34
NOTE: For two stage non-communicating outdoor
units, system will stage airflow automatically for
low stage operation.
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
Tonnage
Selection
Airflow
1
400
2.3
920
3.6
1440
4.9
1960
1.1
440
2.4
960
3.7
1480
5
2000
1.2
480
2.5
1000
3.8
1520
5.1
2040
1.3
520
2.6
1040
3.9
1560
5.2
2080
1.4
560
2.7
1080
4
1600
5.3
2120
1.5
600
2.8
1120
4.1
1640
5.4
2160
1.6
640
2.9
1160
4.2
1680
5.5
2200
1.7
680
3
1200
4.3
1720
5.6
2240
1.8
720
3.1
1240
4.4
1760
5.7
2280
1.9
760
3.2
1280
4.5
1800
5.8
2320
2
800
3.3
1320
4.6
1840
5.9
2360
2.1
840
3.4
1360
4.7
1880
6
2400
2.2
880
3.5
1400
4.8
1920
NOTE: the system will not provide airflows above
the Max Airflow Value.
•
3 Ton Models = 1,400 CFM
• 4 Ton Models = 1,760 CFM
• 5 Ton Models = 2,200 CFM
5.
Use the
CoolCloud
HVAC phone application to
configure/test
furnace
operations.
NOTE: The phone application cannot test a non-
communicating outdoor unit.The thermostat will
be required for outdoor unit testing.
Charging
a.
Two-stage outdoor units:
a.Provide a second stage cooling call from the
thermostat and charge accordingly.
b.
Single-stage outdoor units:
a.Provide a cooling call from the thermostat and
charge accordingly.
Gas Furnace Testing
a. Two stage operation using the
CoolCloud
HVAC application:
a. Select the gas heat icon after entering the
furnace menus.
b. Select any value less than 50% for low stage
operation and any value greater than 50% for
high stage operation.
3. Select the Non-Comm Outdoor Setting menu (OdS)
using the on board push buttons or the
CoolCloud
HVAC phone application. Select 1 AC for single stage
Air Conditioners, 1HP for single stage heat pumps,
2 AC for two stage air conditioners and 2 HP for two
stage Heat Pumps.
4. Go to the tonnage units menu (ton) and select the
tonnage value that corresponds to the desired airflow
for the outdoor unit. See the following table.