Amana VXC20 Series Скачать руководство пользователя страница 14

14

Dehumidification

Dehumidification requires a thermostat capable of reading 

the indoor humidity level and allowing the user to set a 

dehumidification target.

The thermostat controls the humidity level of 

the conditioned space using the cooling system. 

Dehumidification is engaged whenever a cooling demand 

is present and humidity levels are above the target level. 

When this condition exists, the circulating fan output is 

reduced, increasing system run time, over cooling the 

evaporator coil and ultimately removing more humidity from 

the structure than if only in cooling mode.

The thermostat may also allow for an additional 

overcooling limit setting depending on the thermostat 

utilized. This allows the cooling system to further reduce 

humidity by lowering the temperature below the cooling 

setpoint in an attempt to better achieve desired humidity 

levels.

Dehumidification Tips

For effective dehumidification operation:

• 

  Ensure “Dehumidification selection” is NOT set to 

“OFF”.

• 

  Verify the cooling airflow profile is set to “Profile D”. 

-  See the Cool Set-up section of the Installation Manual for 

complete airflow profile details. 

-  By default, “Dehumidification selection” is standard and 

the cooling airflow profile is set to “Profile D”.

• 

  For additional dehumidification control, airflow settings 

are field adjustable and can be fine-tuned to a value 

that is comfortable for the application from a range of 

Cool Airflow Trim. 

•   In addition, the system can have Enhanced 

Dehumidification operation in setting “A”, “B”, 

or “C” of “Dehumidification Selection” based on 

dehumidification demand. 

-  See the DEHUMIDIFICATION SELECT section of the 

Installation Manual for more detail.

COMFORTBRIDGE™ SYSTEM

Overview

The ComfortBridge based inverter heating and air 

conditioning system uses an indoor unit and outdoor unit 

digitally communicating with one another via a two-way 

communications path. ComfortBridge is compatible with 

any 24 VAC single stage thermostat which sends inputs to 

the indoor unit.

Comfortbridge System Advanced Features

The ComfortBridge system permits access to system 

information, advanced set-up features, and advanced 

diagnostic/troubleshooting features via the control board 

push buttons or the CoolCloud HVAC app. 

(If using a CTK04 thermostat, please see the addendum 

for further instructions.)

Fault Code History

The air conditioner’s diagnostics menu provides access 

to the most recent faults. The six most recent faults can 

be accessed through the control board seven segment 

displays or the CoolCloud mobile app. Any consecutively 

repeated fault is stored a maximum of three times.

 

Example: A leak in the system, low refrigerant charge or an 

incompletely open stop valve can cause the unit to flash 

error code E15. This error code suggests that the unit is 

experiencing operation at low pressure. The control will 

only store this fault the first three consecutive times the 

fault occurs. 

NOTE: The fault list can be cleared after 

performing maintenance or servicing the system 

to assist in the troubleshooting process.

Device Status 

This menu displays information about the systems current 

status. This menu can be utilized to confirm correct 

functionality of the equipment and for troubleshooting 

purposes.

The following items will be displayed:

•   Heat Capacity Request Percentage

•   Cool Capacity Request Percentage

•   Heat Capacity Request During Defrost Percentage

• 

  Dehumidification Request Percentage

•   Reversing Valve Status

• 

  Reported Airflow by Indoor Unit

•   Boost Mode

•   Previous Defrost Run Time 

* Information specific to the heat pump is not  

 

   displayed. 

Содержание VXC20 Series

Страница 1: ...ual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying these symbols Failur...

Страница 2: ...Refrigerant Lines 5 Leak Testing Nitrogen Or Nitrogen Traced 7 System Start Up Procedure 7 Electrical Connections 8 Coolcloud Hvac Phone Application 11 Comfortbridge System 14 Air Conditioner Advanced...

Страница 3: ...system must be manufacturer approved and Air Conditioning Heating and Refrigeration Institute AHRI matched NOTE The installation of an inverter condensing unit with unmatched system units will not all...

Страница 4: ...nting assembly to reduce noise vibration Electrical Noise The unit should be well grounded so that potential effects of electrical noise from the inverter to surrounding equipment can be minimized Whe...

Страница 5: ...and vibration absorbing material to be placed or installed between tubing and foundation Any gap between foundation or wall and refrigerant lines should be filled with a pliable silicon based caulk R...

Страница 6: ...6...

Страница 7: ...h a rust preventative The recommended location of the filter drier is before the expansion device at the indoor unit NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will c...

Страница 8: ...NNECTIONS HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK WIRING MUST...

Страница 9: ...electrical noise external noise and malfunction or fail Make sure the wirings will not be pinched by the front panel and close the panel firmly Route the conduit along the unit and so on to prevent wi...

Страница 10: ...60 179 181 273 273 65 182 184 276 276 70 185 187 279 279 75 188 190 282 282 80 191 193 285 285 85 194 196 288 288 90 197 199 291 291 95 200 202 294 294 100 203 205 297 297 105 206 208 300 300 110 209...

Страница 11: ...ists the eqivalent length gained from adding bends to the suction line Properly size the suction line to minimize capacity loss Step 3 System Start up Test NOTICE On initial power start up the outdoor...

Страница 12: ...o the following procedure a If subcooling is low add charge to adjust the subcooling as specified in the following table b If subcooling is high remove chargee to lower the subcooling to 8 1 F SUBCOOL...

Страница 13: ...rant for any length over 15 feet Or Charge by Sub cooling Sub cooling should be 8 F 1 F after adjusting charge please allow at least 20 minutes for the system to stabilize before making further charge...

Страница 14: ...STEM Overview The ComfortBridge based inverter heating and air conditioning system uses an indoor unit and outdoor unit digitally communicating with one another via a two way communications path Comfo...

Страница 15: ...ables 1 1 At Cool and Heat Hi speed trim VXC200601 with VC960804C VM970804C and MVC800804C combination trim more than 5 settings are invalid Trimmed up CFM makes miss matching error 2 At Cool Hi speed...

Страница 16: ...rough the control board seven segment displays or the CoolCloud mobile app Max compressor speed can be changed to get the required capacity or efficiency Once the maximum speed is set the system opera...

Страница 17: ...unning DEHUMIDIFICATION REQUEST Request for dehumidification 0 means dehumidification is not being requested All other values mean dehumidification is being requested OUTDOOR FAN SPEED RPM Current spe...

Страница 18: ...nter PUMP DOWN Mode This procedure runs the equipment for approximately 15 minutes and allows accumulation of refrigerant at the outdoor unit for purposes of removing replacing the indoor unit or outd...

Страница 19: ...17A HPS E1 HR1 HR3 BR WH HR2 HR4 X32A X851A POWER CONDITIONER X12A LIQUID LINE DISCHARGE LINE GR RD Z3C RD BK PU GROUND LUG V W U NOTE 1 1 OFF ON SEE NOTE 3 SEE NOTE 3 2 X52A SHARE DATA Z4C BS1 BS2 BS...

Страница 20: ...K RD L1C L2C TERMINAL BLOCK FIELD WIRING H LPT GND INVERTER BOARD COMPRESSOR TERMINAL ORIENTATION X32A X108A GR Z1C Z2C Z3C X12A COIL INLET LIQUID LINE DISCHARGE LINE U V W 1 OFF ON DS2 2 NOTE 1 BS1 B...

Страница 21: ...1 OFF ON DS2 2 1 THE POSITION OF THE SELECTOR SWITCHES DS1 INDICATE FACTORY SETTING 2 MOTOR OVERLOAD PROTECTION PROVIDED BY INVERTER SEE TABLE 3 USE COPPER CONDUCTORS ONLY 4 CLASS 2 WIRE NOTES BS1 BS2...

Страница 22: ...CITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATE...

Страница 23: ...ICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIAT...

Страница 24: ...ICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIAT...

Страница 25: ...AILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATELY AFTER MEASURING THE RESIDUAL...

Страница 26: ...26 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...

Страница 27: ...27 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...

Страница 28: ...28 Troubleshooting 1 This message is displayed when using the CTK04 thermostat 2 Network communication error Refer to NETWORK TROUBLESHOOTING...

Страница 29: ...29 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...

Страница 30: ...he LED status and the corresponding potential problem Green receive LED Indicates network traffic The table below indicates the LED status and the corresponding potential problem Learn button Used to...

Страница 31: ...corresponding Screen within the display itself which allows the user to navigate and use the features Example The Fault Code is accessed and displayed from Screen 0 of the 7 segment display The Fault...

Страница 32: ...shows the most recent fault To access hold the RECALL button for 5 seconds at screen 0 To access hold the RECALL button for 5 seconds at screen 1 To access hold the RECALL button To access hold the RE...

Страница 33: ...w the user to see the six most recent system faults For a list of the fault codes please see the TROUBLESHOOTING tables in this document 1 SCREEN 0 SCREEN 1 The display will change to SCREEN 1 Display...

Страница 34: ...etting Press RECALL Press RECALL Item number Display flickers at 1 second intervals Value MONITORING MODE NAVIGATION SCR This screen allows the user to monitor system variables as shown in the tables...

Страница 35: ...tem settings as shown in the tables at the end of this section SCREEN 0 Press RECALL Press RECALL to increase the value Press TEST to change setting Press RECALL Press TEST to complete setting and ret...

Страница 36: ...the number Press RECALL Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode Press RECALL Press RECALL Press RECALL SCREEN 0 OFF ON Blink interval 0 4 s...

Страница 37: ...0 Stop 1 Cooling Start up 2 Heating Start up 3 Oil Return Operation 4 Heating Operation 5 Defrost Operation 6 Cooling Operation 3 Compressor Reduction Mode 0 OFF 1 ON 4 demand unit Cut off the decima...

Страница 38: ...System Test 0 ON 1 OFF 8 Pump Down 0 ON 1 OFF 9 Charge Mode 0 ON 1 OFF 10 Maximum Compressor RPS for Cooling 12 BOOST MODE Selection 0 ON 1 OFF 13 BOOST MODE Temperature 0 105F 1 100F 2 95F 3 90F 4 8...

Страница 39: ...39...

Страница 40: ...40...

Страница 41: ...41...

Страница 42: ...rity sensitive Only the data lines 1 and 2 are required between the indoor and outdoor units Data line terminal 1 from outdoor unit must connect to terminal 1 on indoor unit and data line terminal 2 f...

Страница 43: ...section Before starting the SYSTEM TEST turn off the electric heater or gas furnace NOTICE Before starting the SYSTEM TEST turn off the electric heater or gas furnace 1 Ensure the thermostat is insta...

Страница 44: ...password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 6 Select YES to continue 7 From the ComfortNet USER MENU select A...

Страница 45: ...to run for its duration 5 15 minutes EQUIP TEST SCREEN will show the system test is ON once selected System test will operate the outdoor unit and the indoor unit through a series of startup tests Pl...

Страница 46: ...th codes to clear Set Thermostat to CHARGE MODE Please follow the following sequence to enter CHARGE MODE CHARGE mode allows for charging of the system System operates for a duration of approximately...

Страница 47: ...password The password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 4 Select YES to continue 5 Select Air Conditioner 6...

Страница 48: ...ing is not complete after 1 hour repeat 7 and 8 Refer to Adjust Refrigerant Level and Measure Subcooling to Verify Proper Charge for refrigerant charge level adjustment 9 To terminate CHARGE MODE sele...

Страница 49: ...ssor speed in CHARGE MODE Compressor speed is displayed under STATUS menu in the thermostat 8 For TXV Indoor Unit The system subcooling should be 8 F 1 F If not in that range adjust subcooling and sup...

Страница 50: ...tisfy unusual high loads BOOST MODE is BOOST MODE is initiated by an outdoor tempera ture sensor located in the outdoor unit Please note that out door equipment operational sound levels may increase w...

Страница 51: ...ancel button and selecting the Dealer information button Once recorded click the green OK button and return to the previous step 4 Select YES to continue 5 Select AIR CONDITIONER 6 Select SYS SETUP Me...

Страница 52: ...ON option is also available to perma nently engage BOOST MODE Factory default is 105 F Help Previous Menu VERTICAL RISE SET MAX CURRENT OFF BOOST MD ON BOOST TEMP Always On Outdoor Lower Help Previou...

Страница 53: ...enable and disable dehumidification 1 On the CTK04 HOME screen select MENU 2 From the MENU screen scroll down and select Installer Options 3 Enter installer password if known a The password is the the...

Страница 54: ...eak in the system low refrigerant charge or an incompletely open stop valve can cause the unit to flash error code E15 This error code sug gests that the unit is experiencing operation at low pressure...

Страница 55: ...flow and operates there for approximately 7 1 2 minutes The motor then steps up to the full demand airflow Profile C also has a one 1 minute 100 OFF delay 100 CFM OFF OFF Profile D default ramps up to...

Страница 56: ...cessary adjustments to the maximum compressor RPS are made through the following sub menus Maximum Compressor RPS Range for Cooling Select the range that your maximum compressor RPS falls within Maxim...

Страница 57: ...57...

Страница 58: ...58...

Страница 59: ...59 THIS PAGE IS INTENTIONALLY LEFT BLANK...

Страница 60: ...d Quebec residents to register their product does not diminish their warranty rights For Product Registration please register as follows Goodman Brand products https www goodmanmfg com product registr...

Отзывы: