12074208
14
February 1998
Temperature Offset Calibration
Offset amount adjusts temperatures for refrigerator cut-
ins and cut-outs by the amount of offset. The chart
below shows the indicator and the amount of offset from
the factory default setting.
INDICATOR
OFFSET
1
+8
2
+6
3
+4
4
+2
5
0
6
-2
7
-4
8
-6
Coldest
-8
•
Setting Refrigerator Temperature Offset
Press
Ref Temp pad. Refrigerator indicator and one
indicator will glow. Press
Warmer pad to move
offset to the next warmer setting. Press
Colder pad
to move offset to the next colder setting. Factory
default refrigerator offset is +2.
•
Setting Freezer Temperature Offset
Press
Freezer Temp pad. Freezer temperature
indicator and one indicator will glow. Press Warmer
pad to move offset to the next warmer setting.
Press Colder pad to move offset to the next colder
setting. Factory default freezer offset is 0.
Defrost Mode Selection
Toggle
*
pad to select adaptive or conventional defrost
mode. Vacation indicator glows when adaptive defrost
has been selected. If vacation indicator is off,
conventional defrost is selected. Conventional defrost
uses 8 hour CRTD value.
Forced Defrost
Defrost can be forced to start by pressing and holding
the
Alarm Off pad for 3 seconds. Program changes will
be saved permanently in EEPROM and program mode
will exit to Run Mode.
Forced Pulldown (Compressor Start)
Compressor start can be forced by pressing and
holding
Max Frz pad for 3 seconds. Program changes
will be saved permanently in EEPROM. Compressor,
evaporator fan, damper heater, and condenser fan will
come on.
Program Mode
Exiting Program Mode
Press
Display On pad for 3 seconds to exit Program
Mode. Tone will sound three times. Changes made in
Program Mode will be permanently saved in EEPROM.
Note: If no pad is pressed for 10 minutes, Program
Mode will be automatically exited. However, no
changes will be saved if Program Mode exits
automatically.