30
AMC VIBRATION SENSOR / ©AMC VIBRO Sp. z o.o.
7.5.
Events
As mentioned- the GATEWAY monitors all network devices and occurrences by them reported. It reacts
to exceeding measured values above the thresholds of warnings and alarms. These occurrences are listed
in the Events tab. You can choose a sensors to view alerts. There are the following options to choose:
»
From Date – allows you to choose a date since you will be viewing events. Otherwise all possible
will be displayed
»
Source – the source of occurrence: All, Channel X or Channel Y
»
State – All - if all alerts are displayed - past and present or Current – if only still ongoing alerts
are displayed
»
Type – Warnings or Alarms or All
»
Estimate – a kind of estimate which is the source of occurrence / alert
Start date parameter informs when the occurrence began and the End date parameter informs when the
occurrence was stopped.
Figure 25. Events tab
7.6.
Modbus and OPC protocols
Due to AVM GATEWAY functionality measurement data can be readed in various ways. For example they
can be applications to Modbus client or OPC UA client.
By using the GATEWAY you can have access to all current data via Modbus TCP / IP - port 502, function
03 Read Holding Registers. Table 9 shows the Modbus registers of the AVS 2000R, ID number = 1.
The registers available for reading via the GATEWAY for subsequent IDs are shifted by a number equal
to:
2025 + 58 * (ID of AVS 2000R - 1)
Содержание AVM GATEWAY
Страница 13: ...13 AMC VIBRATION SENSOR AMC VIBRO Sp z o o Figure 6 AVS 2000R dimensions in millimeters ...
Страница 18: ...18 AMC VIBRATION SENSOR AMC VIBRO Sp z o o Figure 9 Sensor configuration part 1 ...
Страница 27: ...27 AMC VIBRATION SENSOR AMC VIBRO Sp z o o Figure 21 Data plot Figure 22 Data tab Current Values ...
Страница 34: ...34 AMC VIBRATION SENSOR AMC VIBRO Sp z o o Figure 27 The OPC structure for the Vibration sensor ...