Ambirad VISION COMPACT Series Скачать руководство пользователя страница 12

10

Figure 16

Figure 17

Health and Safety

Isolate gas and electrical supplies before
carrying out any repair work.  Always test
for gas soundness with a suitable leak
detection fluid.

Replacement parts

Any spare part components that are not
approved by Ambi-Rad could invalidate the
approval of the appliance and operation of
the warranty.

It is recommended that the burner assembly
is removed from the product to facilitate
replacement of the following components:

Burner head
Injector
Gas valve
Electrode assembly
Vacuum switch
Electronic sequence controller

To remove the burner assembly proceed as
follows

Withdraw the mains and fan male 
connectors/leads from the female 
connectors on the burner assembly.  Isolate
the gas supply and disconnect the gas feed
pipe at the gas valve.

Figure 18

Figure 19

Remove the fixing screws securing the
controls cover to the burner assembky and
the side of the product.  Remove 
the controls cover.

Slide the burner assembly back towards the
side of the product until the burner spigot
disengages from thefiring tube and the end
of the spigot is clear of the inner face of the
controls divider plate.  Lift the burner
assembly from the product.

With the burner assembly removed from the
product it is now possible to replace 
components as follows:

15  Replacement and servicing of components in the burner assembly

INJECTOR

GASSAFETY CONTROL

VALVE

GASPRESSURE

TEST PIPE

GASSUPPLY

3PINFAN
SOCKET

BURNERHEAD
P/N3035

ELECTRODE/IGNITOR

ASSEMBLY

BURNER ASSEMBLY

SUPPORT SPINNING

VACUUM

PROVINGSWITCH

PRESSURESENSING

TUBES

3PINMAINS
SOCKET

ELECTRONICSEQUENCE
CONTROLLER

COMBUSTIONCHAMBER

SAFETY CONTROL

HOUSING

AIRINTAKEGUARD

NEONS

Figure 11  Vision Compact burner assembly

Содержание VISION COMPACT Series

Страница 1: ...Operation maintenance and servicing manual VC12 VC20 GAS FIRED RADIANT TUBE HEATERS VISION COMPACT...

Страница 2: ...f Vision Compact heaters Flue connection Fresh air ducted inlet all models Commissioning for individually flued and unflued heaters Routine service Herringbone adjustment Replacement of components Tro...

Страница 3: ...lations 1998 Due account should also be taken of any obligations arising from the Health and Safety at Works etc Act 1974 In addition the installation must be carried out in accordance with the curren...

Страница 4: ...ded by the institute of Gas Engineers the manufacturer and Ambi Rad Ltd These instructions must be carried out in accordance with the relevant provisions of the gas safety installation and use regulat...

Страница 5: ...leaflets Circuits and controls All such controls and switchgear must be rated to handle the total inductive load of the circuit they control Load per Ambi Rad heater is 0 55 amp For large installatio...

Страница 6: ...ade to good sound engineering practice or of a proprietary type fixing They must be adequately fixed and designed to carry the whole weight of the heater In the event of suitable roof steelwork not be...

Страница 7: ...n installing the heater at an angle the combustion fan outlet should be positioned so that it remains vertical It is recommended that sufficient clearance from any fixed structure e g a wall is given...

Страница 8: ...e in operation carry out a flow visualisation check using a smoke producing device e g smoker match puffer or joss stick The device shall produce an even trace so that the flow can be observed and the...

Страница 9: ...and resistance to earth To shut down the heater switch off the power supply to the heater Automatic control of the heater or a series of heaters may be achieved by incorporating thermostats time switc...

Страница 10: ...tions but in exceptional dusty or polluted conditions more frequent servicing may be required The manufacturer offers a maintenance service Details are available on request Tools required for servicin...

Страница 11: ...country that the appliance is installed For servicing of injector electrode assembly refer to Section 14 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Remove the 2 M6 bolts and 2 M5 screws securi...

Страница 12: ...d pipe at the gas valve Figure 18 Figure 19 Remove the fixing screws securing the controls cover to the burner assembky and the side of the product Remove the controls cover Slide the burner assembly...

Страница 13: ...is 3 5mm or 0 5mm Replace burner head and injector if necessary and re fit components in reverse order of removal Disconnect connectors on gas valve from wiring harness and remove silicon tube Figure...

Страница 14: ...e wiring harness and the ignition high tension lead Remove the plastic push clips and replace the controller Re fit in reverse order of removal ensuring electrical connections are made Figure 29 S I T...

Страница 15: ...nd 7 of burner control unit plug A reading of 10 000 ohms indicates short circuit on gas valve burner indicator light or associated wiring HB Herringbone system only Leaks in joint separation in manif...

Страница 16: ...mbly 200191 Pressure switch SIT or EAC M101355 VC20 Natural gas G20 only 3 8mm injector 2290 Burner orifice plate 200520 Burner support spinning 200568 SUB VC20 Propane G31 only 2 3mm injector 2281 2...

Страница 17: ...actual or proposed flue measured from the flue spigot 7 7 other resistances of actual flue terminal 1 0 6 0 25 90 bend 0 0 0 135 bend 0 0 0 flue pipe 5 46 1 75 6 06 2 He 2 50 6 22 Note 1m of actual fl...

Страница 18: ...Figure 30 Example layout of a typical flue arrangement Example Layout Of A Typical Flue Arrangement GCI Terminal Heater 1 0 m min 7 0 m max Spigot 16...

Страница 19: ...occurs again switch off heater and call out a service engineer Note U bend will glow but this is acceptable To switch off Vision Compact heater 1 Switch off electrical supply to the heater The burner...