L33354-XA28UEN-E1-S01, REV. A   CLOSED-LOOP TUNING
Copyright © 2020 Amatrol, Inc.

S01-6

SKILL 1   TUNE A CONTROL LOOP USING THE AUTO-TUNE METHOD

6.  Perform the following substeps to configure the PID values.

A. Press the 

P

 key to go to the parameter loop.  

B. Press the 

P

 key repeatedly until 

PId

 displays.

C.  Press the up 

 or down 

 arrow keys to change the value to 

1

 (group 1).

NOTE

In this procedure, you are only configuring one profile, which is profile 1. However, a process in a plant may require 
several steps. For example, the first step may need the level to ramp up from 1 m to 8 m in 10 minutes. Then it 
needs to soak at 8 m for 20 minutes. Then the level needs to ramp down to 1 m in 10 minutes. Finally, it needs to 
soak at 1 m for 30 minutes. Many PID controllers allow you to use a different PID profile for each step and program 
each profile separately.

D. Press the 

P

 key repeatedly until 

ProP

 (proportional band value) displays.

E.  Press the up 

 or down 

 arrow keys to change the value to 

1.5

.

F. Press the 

P

 key repeatedly until 

Intt

 (integral time value) displays.

G.  Press the up 

 or down 

 arrow keys to change the value to 

32

.

H. Press the 

P

 key repeatedly until 

dErt

 (derivative time value) displays.

I.  Press the up 

 or down 

 arrow keys to change the value to 

0

.

J. Press the 

P

 key.

7.  Perform the following substeps to verify the correct zero level is displaying.

A.  Open manual drain valve 

HV 100C

 (

HV4

), which is the drain valve on the right.

B. Turn on 

PB1

 to run the pump for about 15 seconds and then turn 

PB1

 off.

C. Close 

HV 100C

 (

HV4

). 

D.  If the PV value on the display is not approximately 0.00, then adjust the value in the display shift/offset (SHFt) 

parameter, which is in the input parameters module (1-In). 

E.  If not in the display loop, press the 

D

 key to show the main display.

 

The setpoint value will show in the lower line on the display.

F.  Use the up 

 and down 

 arrow keys to adjust the setpoint value to 

3.5

 (if using centimeters) or 

1.5

 (if using 

inches).

8.  Perform the following steps to adjust the water level in the process tank so that it will not adversely affect the response 

plots in this skill.

A.  Start the circulation pump by pressing 

PB1

 to the 

ON

 position.

B.  Monitor the water level in the process tank. When it reaches approximately 3.5 cm (1.5 in.) in both the left and right 

sides of the tank, press 

PB1

 to the 

OFF

 position to turn off the circulation pump.

C.  Press PB2 to the 

OFF

 position.

 

The water should remain in both sides of the process tank.

D.  Adjust the setpoint to

 5.0

 cm (

2.0

 in.).

9.  Perform the following substeps to auto-tune the PID controller.

A.  Press and hold the 

P

 key to enter the hidden loop.

B.  Insure that auto control mode (

CtrL

) is set to 

PID

.

C.  Insure that control mode transfer (

trnF

) is set to 

Auto

D.  Turn on PB1 and PB2 to start the pump and turn on the solenoid valve.

E.  Change the auto-tune start (

tUnE

) setting to 

YES

.

 

You may need to re-enter the hidden loop to find tUne. This starts the auto-tuning process, which may take a few 
minutes. During this time AT will flash on and off on the left side of the display. The AT will stop flashing when the 
auto-tuning is complete. If the auto-tuning takes way too long, you may stop it by changing the value of tUne from 
YES to nO. It should finish auto-tuning within four minutes.

Содержание 990-PC1

Страница 1: ...out tagout 2 Perform the following substeps to set up the 990 PC1 as shown in figure 1 1 NOTE The appearance of the electrical outlet will differ based on the electrical power supplied at your locatio...

Страница 2: ...e D Close fully clockwise the two process tank manual drain valves HV 300 HV3 and HV 100C HV4 E Open fully counterclockwise the manual flow control valve FV 100 HFV F Open fully counterclockwise the f...

Страница 3: ...tive components and wiring are highlighted Figure 1 4 990 PC1 P ID 24 VDC CONTROLLER INPUTS PRESSURE SENSOR CONTROLLER OUTPUT 4 20mA I P CONVERTER DC POWER SUPPLY PB1 PB2 AI1 LT1 A01 FV1 CIRC PUMP P1...

Страница 4: ...Press the P key which accepts that value and goes to the next parameter When a parameter is showing use the up or down arrow keys to change the value and press the P key to accept that value and move...

Страница 5: ...ameters Module shows N With 3 LC displaying press the P key to enter the lockout parameters module O Configure the lockout parameters to have the values show in figure 1 7 Module 3 Lockout Parameters...

Страница 6: ...D If the PV value on the display is not approximately 0 00 then adjust the value in the display shift offset SHFt parameter which is in the input parameters module 1 In E If not in the display loop p...

Страница 7: ...process tank until the level is about 3 5 cm or 1 5 in C Open the solenoid drain valve SV 100C SV3 PB2 on D Start the circulation pump PB1 on E Record the value of the PV every five seconds in a tabl...

Страница 8: ...to plot the response of the system Figure 1 9 Graph of PV inches vs Time Figure 1 10 Graph of PV cm vs Time 2 3 2 2 2 1 2 0 1 9 1 8 1 7 1 5 1 6 1 4 1 3 1 2 1 1 1 0 0 70 80 90 100 110 120 130 140 150...

Страница 9: ...l dropped while you were calculating the new tuning parameters Your response may have little overshoot which is good also Figure 1 11 Response of the System PV in inches Figure 1 12 Response of the Sy...

Страница 10: ...llations C Determine if the process is currently too slow and sluggish If you determine it is too sluggish the proper correction depends on the cause of the sluggishness If the proportional band is se...