INSTALLATION AND OPERATING INSTRUCTIONS

72-0106    02-26-16                                                                                                                                                                                                                            

                               7013482      314 SKSM 215 B

Page 2

DIAGRAM 1

MOUNTING BRACKET LOCATION AND MINIMUM DISTANCE TO COMBUSTIBLE MATERIAL

C

High Limit Control

D

2"

1"

18½"

74"

Minimum

Screws

6"

14 3/8" B

10½"

Use the long screws in the upper 
holes of the mounting bracket

A

6½"

Min.

5"

Temperature

Sensor

44"

Minimum

Guard

Rail

(Upper Bench)

K

Recheck your distances from the heater to 
combustible  materials to be sure you have 
the proper minimum distances. 

NOTE 1: Neutral is required for heater and Control light supplies a maximum of 2 amps for light circuit.

DIAGRAM 2

OBSERVING MINIMUM DISTANCES IS REQUIRED 
TO REDUCE THE RISK OF FIRE 

"A"

DISTANCE

"B"

DISTANCE

"C"

DISTANCE

"D"

DISTANCE

"K"

DISTANCE

Designer 4.5

3.0"

3 5/8"

4.0"

11 1/2"

23"

Designer 6.0

4.0"

4 5/8"

5.0"

11 1/2"

23"

Designer 8.0

5.0"

5 5/8"

6.0"

11 1/2"

23"

HEATER

MINIMUM

WIRE SIZE

Floor Area

Ceiling 

Height

Volume

Cu.Ft.

Ceiling 

Height

Volume 

Cu.Ft.

Power Supply to 

Heater

1

208

21.6

2 #10AWG+N+GR 

1

240

18.8

2 #10AWG+N+GR 

3

208

12.5

3 #12AWG+N+GR 

3

240

10.8

3 #12AWG+N+GR 

1

208

28.8

2 #8AWG+N+GR 

1

240

25

2 #10AWG+N+GR 

3

208

16.7

3 #12AWG+N+GR 

3

240

14.4

3 #12AWG+N+GR 

1

208

38.5

2 #8AWG+N+GR 

1

240

33.3

2 #8AWG+N+GR 

3

208

22.2

3 #10AWG+N+GR 

3

240

19.2

3 #10AWG+N+GR 

310

Designer 

Trend 8.0 

1712-80-1706

8.0

31 sq. ft.

74"

250

96"

425

Designer 

Trend 6.0 

1712-60-1706

6.0

21 sq. ft.

74"

175

96"

AMPS

Light 

Circuit 

Supply

Designer 

Trend 4.5 

1712-45-1706

4.5

12 sq. ft.

74"

100

96"

210

S

e
e

 

N
o

t

e

 

1

 

B

e

l

o

w

HEATER 

MODEL

 / 

Product 
Number

KW

MINIMUM ROOM

MAXIMUM ROOM

PHASE

VAC

Содержание Designer 4.5

Страница 1: ...ntrol Type 1601 31 and 1601 31 1 Read all instructions carefully before installation Please leave all instructions and warranty with the owner WARNING Prolonged exposure to elevated temperatures is ca...

Страница 2: ...STANCE B DISTANCE C DISTANCE D DISTANCE K DISTANCE Designer 4 5 3 0 3 5 8 4 0 11 1 2 23 Designer 6 0 4 0 4 5 8 5 0 11 1 2 23 Designer 8 0 5 0 5 5 8 6 0 11 1 2 23 HEATER MINIMUM WIRE SIZE Floor Area Ce...

Страница 3: ...rvice to this equipment should be performed by quali ed licensed personnel in accordance with local and national codes Do not construct sauna room so as to restrict air ow through the bottom of the he...

Страница 4: ...above the heater Insert screwdriver tip here to unsnap sensor cover from sensor Note vertical orientation of cover before removing Diagram 4 was intentionally left blank Sensor protective cover Locat...

Страница 5: ...2 3 02 26 2016 P1 P2 P3 1 3 5 7 A1 2 4 6 8 A2 X1 X2 X3 X5 X7 X4 X6 X8 X9 X10 N N H Trans former 120 Volt Light Output 2 0 Amp Max Connect L1 to terminals 1 2 and 5 Connect L2 to terminals 3 4 and 6 C...

Страница 6: ...26 2016 P1 P2 P3 1 3 5 7 A1 2 4 6 8 A2 X1 X2 X3 X5 X7 X4 X6 X8 X9 X10 N N H 2 3 Trans former 120 Volt Light Output 2 0 Amp Max 3 Phase Connection Connect L1 to terminals 1 and 2 Connect L3 to terminal...

Страница 7: ...the control and push any excess cable into wall cavity before securing control to the wall Maximum control cable length is 50 feet Remove the adhesive tape from the back of the the control place the c...

Страница 8: ...stopped Some sauna bathers enjoy the soothing effect of steam by splashing water on the heated sauna rocks Use only one dipper full approx cup at a time and keep clear of the steam as it rises off the...

Страница 9: ...and the outer wall will reduce cycling of the heater b Rocks must be placed between the elements and the wall of the rock compartment Incorrect Placement of Rocks a Loosely place rocks between the ele...

Страница 10: ...The enclosed CAUTION Reduce the risk of re caution plate must be mounted on the interior wall above the heater The heater should not be operated without its container properly lled with rocks and the...

Страница 11: ...a oor mopped and dried in a conventional manner and the duckboard thoroughly scrubbed and dried before returning to the sauna room The sauna heater should be wiped down occasionally with a damp cloth...

Страница 12: ...scale of the control The fault error code will be displayed with a constant LED light or a ashing LED light See the list below for fault codes Constant LED Fault Code ones marked with n a are not in...

Отзывы: