Airflow Table

Note:

 ^Default speed

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM CFM CFM CFM CFM CFM CFM CFM

F01

753

708

663

616

568

513

470

423

F02

915

883

845

809

773

730

690

650

F03

529

518

461

394

343

288

223

N/A

F04^

880

843

807

768

723

683

643

590

F05

1055 1022

990

959

930

891

858

825

F06

1101 1072 1040 1010

980

949

918

881

F07

1190 1162 1134 1104 1077 1042 1013

982

F08

1183 1157 1130 1103 1077 1047 1018

988

F09

1229 1206 1178 1153 1128 1100 1070 1042

F01

733

691

650

602

553

498

448

402

F02

1051 1024

996

966

935

907

868

836

F03

665

620

570

517

462

407

359

309

F04^

915

881

846

814

780

737

695

652

F05

1138 1114 1092 1064 1035 1006

977

947

F06

887

855

823

790

751

705

666

608

F07

1189 1163 1138 1111 1085 1059 1032 1001

F08

1266 1243 1218 1197 1172 1148 1123 1099

F09

1342 1324 1305 1280 1263 1239 1216 1193

F01

900

867

830

798

758

718

682

645

F02

1292 1272 1248 1227 1206 1184 1162 1137

F03

688

649

603

551

499

447

405

359

F04^

866

830

797

759

717

675

634

591

F05

1223 1195 1176 1149 1124 1101 1074 1047

F06

1037 1004

975

950

921

886

853

823

F07

1079 1053 1025 1000

970

941

911

873

F08

1128 1099 1075 1050 1022

993

965

937

F09

1171 1148 1124 1096 1070 1045 1017

988

F01

914

864

815

762

704

654

604

560

F02

1121 1083 1041

996

953

906

861

818

F03

758

696

636

572

512

460

412

N/A

F04^

960

917

864

812

764

708

661

614

F05

1164 1123 1084 1042 1003

960

920

871

F06

1219 1180 1141 1102 1062 1020

978

940

F07

1273 1240 1207 1171 1128 1089 1051 1012

F08

1307 1270 1235 1198 1160 1122 1083 1043

F09

1427 1390 1362 1327 1297 1260 1224 1193

F01

1205 1169 1131 1091 1053 1014

974

934

F02

1415 1385 1355 1322 1291 1255 1219 1186

F03

696

635

568

500

442

390

336

255

F04^ 1152 1112 1076 1035

996

954

916

868

F05

1321 1287 1251 1217 1181 1146 1112 1072

F06

901

851

801

746

690

638

587

543

F07

1112 1076 1032

992

949

905

858

819

F08

1290 1252 1215 1182 1143 1107 1071 1032

F09

1471 1440 1409 1377 1347 1314 1283 1247

F01

1289 1234 1180 1122 1058

991

917

840

F02

1836 1784 1741 1703 1664 1628 1585 1537

F03

1297 1246 1199 1142 1083 1020

949

872

F04^ 1194 1137 1079 1014

948

873

792

712

F05

1748 1696 1650 1612 1574 1526 1478 1428

F06

1451 1399 1354 1309 1256 1200 1142 1077

F07

1587 1534 1489 1445 1406 1354 1298 1244

F08

1683 1633 1589 1546 1502 1460 1406 1355

F09

1919 1890 1846 1807 1771 1735 1694 1650

F01

1475 1421 1369 1314 1260 1207 1152 1097

F02

1791 1741 1699 1652 1609 1561 1513 1465

F03

924

846

767

684

606

529

463

398

F04^ 1259 1197 1138 1074 1015

947

885

821

F05

1710 1660 1613 1583 1517 1470 1421 1374

F06

1592 1536 1486 1436 1383 1331 1281 1233

F07

1627 1574 1524 1474 1423 1370 1320 1271

F08

1921 1879 1840 1791 1751 1705 1656 1610

F09

2026 1981 1929 1901 1858 1819 1773 1733

F01

1259 1197 1138 1074 1015

947

885

821

F02

1791 1741 1699 1652 1609 1561 1513 1465

F03

1176 1108 1044

980

913

845

779

718

F04^ 1347 1286 1231 1172 1115 1055

995

933

F05

1921 1879 1840 1791 1751 1705 1656 1610

F06

1446 1404 1335 1280 1226 1171 1117 1062

F07

1618 1567 1510 1460 1413 1364 1312 1262

F08

2009 1964 1918 1886 1852 1811 1759 1722

F09

2161 2122 2084 2048 2010 1973 1940 1914

F01

1766 1712 1666 1612 1558 1506 1450 1395

F02

2205 2157 2110 2064 2021 1974 1925 1879

F03

1118 1035

952

860

750

663

590

519

F04^ 1684 1620 1561 1499 1438 1378 1318 1259

F05

2031 1981 1933 1901 1850 1799 1750 1702

F06

1220 1145 1070

995

952

907

811

725

F07

1357 1311 1243 1175 1107 1021

932

861

F08

1906 1877 1828 1778 1726 1674 1622 1568

F09

2454 2396 2347 2296 2250 2202 2157 2113

LOW STAGE COOLING AIFLOW

*M9C960403AN

Y/Y1 

*M9C960603AN

Y/Y1 

*M9C960603BN

Y/Y1 

MODEL

THERMOSTAT 

CALL

TAP #

EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)

*M9C960303AN

Y/Y1 

*M9C960803BN

Y/Y1 

*M9C960804CN

Y/Y1 

*M9C961004CN

*M9C961005CN

*M9C961205DN

Y/Y1 

Y/Y1 

Y/Y1 

HIGH STAGE COOLING AIFLOW

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

CFM CFM CFM CFM CFM CFM CFM CFM

F01

753

708

663

616

568

513

470

423

F02

915

883

845

809

773

730

690

650

F03

529

518

461

394

343

288

223

N/A

F04

880

843

807

768

723

683

643

590

F05^ 1055 1022

990

959

930

891

858

825

F06

1101 1072 1040 1010

980

949

918

881

F07

1190 1162 1134 1104 1077 1042 1013

982

F08

1183 1157 1130 1103 1077 1047 1018

988

F09

1229 1206 1178 1153 1128 1100 1070 1042

F01

733

691

650

602

553

498

448

402

F02

1051 1024

996

966

935

907

868

836

F03

665

620

570

517

462

407

359

309

F04

915

881

846

814

780

737

695

652

F05^ 1138 1114 1092 1064 1035 1006

977

947

F06

887

855

823

790

751

705

666

608

F07

1189 1163 1138 1111 1085 1059 1032 1001

F08

1266 1243 1218 1197 1172 1148 1123 1099

F09

1342 1324 1305 1280 1263 1239 1216 1193

F01

900

867

830

798

758

718

682

645

F02

1292 1272 1248 1227 1206 1184 1162 1137

F03

688

649

603

551

499

447

405

359

F04

866

830

797

759

717

675

634

591

F05^ 1223 1195 1176 1149 1124 1101 1074 1047

F06

1037 1004

975

950

921

886

853

823

F07

1079 1053 1025 1000

970

941

911

873

F08

1128 1099 1075 1050 1022

993

965

937

F09

1171 1148 1124 1096 1070 1045 1017

988

F01

914

864

815

762

704

654

604

560

F02

1121 1083 1041

996

953

906

861

818

F03

758

696

636

572

512

460

412

N/A

F04

960

917

864

812

764

708

661

614

F05^ 1164 1123 1084 1042 1003

960

920

871

F06

1219 1180 1141 1102 1062 1020

978

940

F07

1273 1240 1207 1171 1128 1089 1051 1012

F08

1307 1270 1235 1198 1160 1122 1083 1043

F09

1427 1390 1362 1327 1297 1260 1224 1193

F01

1205 1169 1131 1091 1053 1014

974

934

F02

1415 1385 1355 1322 1291 1255 1219 1186

F03

696

635

568

500

442

390

336

255

F04

1152 1112 1076 1035

996

954

916

868

F05^ 1321 1287 1251 1217 1181 1146 1112 1072

F06

901

851

801

746

690

638

587

543

F07

1112 1076 1032

992

949

905

858

819

F08

1290 1252 1215 1182 1143 1107 1071 1032

F09

1471 1440 1409 1377 1347 1314 1283 1247

F01

1289 1234 1180 1122 1058

991

917

840

F02

1836 1784 1741 1703 1664 1628 1585 1537

F03

1297 1246 1199 1142 1083 1020

949

872

F04

1194 1137 1079 1014

948

873

792

712

F05^ 1748 1696 1650 1612 1574 1526 1478 1428

F06

1451 1399 1354 1309 1256 1200 1142 1077

F07

1587 1534 1489 1445 1406 1354 1298 1244

F08

1683 1633 1589 1546 1502 1460 1406 1355

F09

1919 1890 1846 1807 1771 1735 1694 1650

F01

1475 1421 1369 1314 1260 1207 1152 1097

F02

1791 1741 1699 1652 1609 1561 1513 1465

F03

924

846

767

684

606

529

463

398

F04

1259 1197 1138 1074 1015

947

885

821

F05^ 1710 1660 1613 1583 1517 1470 1421 1374

F06

1592 1536 1486 1436 1383 1331 1281 1233

F07

1627 1574 1524 1474 1423 1370 1320 1271

F08

1921 1879 1840 1791 1751 1705 1656 1610

F09

2026 1981 1929 1901 1858 1819 1773 1733

F01

1259 1197 1138 1074 1015

947

885

821

F02

1791 1741 1699 1652 1609 1561 1513 1465

F03

1176 1108 1044

980

913

845

779

718

F04

1347 1286 1231 1172 1115 1055

995

933

F05^ 1921 1879 1840 1791 1751 1705 1656 1610

F06

1446 1404 1335 1280 1226 1171 1117 1062

F07

1618 1567 1510 1460 1413 1364 1312 1262

F08

2009 1964 1918 1886 1852 1811 1759 1722

F09

2161 2122 2084 2048 2010 1973 1940 1914

F01

1766 1712 1666 1612 1558 1506 1450 1395

F02

2205 2157 2110 2064 2021 1974 1925 1879

F03

1118 1035

952

860

750

663

590

519

F04

1684 1620 1561 1499 1438 1378 1318 1259

F05^ 2031 1981 1933 1901 1850 1799 1750 1702

F06

1220 1145 1070

995

952

907

811

725

F07

1357 1311 1243 1175 1107 1021

932

861

F08

1906 1877 1828 1778 1726 1674 1622 1568

F09

2454 2396 2347 2296 2250 2202 2157

 

MODEL

THERMOSTAT 

CALL

TAP #

EXTERNAL STATIC PRESSURE, (INCHES WATER COLUMN)

*M9C960303AN

 Y2

*M9C960403AN

 Y2

 Y2

*M9C960803BN

 Y2

*M9C960804CN

 Y2

*M9C960603AN

 Y2

*M9C961004CN

 Y2

*M9C961005CN

 Y2

*M9C961205DN

 Y2

*M9C960603BN

Содержание C9C96 Series

Страница 1: ...NOTE Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual Thesefurnacescomplywithrequirements embodied in the American National Standard Na...

Страница 2: ...pane Gas High Altitude Installations 11 Condensate Drain Lines Drain Trap 18 Electrical Connections 23 Gas Supply and Piping 26 Circulating Air Filters 29 Startup Procedure Adjustment 31 Airflow Table...

Страница 3: ...manual Always install a furnace to operate within the furnace s intended temperature rise range with a duct system which has external static pressure within the allowable range as specified on the fu...

Страница 4: ...and for a thorough investigation of each claim The distributor or manufacturer will not accept claims from dealers for transportation damage SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OF...

Страница 5: ...os cuartos de servicio B10259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparat...

Страница 6: ...capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated The total heat loss should be calculated by an approved method or in accordance with ASHRAE Guid...

Страница 7: ...ace must face the same direction If the furnace is installed in a residential garage position the furnace so that the burners and ignition source are located not less than 18 inches 457 mm above the f...

Страница 8: ...thin 12 inches of the bottom of the confined space In a typical construction the clearance between the door and door frame is usually ade quate to satisfy this ventilation requirement CARBON MONOXIDE...

Страница 9: ...tilateurs les registres de foyer et tous les autres appareils de combustion aliment s au gaz doivent tre remis dans leur tat initial AVERTISSEMENT Existing Furnace Removal NOTE When an existing furnac...

Страница 10: ...oors and windows These changes have helped in reducing heating cooling costs but have created a problem supplying combustion and ventilation air for gas fired and other fuel burning appliances Applian...

Страница 11: ...bing Drain Trap and Lines In horizontal applications the condensate drain trap is secured to the furnace side panel suspending it below the furnace A minimum clearance of 5 5 below the furnace must be...

Страница 12: ...utdoors as the vent pipe or flue pipe The pipe that supplies air for combustion to the furnace will be referred to as the intake pipe or combustion air pipe This furnace is dual certified and may be i...

Страница 13: ...S ULC S636 WARNING Upon completion of the furnace installation carefully inspect the entire flue system both inside and outside of the furnace to assure it is properly sealed Leaks in the flue system...

Страница 14: ...e Termination Forced Air Inlet Non Direct Vent Direct Vent Vent Flue Terminations Grade or Highest Anticipated Snow Level Vent Clearances Figure 7 VENT DRAIN RF000142 Coupling Figure 8 WARNING Edges o...

Страница 15: ...35 30 25 20 15 10 5 NA 3 103 96 89 82 75 68 61 54 2 45 40 35 30 25 20 15 10 3 110 103 96 89 82 75 68 61 MEC96 CEC96 Direct Vent 2 Pipe and Non Direct Vent 1 Pipe 6 Maximum Allowable Length of Vent Flu...

Страница 16: ...e 12 The RF000142 coupling Figure 8 can be secured directly to the furnace intake coupling if condensation is a concern If the RF000142 is used on the combustion air inlet it must be installed with th...

Страница 17: ...tion Dual Pipe Figure 18 VENT FLUE TEE COMBUSTION AIR INTAKE DISTANCE BETWEEN COMBUSTION AIR INTAKE AND GRADE DISTANCE BETWEEN VENT AND GRADE Figure 19 Combustion Air Intake may also be snorkeled to o...

Страница 18: ...ducts of combustion to the point where condensation takes place The condensate must be collected in the furnace drain trap and routed to an appropriate drain location in compliance with local and nati...

Страница 19: ...THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE WARNING WARNING TO AVOID THE RISK OF INJURY ELECTRICAL SHOCK OR DEATH THE FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR IN TH...

Страница 20: ...ection Insert hose 2 from outside the cabinet through the cabinet drain hole nearest the top Secure it to the barbed fitting in the elbow with a red clamp 6 For models DM96VE0303AN DM96VE0403AN and DM...

Страница 21: ...the RF000142 Coupling Locate hose 2 factory installed Cut off and discard the 45 radius end 2 Install 90 radius end of hose 2 on RF000142 drain outlet and secure with a red clamp 3 Insert coupling in...

Страница 22: ...to obtain the respective hoses needed for installation and install per the following directions 1 Remove the drain trap and factory installed drain tube assemblies 2 Remove two 1 plugs from right sid...

Страница 23: ...ection of hose 4 to the 100 elbow and the PVC pipe and secure with red clamps 15 Connect the hoses to the trap inlets and secure with silver clamps drain trap outlet must point to the original bottom...

Страница 24: ...configured for a left side electrical connection To make electrical connections through the opposite side of the furnace the junction box must be relocated to the left side prior to making electrical...

Страница 25: ...ump or gas furnace A heat pump thermostat with three stages of heat is required to properly use a two stage furnace in conjunction with a heat pump Refer to the fossil fuel kit installation instructio...

Страница 26: ...any time the draft inducer is powered See con nection diagram below Note This is a 24 volt circuit only the common connection must be on C terminal of the low voltage terminal strip where thermostat...

Страница 27: ...ng from an appro priate manufacturer s propane gas conversion kit Taps for measuring the gas supply pressure and manifold pressure are provided on the valve The gas valve has a manual ON OFF control l...

Страница 28: ...long nipple is required For models with a hook shaped manifold a 2 long nipple is required Asemi rigid connector to the gas piping can be used outside the cabinet per local codes From the elbow the le...

Страница 29: ...the return duct connected to the furnace NOTE Ductwork must never be attached to the back of the furnace For upflow installations requiring 1800 CFM or more use either two side returns or bottom retur...

Страница 30: ...changer can be viewed for visual light inspection or such that a sampling probe can be inserted into the airstream The access panel must be made to prevent air leaks when the furnace is in operation W...

Страница 31: ...d or other suitable method to prevent air leakage For optimal performance verify that all door gaskets are properly in place and replace as needed to prevent air leakage Drain Trap Priming The drain t...

Страница 32: ...ed with the burners operating To measure and adjust the manifold pressure use the following procedure 1 Turn OFF gas to furnace at the manual gas shutoff valve external to the furnace 2 Turn off all e...

Страница 33: ...f in step 1 Be certain that all appliances are functioning properly and that all pilot burners are operating Temperature Rise Temperature rise must be within the range specified on the unit rating pla...

Страница 34: ...90 1251 1221 1186 F09 1468 1436 1393 1359 1323 1285 1248 1210 F01 1167 1124 1087 1040 995 954 916 869 F02 1317 1277 1240 1201 1161 1122 1081 1045 F03 733 669 606 543 482 424 372 300 F04 1217 1174 1130...

Страница 35: ...028 983 943 F01 1167 43 1124 44 1087 46 1040 48 995 50 954 916 869 F03 733 N A 669 N A 606 N A 543 N A 482 N A 424 372 300 F04 1217 41 1174 42 1130 44 1086 46 1045 48 1003 962 925 F02 1317 54 1277 56...

Страница 36: ...ESSURE INCHES WATER COLUMN M9C960303AN Y Y1 M9C960803BN Y Y1 M9C960804CN Y Y1 M9C961004CN M9C961005CN M9C961205DN Y Y1 Y Y1 Y Y1 HIGH STAGE COOLING AIFLOW 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 CFM CFM CFM C...

Страница 37: ...1 1217 1181 1146 1112 1072 F06 901 851 801 746 690 638 587 543 F07 1112 1076 1032 992 949 905 858 819 F08 1290 1252 1215 1182 1143 1107 1071 1032 F09 1471 1440 1409 1377 1347 1314 1283 1247 F01 1289 1...

Страница 38: ...916 868 F05 1321 54 1287 55 1251 57 1217 58 1181 60 1146 1112 1072 F01 1289 39 1234 40 1180 42 1122 44 1058 47 991 917 840 F03 1297 38 1246 40 1199 42 1142 44 1083 46 1020 949 872 F04 1194 42 1137 44...

Страница 39: ...speed number every time Left Right switches are pressed Table below shows the available speeds for Low High heat mode 3 When the center switch is pressed the current displayed speed shall be selected...

Страница 40: ...08 F09 TWO STAGE COOLING SPEED TABLE FOR 2 STAGE IFC Cooling Mode Low Stage Cooling Mode Sequence On a call for low stage cooling the Y Y1 or Y Y1 and G ther mostat contacts close signaling the furnac...

Страница 41: ...t still exists the control will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Safety Circuit Description A number of safety circuits are employed to ensure safe...

Страница 42: ...er of the same type and size TO ENSURE PROPER UNIT PERFORMANCE ADHERE TO THE FILTER SIZES GIVEN IN THE RECOMMENDED MINIMUM FILTER SIZE TABLE OR SPECIFICATION SHEET APPLICABLE TO YOUR MODEL CAUTION Fil...

Страница 43: ...er Only Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as...

Страница 44: ...Cool On Delay Delay Seconds Default set at 7 Secs Adjustments can be made in 7 Secs increments from0 to 35 Secs Cool Off Delay Delay Seconds Default set at 65 Secs Adjustments can be made in 5 Secs in...

Страница 45: ...with no furnace operation Inspect pressure switch hose repair replace if necessary Blocked flue and or inlet air pipe blocked drain system or weak induced draft blower Circulator blower runs continuo...

Страница 46: ...AT AT 0 7 AMPS 2 MANUFACTURER S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATE...

Страница 47: ...ize no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipmen...

Страница 48: ...lta T Difference between Supply and Return Temperatures DB F GAS PRESSURES Gas Inlet Pressure IN W C Gas Manifold Pressure Low Fire IN W C Gas Manifold Pressure High Fire IN W C Gas Type NG Natural Ga...

Страница 49: ...49 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 50: ...50 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 51: ...51 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 52: ...rchased to be directed to the feedback page GOODMAN BRAND AMANA BRAND GOODMAN BRAND AMANA BRAND PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the...

Отзывы: