Setback Temps - DD01E / DD01F

The DD01* and the DigiSmart™ control can be programmed for 3 different times to activate temperature setbacks. The
current factory default temperature setbacks in v2.5 * software release are: 2º from set point in 30 minutes, 3º in one
(1) hour, and 6º in three (3) hours. For each time, you can select a setback temperature. The amount of setback is the
amount of degrees the control will operate from guest’s setting in degrees F. If a change to the factory default temperature
settings is desired, use the following instructions.

NOTE:

When first entering the configuration mode, if you see “ - - ” then you have version 2.5 or higher.
You can verify the software version by starting with the unit in the OFF position, and while holding down the
“+” and “-” buttons , double click the COOL button and then release and push the FAN button within one
second.  The unit display will scroll through all of the thermister temperatures and the last item displayed
will bs CS (current software) and you will see 25 for v2.5.

*Other software versions may have different factory setback defaults.  Contact y

our PTAC representative to

determine factory default settings.

WARNING

4. To select first unoccupied set back temperature, press the HEAT

  key until 

 

feature code

 

comes up.

To scroll to a previously viewed feature codes, press the COOL

  key.

Once you have scrolled to the 

 feature, press either the up or down arrow 

  to scroll to the desired first

unoccupied setback temperature. Cooling example: 72

0

 (guest set point) + 2

0

 (Setback temperature) = 74

0

 (opera-

tional set point).

5. Press HEAT 

  key to scroll to 

 first unoccupied setback time. The first unoccupied setback time is the

time between when the control determines that the room is not occupied and when the control sets the operating
set point temperature back. The increments are in hours (.1 = 6 mins., .5 = 30 mins., 1 = 1 hour, etc.).  Press ei-

ther the up or down arrow 

  to the desired first unoccupied setback time. c

6. To select second unoccupied setback temperature, press the HEAT

  key until 

 comes up. Press either

the up or down arrow 

  to the desired second unoccupied setback temperature.

 Cooling example: 72

0

 (guest set point) + 4

0

 (Setback temperature) = 76

0

 (operational set point).

7. Press HEAT 

  key to scroll to 

 second unoccupied setback time. Press either the up or down arrow

to the desired second unoccupied setback time. Example: Operating set point would be 76

0

 instead of 72

0

, one

hour (1.0 hour) after guest leaves room.

8. Press HEAT

  key to scroll to 

 third unoccupied setback temperature. Press either the up or down arrow

  to the desired third unoccupied setback temperature.

Содержание DD01E

Страница 1: ...installation or repair it is possible to place yourself in a position which is more hazardous than when the unit is in operation Remember it is your responsibility to install the product safely and t...

Страница 2: ...r at the fuse box or circuit breaker 2 If the cabinet front is screwed to the chassis remove the 1 4 screw or screws See following figure Front Mounting Screw accessed through louvers 3 Remove cabinet...

Страница 3: ...plate 4 If mounting in drywall tap plastic anchors into wall For other surfaces drill a 3 16 hole 5 Screw mounting plate to the wall DO NOT SNAP THER MOSTAT INTO PLACE UNTIL AFTER BINDING PROCESS See...

Страница 4: ...door frame the sensor will need to be mounted on the wall next to the door In these cases a wired magnet a field supplied single pole single throw wired magnet can be recessed or surface mounted andw...

Страница 5: ...r where it will be as close as possible to the bottom of the motion sensor but no more then 1 8 from the bottom center of the sensor DD01E or DD01F when the door is closed Select the correct slot in t...

Страница 6: ...Screw location located on each side of sensor SIDE VIEW P O S I T I O N A P O S I T I O N B P O S I T I O N C MAGNET SLOTS MAGNET HOLDER TOP VIEW INSTALL THE MAGNET IN THE CORRECT SLOT 15 16th FROM B...

Страница 7: ...oor frame POSITION A Spacers Two 2 1 4 spacers are included in kit CONSTRUCTION STYLE 4 Place magnet in Position A in instances when the door frame extends into the room beyond the door NOTE Two 2 1 4...

Страница 8: ...cally self configure to activate pre configured energy management routine when the DD01E or DD01F is installed and bound to the PTAC Additionally the setback times and setback temperatures can be chan...

Страница 9: ...s the HEAT key until appears then press the up and down arrows to select 01 3 If a room contains more than one unit a suite a suffix must also be entered to identify which unit is in the main room and...

Страница 10: ...lease the white button a second time Skip this step if there is no thermostat 3 Press and then immediately release the white tactile button on the back of the DD01 motion sensor or should now be displ...

Страница 11: ...00 99 00 99 C5 Room I D Digit 3 4 00 99 00 99 C6 Wired or Wireless Occupancy 0 Off 1 On 18 18 Hour Automatic Entry C8 Temp Limiting Cool 60 72 60 72 C9 Temp Limiting Heat 68 90 80 68 90 80 Cd English...

Страница 12: ...back temperature press the HEAT key until feature code comes up To scroll to a previously viewed feature codes press the COOL key Once you have scrolled to the feature press either the up or down arr...

Страница 13: ...10 To exit configuration mode Press the OFF key NOTE Configuration feature mode will also automatically exit if no keys are pressed for a period of two 2 minutes The changes made in configuration mode...

Страница 14: ...between the equipment and all persons This equipment is authorized for use under the United States Federal Communication Commission Rules and Regulations Code of Federal Regulations Chapter 47 part 1...

Страница 15: ...15 THIS PAGE LEFT BLANK INTENTIONALLY...

Страница 16: ...k of Maytag Corporation or its related companies and is used under license to Goodman Company L P Houston TX All rights reserved PTAC Direct Sales Inc 185 S Kimball Ave Suite 130 Southlake TX 76092 87...

Отзывы: