13
D
O
NOT
ADJUST
THE
CHARGE
BASED
ON
SUCTION
PRESSURE
UNLESS
THERE
IS
A
GROSS
UNDERCHARGE
.
NOTICE
SUCTION PRESSURE
PSIG
R-410A °F
SUCTION PRESSURE
PSIG
R-410A °F
50
1
200
70
52
3
210
73
54
4
220
76
56
6
225
78
58
7
235
80
60
8
245
83
62
10
255
85
64
11
265
88
66
13
275
90
68
14
285
92
70
15
295
95
72
16
305
97
74
17
325
101
76
19
355
108
78
20
375
112
80
21
405
118
85
24
415
119
90
26
425
121
95
29
435
123
100
31
445
125
110
36
475
130
120
41
500
134
130
45
525
138
140
49
550
142
150
53
575
145
160
56
600
149
170
60
625
152
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
SATURATED SUCTION PRESSURE
TEMPERATURE CHART
ATTENTION INSTALLER - IMPORTANT NOTICE!
Please read carefully before installing this unit.
•
Do not attach any wires to the R & C Terminals on the
Condensing Unit, as they are not needed for inverter unit
setup.
•
Data Line Terminals #1 and #2 are polarity sensity. Only
the data lines, 1 and 2 are required between the indoor
and outdoor units.
•
Data Line Terminal #1 from outdoor unit must connect to
terminal #1 on indoor unit and data line terminal #2 from
outdoor unit must connect to terminal #2 on indoor unit.
Verify wires are not reversed.
•
Calculate the Liquid Line Set length and weigh in 0.6
ounces per foot of R410A refrigerant for any length
over 15 feet.
Or
•
Charge by Sub-cooling.
Sub-cooling should be 8°F ± 1°F. after adjusting charge,
please allow at least 20 minutes for the system to stabilize
before making further charge adjustment.
Setting
Function
1
ON
CT Communication Terminal Resister
2
ON
CT Communication Terminal Resister
1
ON
Cooling Emergency Mode*
2
ON
Cooling Emergency Mode*
OUTDOOR UNIT DIPSWITCH FACTORY DEFAULT SETTINGS
Switch #
DS1
DS2
* DS2 sw itch 1 and 2 both must be turned on during normal operation mode
Field Selectable Boost Mode
BOOST MODE can be enabled or disabled through the
control board push buttons or through the CoolCloud app.
BOOST MODE allows the system to operate at increased
compressor speed to satisfy unusually high loads. BOOST
MODE is initiated by an outdoor temperature sensor
located in the outdoor unit.
Please note that outdoor equipment operational sound
levels may increase while the equipment is running in
BOOST MODE. Disabling BOOST MODE will provide the
quietest and most efficient operation.
NOTE: BOOST MODE is applicable only for
AVXC200**1AB or later revision.
BOOST MODE is ON by default and is activated when the
outdoor temperature reaches 105°F. BOOST MODE can
be disabled and enabled and the activation temperature
adjusted in the Settings menu of the CoolCloud app or
through the indoor / outdoor push button menus.
If installing with a CTK04 thermostat, please see the
addendum for further instructions.
Содержание VXC20 Series
Страница 6: ...6...
Страница 26: ...26 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Страница 27: ...27 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Страница 29: ...29 Troubleshooting 1 This message is displayed when using the CTK04 thermostat...
Страница 39: ...39...
Страница 40: ...40...
Страница 41: ...41...
Страница 57: ...57...
Страница 58: ...58...
Страница 59: ...59 THIS PAGE IS INTENTIONALLY LEFT BLANK...