Ambirad VISION COMPACT Series Скачать руководство пользователя страница 9

7

Inspect installation and ensure that it has
been carried out in accordance with these
instructions.  Ensure that electrical and gas
supplies are isolated.  The gas supply should
be purged and tested for soundness in
accordance with the BS6891:1988, BGIM/16,
IGE Report 1M/2 and any other British
Standard and Codes of Practice.  Open 
isolating valve.

Remove the combustion chamber cover
plate by unscrewing 6 fixing screws.  Take
care not to damage the sealing gasket.  

Open the control housing cover by 
unscrewing the securing screws.  Ensure all
internal components are securely fixed and
all connections securely made.

Switch on the electrical supply to the heater
and observe the correct start up sequence as
follows:

The mains lamp (red) will illuminate.  The ID
fan will start to run and the vacuum switch
checking relay (inside flame electronic
sequence control box) will pull in.  Safe start
checks are carried out automatically and a
purge period of approximately 9 seconds will
commence.

At the end of the purge period the ignition
sequence will commence.  The spark ignition
will be energised producing a spark at the
ignition electrode.  The gas shut off valve

will at the same time be energised.  If 
ignition is successful the flame is detected
by the flame sensing probe and the ignition
spark will be switched off.  The ‘burner on’
(amber) lamp indicates that the gas safety
control valves are energised.

If the ignition is unsuccessful the gas safety
control valve is closed and the spark ignition
de-energised after approximately 5 - 7 
seconds.  

After an unsuccessful ignition attempt the
electronic sequence controller will ‘lock out’.
The ‘power lamp’ (red) only will remain 
illuminated and the fan will continue to run.
To reset this ‘lock out’ condition, switch the
power supply to the heater, wait 5 seconds
then restore it.  If repeated lock out occurs
investigate cause.

In the event of an electrical fault after
installation of the appliance preliminary
electrical systems checks should be carried
out (re earth continuity polarity and 
resistance to earth).

To shut down the heater, switch off the
power supply to the heater.  Automatic 
control of the heater or a series of heaters
may be achieved by incorporating 
thermostats, time switches, frost 
thermostats, manual over-ride switches etc,
in the electrical supply to the heater(s).  It is
essential to allow a delay of 15 seconds
after switching off a heater before 
attempting to restart.

If at any time after completion of the start
up sequences, loss of flame should occur,
the electronic sequence controller will
attempt to re-ignite.  If this is unsuccessful
lock out will occur.

Set burner gas pressure as follows:

Isolate gas supply.  Unplug mains input 
connector to heater.  

12  Commissioning for 
individually flued and unflued
heaters

When the Vision Compact heater is to be
installed in locations where there is airborne
dust or where there is a polluted atmos-
phere e.g. chlorinated vapours, process dust
etc., a ducted fresh air supply must be pro-
vided to the burner.  Where a fresh air duct-
ed inlet is to be fitted to the burner assem-
bly the aluminised steel air intake grill must
be removed from the burner casing and the
D/A fitting attached over the burner orifice
plate.

These models incorporate a 100mm (4in)
fresh air duct connection (Pt. No. 
M201601-SUB).  A fresh air duct of 
minimum 100mm (4in) diameter should be
connected to the D/A duct. A flexible joining
piece should be used, available from the
manufacturer (Pt. No. 7531), fixed with hose
clips to facilitate disconnection when 
servicing the burner.

The maximum length of fresh air inlet duct
is 7 m of 100mm (4in) diameter duct, the
maximum number of bends is two. The fresh
air inlet duct can be installed either 
vertically or horizontally.  A position should
be selected for the inlet of the fresh air duct
so that it will receive dust free clean air.  A
cowl of the British Gas tested and certified
type, such as the GCI or GLC terminal,
should be fitted at the inlet of the duct.  If
the duct inlet is located on a roof the
underside of the inlet cowl must be at least
600mm (2ft) above roof level and at least
250mm (10in) higher than any projection on
the roof within a 2m radius of the cowl. 

11  Fresh air ducted inlet (all
models)

Figure 5  

Figure 6  

Figure 7  

Содержание VISION COMPACT Series

Страница 1: ...Operation maintenance and servicing manual VC12 VC20 GAS FIRED RADIANT TUBE HEATERS VISION COMPACT...

Страница 2: ...f Vision Compact heaters Flue connection Fresh air ducted inlet all models Commissioning for individually flued and unflued heaters Routine service Herringbone adjustment Replacement of components Tro...

Страница 3: ...lations 1998 Due account should also be taken of any obligations arising from the Health and Safety at Works etc Act 1974 In addition the installation must be carried out in accordance with the curren...

Страница 4: ...ded by the institute of Gas Engineers the manufacturer and Ambi Rad Ltd These instructions must be carried out in accordance with the relevant provisions of the gas safety installation and use regulat...

Страница 5: ...leaflets Circuits and controls All such controls and switchgear must be rated to handle the total inductive load of the circuit they control Load per Ambi Rad heater is 0 55 amp For large installatio...

Страница 6: ...ade to good sound engineering practice or of a proprietary type fixing They must be adequately fixed and designed to carry the whole weight of the heater In the event of suitable roof steelwork not be...

Страница 7: ...n installing the heater at an angle the combustion fan outlet should be positioned so that it remains vertical It is recommended that sufficient clearance from any fixed structure e g a wall is given...

Страница 8: ...e in operation carry out a flow visualisation check using a smoke producing device e g smoker match puffer or joss stick The device shall produce an even trace so that the flow can be observed and the...

Страница 9: ...and resistance to earth To shut down the heater switch off the power supply to the heater Automatic control of the heater or a series of heaters may be achieved by incorporating thermostats time switc...

Страница 10: ...tions but in exceptional dusty or polluted conditions more frequent servicing may be required The manufacturer offers a maintenance service Details are available on request Tools required for servicin...

Страница 11: ...country that the appliance is installed For servicing of injector electrode assembly refer to Section 14 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Remove the 2 M6 bolts and 2 M5 screws securi...

Страница 12: ...d pipe at the gas valve Figure 18 Figure 19 Remove the fixing screws securing the controls cover to the burner assembky and the side of the product Remove the controls cover Slide the burner assembly...

Страница 13: ...is 3 5mm or 0 5mm Replace burner head and injector if necessary and re fit components in reverse order of removal Disconnect connectors on gas valve from wiring harness and remove silicon tube Figure...

Страница 14: ...e wiring harness and the ignition high tension lead Remove the plastic push clips and replace the controller Re fit in reverse order of removal ensuring electrical connections are made Figure 29 S I T...

Страница 15: ...nd 7 of burner control unit plug A reading of 10 000 ohms indicates short circuit on gas valve burner indicator light or associated wiring HB Herringbone system only Leaks in joint separation in manif...

Страница 16: ...mbly 200191 Pressure switch SIT or EAC M101355 VC20 Natural gas G20 only 3 8mm injector 2290 Burner orifice plate 200520 Burner support spinning 200568 SUB VC20 Propane G31 only 2 3mm injector 2281 2...

Страница 17: ...actual or proposed flue measured from the flue spigot 7 7 other resistances of actual flue terminal 1 0 6 0 25 90 bend 0 0 0 135 bend 0 0 0 flue pipe 5 46 1 75 6 06 2 He 2 50 6 22 Note 1m of actual fl...

Страница 18: ...Figure 30 Example layout of a typical flue arrangement Example Layout Of A Typical Flue Arrangement GCI Terminal Heater 1 0 m min 7 0 m max Spigot 16...

Страница 19: ...occurs again switch off heater and call out a service engineer Note U bend will glow but this is acceptable To switch off Vision Compact heater 1 Switch off electrical supply to the heater The burner...

Отзывы: