3

DO NOT locate the unit:

– Directly under a vent termination for a gas appliance.
– Within 3 feet of a clothes drier vent.
– Where the refreezing of defrost water would create

a hazard.

– Where water may rise into the unit.
– Where the noise would prove to be a nuisance to the

customer (i.e. windows, patios, decks, etc.)

DO locate the unit:

– With the bottom of the unit at least three inches

above the maximum expected snow accumulation

level.

– In accordance with the minimum clearances described

in Figure 1.

– To minimize the length of refrigerant piping required.
– To provide adequate service clearances.
– On a level concrete pad (or other sturdy, weather

resistant platform).

– Isolated from the building structure  to avoid transmis-

sion of vibrations.

NOTE:

  Short runs of refrigerant piping are better than long

runs.  Locate the unit to provide safe access for future
maintenance and service.  If possible, discuss unit location
with the owner before proceeding.

ROOFTOP INSTALLATIONS

Before installing this unit on a roof, ensure that the roof will
support the weight of the unit, its platform, and the service
personnel.  For the unit weight, see the outdoor unit
specification sheet (all weights are approximate). If there
is doubt about the adequacy of the roof, contact a qualified
architect or structural engineer before installing the unit.
Ensure the unit is placed on a level, weather-resistant
platform.

APPLICATION NOTE

For proper performance, the indoor equipment and duct-
work must be adequate for moving about 400 CFM of
indoor air for every ton of cooling capacity to be installed.
If they are not, modify the ductwork or indoor equipment
accordingly.

Refrigerant Piping

REFRIGERANT VAPOR AND LIQUID LINE SIZING

See unit “Specification Sheet” for the required vapor and
liquid line tubing sizes.  The listed sizes in the specification
sheet are suitable for line lengths of fifty feet or less and
indoor coil elevations of no more than forty feet above or
below the outdoor unit.  

NOTE:  

Unit performance is

affected by vapor line tubing size. A larger than required
vapor line tubing inhibits oil return to the unit.  A smaller
than required vapor line tubing size decreases unit perfor-
mance by up to 10%.  If a run of more than fifty feet is
required, contact your Amana distributor for assistance.
Check the indoor coil liquid and vapor line diameter. A
bushing or coupling may be needed to match with the line

General

This manual covers only the installation of the remote heat
pump.  See the unit specification sheet for information
regarding accessories.

SHIPPING AND HANDLING

Units are securely packed in shipping containers ap-
proved by the International Safe Transit Association.  Check
the carton upon arrival for external damage.  If damage is
found, file a request in writing for inspection by the carrier
agent immediately.  The carrier is responsible for making
prompt inspection of damage and for a thorough investiga-
tion of each claim. The distributor or manufacturer will not
accept claims from dealers for transportation damage.  If
no damage is found, carefully remove all shipping material
and properly dispose of it.
Keep the unit as upright as  possible.  Laying the unit on its
side or top could cause equipment damage.

LOCATION AND CLEARANCES

This unit is for outdoor installation only.  The unit cannot be
completely enclosed.  At least one side must be unre-
stricted.  Refer to Figure 1 for clearances from the sides
and top of the unit to walls and other objects.

NOTE:  

These minimum clearances do not guarantee

adequate service access.  Sufficient clearances for servic-
ing the unit(s) must be provided.
If installing two or more units at the same location, allow at
least 24 inches between the units when using the 6”-12”-
12” guidelines in Figure 1.  The space between two units
may be reduced to 12” if the clearances in Figure 1 are
increased to 12”-24”-24”.

12"

12"

6"

MINIMUM CLEARANCES

SIDE VIEW

5'

Figure 1

Содержание RHA Series

Страница 1: ...utions listed here take precedence RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION Goodman Company L P 1810 Wilson Parkway Fayetteville Tennessee 37334 www amana hac com RHA B D VHA B A Remote Heat Pump...

Страница 2: ...throughout this manual to indicate immediate or potential safety hazards It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying...

Страница 3: ...ne lengths of fifty feet or less and indoor coil elevations of no more than forty feet above or below the outdoor unit NOTE Unit performance is affected by vapor line tubing size A larger than require...

Страница 4: ...them first dig the trench so that it gradually slopes toward the compressor at least 1 inch per 10 feet Then insulate the liquid and suction lines separately Enclose all under ground portions of the...

Страница 5: ...s a through c again Otherwise the pump and gauge are operating properly and you can continue on to the next step evacuating the system Before proceeding be sure to close the valve D to the vacuum gaug...

Страница 6: ...ns or less d Close the valve to the vacuum pump C Wait five minutes then check the pressure on the vacuum gauge 1 If the pressure is not more than 1500 microns the system is leak free and properly eva...

Страница 7: ...y route the power supply and ground wires through the high voltage entrance in the unit 2 Connect the ground wire to the ground lug and power supply wires to the contactor 3 Route the low voltage wiri...

Страница 8: ...oz of R 22 per deviating foot CAUTION Using refrigerant that does not meet ARI Standard700maycausecompressordam age and void the warranty IMPORTANT If adding refrigerant to a system add only refriger...

Страница 9: ...100 110 120 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 SUPERHEAT O D UNIT OUTDOOR TEMPERATURE DESIRED SUPERHEAT vs OUTDOOR TEMPERATURE 9 0 F I n d o o r 70 F Indoor 7 5 F I n d o o r 8 0 F I n d o...

Страница 10: ...e 350 to 450 CFM per ton of cooling based on the size of the outdoor unit If further information is needed see the Remote Heat Pump Service Manual or contact your Amana distributor Defrost System Your...

Страница 11: ...ccessories wiring may have to be modified Follow the instructions in the accessory kit s installation instructions WARNING To avoid personal injury shock or death disconnect the electrical power befor...

Страница 12: ...or Is it within the limits shown on the nameplate of the motor 16 Are all access panels installed and secured 17 Do controls function properly Are manual reset switches in the reset position high pres...

Отзывы: