background image

12

Suggested Field Testing/Trouble Shooting

1. Run unit in the heating mode (room thermostat calling for heat).
2. Check unit for proper charge. 

NOTE: Bands of frost on the condenser coil indicate low refrigerant charge.

3. Shut off power to unit.
4. Disconnect outdoor fan by removing the outdoor fan motor wire from “DF2” on defrost control.
5. Restart unit and allow frost to accumulate.
6. After a few minutes of operation, the unit’s defrost thermostat should close. To verify this, check for 24 volts between “DFT” and

“C” on board. If the temperature at the thermostat is less than 28°F and the thermostat is open, replace the unit’s defrost
thermostat, as it is defective.

7. When the unit’s defrost thermostat has closed, short the test pins on the defrost board until the reversing valve shifts, indicating

defrost.  This should take up to 22 seconds depending on what timing period the control is set on.  After defrost initiation, the
short must instantly be removed or the unit’s defrost period will only last 3 seconds.

8. The control is shipped from the factory with the compressor delay option selected. This will de-energize the compressor

contactor for 30 seconds on defrost initiation and defrost termination. If the jumper is set to Normal, the compressor will
continue to run during defrost initiation and defrost termination. The control will also ignore the low pressure switch connected
to R-PS1 and PS2 for 5 minutes upon defrost initiation and 5 minutes after defrost termination.

9. After the unit’s defrost thermostat has terminated, check the defrost thermostat for 24 volts between “DFT” and “C”. The reading

should indicate 0 volts (open sensor).

10. Shut off power to unit.
11. Replace outdoor fan motor lead to terminal “DF2” on defrost board and turn on power.

A

IR

 

FLOW

 M

EASUREMENT

 

AND

 A

DJUSTMENT

Please review the 

Duct Work

 section before proceeding with the airflow measurements and adjustments in this section.

Unit blower curves (see Specification Sheets) are based on external static pressure (ESP per in/W.C.).  The duct openings on the
unit are considered internal static pressure. As long as ESP is maintained, the unit will deliver the proper air up to the maximum
static pressure listed for the CFM required by the application (i.e. home, building, etc.)
In general, 400 CFM per ton of cooling capacity is a rule of thumb.  Some applications depending on the sensible and latent
capacity requirements may need only 350 CFM or up to 425 CFM per ton.  Check condition space load requirements (from load
calculations) and equipment expanded ratings data to match CFM and capacity.
After unit is set and duct work completed, verify the ESP with a 1-inch inclined manometer with pilot tubes or a Magnahelic gauge
and confirm CFM to blower curves in the Specification Sheets.

NOTE: 

Never run CFM below 350 CFM per ton, evaporator freezing or poor unit performance is possible.

A

IR

 F

LOW

 A

DJUSTMENTS

 F

OR

 I

NDOOR

 B

LOWER

 M

OTOR

ECM Motor

The ECM control board is factory set with the dip switch #4 in the “ON” position for single stage units and to the "OFF" position for
the 2 stage units. All other dip switches are factory set in the “OFF” position.  

 For most applications, the settings are to be changed

according to the electric heat size.

The ECM motor provides many features not available on the traditional PSC motor.  These features include:

Improved Efficiency

Constant CFM

Soft Start and Stop

Improved Humidity Control

ECM Motor Speed Adjustment

Each ECM blower motor has been preprogrammed for operation at 4 distinct air flow levels when operating in Cooling/Heat Pump
mode or Electric Heat mode.  These 4 distinct levels may also be adjusted slightly lower or higher if desired.  The adjustment
between levels and the trim adjustments are made by changing the dip switch(s) either to an "OFF" or "ON" position.

See Appendix for Blower Performance Data tables.

APH D

IP

 S

WITCH

 F

UNCTIONS

The ECM motor has an electronic control that contains eight (8) 2-
position dip switches.  The function of these dip switches is shown
in 

Table 1.

APH CFM D

ELIVERY

 

AND

 A

DJUSTMENTS

See Appendix for CFM Output, Adjustments and DIP switch
settings.

APH T

HERMOSTAT

 “F

AN

 O

NLY

” M

ODE

During Fan Only Operations, the CFM output is 50% of the high stage
cooling setting.

DIP SWITCH NUMBER

FUNCTION

1

2

3

N/A

4

Indoor Thermostat

5

6

7

8

Cooling & Heat Pump CFM

CFM Trim Adjust

Elect ric Heat  

Table 1

Содержание APG1624060M41

Страница 1: ...15 Goodman Manufacturing Company L P INSTALLATION INSTRUCTIONS FOR SELF CONTAINED PACKAGE HEAT PUMP UNITS APH16 M SERIES NOTE Please contact your distributor or our website for the applicable Specific...

Страница 2: ...8 CONDENSATE DRAIN 8 WIRING 8 HIGH VOLTAGE WIRING 8 LOW VOLTAGE WIRING 9 INTERNAL WIRING 9 STARTUP ADJUSTMENTS AND CHECKS 9 COOLING START UP PROCEDURES 9 HEAT PUMP START UP PROCEDURE 9 FINAL SYSTEM CH...

Страница 3: ...NG REVERSING VALVE THIS MAY BE DUE TO 15 APPENDIX 16 TROUBLESHOOTING CHART 17 APH16 BLOWER PERFORMANCE DATA 18 APH16 CFM OUTPUT AND DIP SWITCH SETTINGS 19 CFM OUTPUT FOR DIP SWITCH COMBINATIONS 1 2 EL...

Страница 4: ...ck the unit model number specifications electrical characteristics and accessories to determine if they are correct In the event an incorrect unit is shipped it must be returned to the supplier and mu...

Страница 5: ...necessary internal electrical wiring The heat pump also includes a reversing valve solenoid defrost thermostat and control and loss of charge protection The system is factory evacuated charged and per...

Страница 6: ...cient structural strength to carry the weight of the unit s and snow or water loads as required by local codes Consult a structural engineer to determine the weight capabilities of the roof The unit m...

Страница 7: ...methods of Air Conditioning Contractors of America Manual D Residential or Manual Q Commercial All duct work exposed to the outdoors must include a weatherproof barrier and adequate insulation A duct...

Страница 8: ...isconnect near the unit Determine wire sizes and overcurrent protection from the unit nameplate ampacity and in accordance with the Minimum Filter Size or the N E C The wiring should never be sized sm...

Страница 9: ...on 3 Turn on the electrical supply at the disconnect 4 Turn the fan switch to the ON position The blower should begin ramping up immediately 5 Turn the fan switch to AUTO position The blower should be...

Страница 10: ...tc Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use NOTE The Cooling Start up Procedure is a recommended step as it serves as an system indi...

Страница 11: ...ity of the heat pump This phenomenon is a characteristic of a heat pump It is a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 4...

Страница 12: ...pressure As long as ESP is maintained the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application i e home building etc In general 400 CFM per...

Страница 13: ...ll thermometer on liquid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on high stag...

Страница 14: ...before taking readings Do not adjust TXV more than 1 4 of a turn between readings ELECTRICAL ADJUSTMENTS This series of electric cooling and heat pump package equipment is designed to accept a field i...

Страница 15: ...ACT The unit s defrost terminating sensor must make good thermal contact with the outdoor coil tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cu...

Страница 16: ...16 APPENDIX...

Страница 17: ...grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage must be w...

Страница 18: ...al 1 225 D Plus 880 D Plus 880 D Plus 1 348 D Plus 1 348 C Minus 900 C Minus 900 C Minus 1 260 C Minus 1 260 C Normal 1 000 C Normal 1 000 C Normal 1 400 C Normal 1 400 C Plus 1 100 C Plus 1 100 C Plu...

Страница 19: ...D On On 700 A Off Off 1250 F B On Off 1100 C Off On 1000 D On On 800 A Off Off 1250 F B On Off 1100 C Off On 1000 D On On 800 A Off Off 1800 B On Off 1700 C Off On 1400 F D On On 1225 A Off Off 1800 F...

Страница 20: ...S 3 MIN 12 MIN 36 MIN FOR SERVICE 48 MIN 12 MIN 36 MIN FOR SERVICE NOTE Roof overhang should be no more than 36 BLOWER ACCESS PANEL 2 34 51 47 SUPPLY 1 3 8 A RETURN POWER WIRE ENTRANCE 4 1 8 2 1 8 6 1...

Страница 21: ...r rubbing and leaks Repair if necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed V...

Страница 22: ...Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Cir...

Страница 23: ...23 THIS PAGE LEFT INTENTIONALLYBLANK...

Страница 24: ...24 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com 2015 Goodman Manufacturing Company L P...

Отзывы: