L33354-XA28UEN-E1-S01, REV. A   CLOSED-LOOP TUNING
Copyright © 2020 Amatrol, Inc.

S01-9

SKILL 1   TUNE A CONTROL LOOP USING THE AUTO-TUNE METHOD

G.  Plot the response using the data you collected in substep D. 

 

Your response curve should be similar to the ones in figure 1-12 for PV in inches or figure 1-13 for PV in cm.

 

The initial value for your response curve will vary depending on how much the level dropped while you were 
calculating the new tuning parameters. Your response may have little overshoot, which is good also.

Figure 1-11.  Response of the System (PV in inches)

Figure 1-12.  Response of the System (PV in cm)

2.3

2.2

2.1

2.0

1.9

1.8

1.7

1.5

1.6

1.4

1.3

1.2

1.1

1.0

0

70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300

60

50

40

30

20

10

PV

(INCHES)

TIME
(SECONDS)

SP

0

70 80 90 100 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300

60

50

40

30

20

10

PV

(cm)

TIME
(SECONDS)

SP

4.75

5.0

4.25

4.5

3.75

4.0

3.5

5.5

5.75

5.25

Содержание 990-PC1

Страница 1: ...out tagout 2 Perform the following substeps to set up the 990 PC1 as shown in figure 1 1 NOTE The appearance of the electrical outlet will differ based on the electrical power supplied at your locatio...

Страница 2: ...e D Close fully clockwise the two process tank manual drain valves HV 300 HV3 and HV 100C HV4 E Open fully counterclockwise the manual flow control valve FV 100 HFV F Open fully counterclockwise the f...

Страница 3: ...tive components and wiring are highlighted Figure 1 4 990 PC1 P ID 24 VDC CONTROLLER INPUTS PRESSURE SENSOR CONTROLLER OUTPUT 4 20mA I P CONVERTER DC POWER SUPPLY PB1 PB2 AI1 LT1 A01 FV1 CIRC PUMP P1...

Страница 4: ...Press the P key which accepts that value and goes to the next parameter When a parameter is showing use the up or down arrow keys to change the value and press the P key to accept that value and move...

Страница 5: ...ameters Module shows N With 3 LC displaying press the P key to enter the lockout parameters module O Configure the lockout parameters to have the values show in figure 1 7 Module 3 Lockout Parameters...

Страница 6: ...D If the PV value on the display is not approximately 0 00 then adjust the value in the display shift offset SHFt parameter which is in the input parameters module 1 In E If not in the display loop p...

Страница 7: ...process tank until the level is about 3 5 cm or 1 5 in C Open the solenoid drain valve SV 100C SV3 PB2 on D Start the circulation pump PB1 on E Record the value of the PV every five seconds in a tabl...

Страница 8: ...to plot the response of the system Figure 1 9 Graph of PV inches vs Time Figure 1 10 Graph of PV cm vs Time 2 3 2 2 2 1 2 0 1 9 1 8 1 7 1 5 1 6 1 4 1 3 1 2 1 1 1 0 0 70 80 90 100 110 120 130 140 150...

Страница 9: ...l dropped while you were calculating the new tuning parameters Your response may have little overshoot which is good also Figure 1 11 Response of the System PV in inches Figure 1 12 Response of the Sy...

Страница 10: ...llations C Determine if the process is currently too slow and sluggish If you determine it is too sluggish the proper correction depends on the cause of the sluggishness If the proportional band is se...

Отзывы: