable for loose/bad

 

connections or damage. 

 12 

Level sensing faulty. 

Check level probe wiring; clean level probe.

 

 14

 Temperature sensor faulty. 

Check the sensor and sensor cable for loose/bad

 

connections or damage.

 

 15

 Communication problem with steamer. 

Check the control cable for loose/bad

 

connections or damage.

 

 

For some errors, turning off power to the steamer for a brief period and then turning it back on again may correct 

the error. This mostly concerns problems that have occurred with communication between the steamer and 

control.  

 

In the event of error number 3, the steam bath will be automatically switched off. When the circuit board 

temperature has dropped approx. 68°F (20°C), the steam bath can be restarted. Always investigate why the 

steamer overheated. It can be the result of insufficient ventilation or too high a temperature around the steam 

generator. 

 

Some errors will cause the      Door indicator or      Start indicator to light or blink red. 

Make sure water is getting 

in to the steamer and that the drain is working well

 

Contact technical support for other error codes or if an error cannot be corrected according to the above.  

 

 

For further assistance, contact 

 

ADHESIVE 

SILICONE 

OR 

P.O. Box 2258, Woodinville, WA 98072 

Phone 1-800-363-0251 

            1-425-951-1120 

Fax      1-425-951-1130 

eMail   [email protected]

 