L33354-XA28UEN-E1-S01, REV. A   CLOSED-LOOP TUNING
Copyright © 2020 Amatrol, Inc.

S01-4

SKILL 1   TUNE A CONTROL LOOP USING THE AUTO-TUNE METHOD

3.  Remove the lockout/tagout.

4.  Press pushbutton switch 

PB1

 to the off (out) position.

 

PB1 is used to turn the circulation pump on and off.

5.  Perform the following substeps to configure the parameters in the PID controller as a closed loop system.

 

Typically, most of the parameters will already be configured as needed. 

A.  Turn on the main circuit breaker to apply power to the system.

B.  Press and hold the 

P

 key for 3 seconds to go to the hidden loop and the configuration loop.

 

Typically, tunE will appear if additional parameters have not been hidden.  

C. Press the 

P

 key repeatedly until 

CnFP

 (configuration loop) displays in the lower display area.

D.  With CnFP/no displaying, press the up 

 arrow key to enter the configuration loop.

 

The first parameter group to display is the input parameters module (1-In).

E.  Press the up 

 arrow to go to the

 1-In

 (input menu), if 1-In is not already showing.

F.  With 1-In displaying, press the 

P

 key to enter the input parameters module.

 

The first parameter, which is input type (tyPE), will display.

G.  Under type, use the up 

 or down 

 arrow keys to change the parameter to

 4-20

 (4-20 mA input).

H. Press the 

P

 key, which accepts that value and goes to the next parameter.

 

When a parameter is showing, use the up 

 or down 

 arrow keys to change the value and press the 

P

 key to 

accept that value and move to the next parameter. 

I.  Continue configuring the input parameters to have the values shown in figure 1-5.

 

When dual values are shown in the setting column, the first number is in centimeters, and the second number is in 
inches. You will use one or the other. If you are not sure which one to use, ask your instructor.

Module 1-Input Parameters (1-In)

Parameter

Description

Setting (cm/in.)

tyPE

Input type

4-20

dCPt

Decimal resolution

0.00

FLtr

Digital fi ltering

8

bANd

Input fi lter band

.1

SHFt

Shift/offset

-1.8

dSP1

Display value scaling point 1 (low)

0.00

dSP2

Display value scaling point 2 (high)

70.36/27.70

SPLO

Setpoint low limit

1.00/0.50

SPHI

Setpoint high limit

6.50/2.50

USr1

User input function 1

SPSL

USr2

User input function 2

ALrS

F1In

F key function 1

Trnf

F2In

F key function 2

None

Figure 1-5.  Input Parameter Values

 

Notice that the setting for dCPt (decimal resolution) is 0.00, which means two decimal places. This two-decimal 
place setting will apply to other parameter settings that take decimal places.

 

Once the last parameter is entered for that module, the display will return to CnFP. 

J.  Press the up 

 arrow key until 

2-OP

 (Output Parameters Module) shows.

K.  With 2-OP displaying, press the 

P

 key to enter the output parameters module.

Содержание 990-PC1

Страница 1: ...out tagout 2 Perform the following substeps to set up the 990 PC1 as shown in figure 1 1 NOTE The appearance of the electrical outlet will differ based on the electrical power supplied at your locatio...

Страница 2: ...e D Close fully clockwise the two process tank manual drain valves HV 300 HV3 and HV 100C HV4 E Open fully counterclockwise the manual flow control valve FV 100 HFV F Open fully counterclockwise the f...

Страница 3: ...tive components and wiring are highlighted Figure 1 4 990 PC1 P ID 24 VDC CONTROLLER INPUTS PRESSURE SENSOR CONTROLLER OUTPUT 4 20mA I P CONVERTER DC POWER SUPPLY PB1 PB2 AI1 LT1 A01 FV1 CIRC PUMP P1...

Страница 4: ...Press the P key which accepts that value and goes to the next parameter When a parameter is showing use the up or down arrow keys to change the value and press the P key to accept that value and move...

Страница 5: ...ameters Module shows N With 3 LC displaying press the P key to enter the lockout parameters module O Configure the lockout parameters to have the values show in figure 1 7 Module 3 Lockout Parameters...

Страница 6: ...D If the PV value on the display is not approximately 0 00 then adjust the value in the display shift offset SHFt parameter which is in the input parameters module 1 In E If not in the display loop p...

Страница 7: ...process tank until the level is about 3 5 cm or 1 5 in C Open the solenoid drain valve SV 100C SV3 PB2 on D Start the circulation pump PB1 on E Record the value of the PV every five seconds in a tabl...

Страница 8: ...to plot the response of the system Figure 1 9 Graph of PV inches vs Time Figure 1 10 Graph of PV cm vs Time 2 3 2 2 2 1 2 0 1 9 1 8 1 7 1 5 1 6 1 4 1 3 1 2 1 1 1 0 0 70 80 90 100 110 120 130 140 150...

Страница 9: ...l dropped while you were calculating the new tuning parameters Your response may have little overshoot which is good also Figure 1 11 Response of the System PV in inches Figure 1 12 Response of the Sy...

Страница 10: ...llations C Determine if the process is currently too slow and sluggish If you determine it is too sluggish the proper correction depends on the cause of the sluggishness If the proportional band is se...

Отзывы: