background image

10

4. If the outdoor ambient is above 80°F, the unit may trip on its high pressure cut out when on heating. The compressor should

stop.  The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable.
DO NOT FAIL TO TEST.

5. If the outdoor ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation

by blocking off the indoor return air until the unit trips.

6. If unit operates properly in the heating cycle, raise the temperature setting until the heating second stage makes contact.

Supplemental resistance heat, if installed should now come on. Ensure all heaters energize.

NOTE:  

All 16 SEER models have two stages of compressor heat. During resistance heat test, increase temperature setting

until third stage heat is energized.

If outdoor thermostats are installed, the outdoor ambient must be below the set point of these thermostats for the heaters to
operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient is mild.

7.

THERMOSTATS WITH EMERGENCY HEAT.  

For thermostats with an emergency heat switch, raise the temperature setting until

the heating second stage makes contact. The emergency heat switch is located at the bottom of the thermostat. Move the switch
to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat
emergency heat light will come on.

8. If checking the unit in the wintertime, when the outdoor coil is cold enough to actuate the defrost control, observe at least one

defrost cycle to make sure the unit defrosts completely.

F

INAL

 S

YSTEM

 C

HECKS

1. Ensure all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise

between heating and cooling.

2. Ensure there are no air leaks in the duct work.

3. Check air flow and refrigerant charge. See Sections on

 

Air Flow Measurement and Adjustment

 and 

Checking Charge

.

4. Ensure the unit is free of “rattles”, and the tubing in the unit is free from excessive vibration. The tubes or lines should not rub

against sheet metal surfaces, edges or each other.

5. Ensure the Owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc.
Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.

NOTE:

 The “Cooling Start-up Procedure” is a recommended  step as it serves as an system indicator that the unit will operate

normally.

COMPONENTS

Contactor

This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has a 24V coil and supplies
power to the compressor and outdoor fan motor.

Crankcase Heater

This item is “ON” whenever power

 

is supplied to the unit and the crankcase heater thermostat is closed. Crankcase heater

thermostat closes at 67° and opens at 85°. It warms the compressor crankcase thereby preventing liquid migration and subsequent
compressor damage. The insert type heater is self regulating.  It is connected electrically to the contactor L1 and L2 terminals.

Condenser Motor

This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation. On 460V
heat pumps, the condenser motor is activated by the CMR.

Compressor

This item is activated by the contactor for heating and cooling, except during emergency heat. It is protected by

 

an internal overload.

Contactor Relay

This control is activated by the thermostat (24V coil) and supplies power to the contactor.

Defrost Control

The Defrost Control provides time/temperature initiation and termination of the defrost cycle. When a defrost cycle is initiated, the
Defrost Control shifts the reversing valve to “COOLING” mode, stops the outdoor fan and brings on supplemental heat. Normally,
a defrost cycle will take only 2-3 minutes unless system is low on refrigerant charge or outdoor conditions are severe (i.e. windy
and cold). The defrost control also provides for a 3 minute off cycle compressor delay.

Outdoor Thermostat

These optional controls are used to prevent full electric heater operation at varying outdoor ambient (0°F to 45°F). They are normally
open above their set points and closed below to permit staging of indoor supplement heater operation.  If the outdoor ambient
temperature is below 0°F (-18°C) with 50% or higher RH, an outdoor thermostat (OT) must be installed and set at (0°) on the dial.
Failure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer’s
warranty.

Reversing Valve Coil

This coil is activated by the thermostat, in the cooling mode and during defrost. It positions the reversing valve pilot valve for cooling
operation.

Содержание APG1624060M41

Страница 1: ...15 Goodman Manufacturing Company L P INSTALLATION INSTRUCTIONS FOR SELF CONTAINED PACKAGE HEAT PUMP UNITS APH16 M SERIES NOTE Please contact your distributor or our website for the applicable Specific...

Страница 2: ...8 CONDENSATE DRAIN 8 WIRING 8 HIGH VOLTAGE WIRING 8 LOW VOLTAGE WIRING 9 INTERNAL WIRING 9 STARTUP ADJUSTMENTS AND CHECKS 9 COOLING START UP PROCEDURES 9 HEAT PUMP START UP PROCEDURE 9 FINAL SYSTEM CH...

Страница 3: ...NG REVERSING VALVE THIS MAY BE DUE TO 15 APPENDIX 16 TROUBLESHOOTING CHART 17 APH16 BLOWER PERFORMANCE DATA 18 APH16 CFM OUTPUT AND DIP SWITCH SETTINGS 19 CFM OUTPUT FOR DIP SWITCH COMBINATIONS 1 2 EL...

Страница 4: ...ck the unit model number specifications electrical characteristics and accessories to determine if they are correct In the event an incorrect unit is shipped it must be returned to the supplier and mu...

Страница 5: ...necessary internal electrical wiring The heat pump also includes a reversing valve solenoid defrost thermostat and control and loss of charge protection The system is factory evacuated charged and per...

Страница 6: ...cient structural strength to carry the weight of the unit s and snow or water loads as required by local codes Consult a structural engineer to determine the weight capabilities of the roof The unit m...

Страница 7: ...methods of Air Conditioning Contractors of America Manual D Residential or Manual Q Commercial All duct work exposed to the outdoors must include a weatherproof barrier and adequate insulation A duct...

Страница 8: ...isconnect near the unit Determine wire sizes and overcurrent protection from the unit nameplate ampacity and in accordance with the Minimum Filter Size or the N E C The wiring should never be sized sm...

Страница 9: ...on 3 Turn on the electrical supply at the disconnect 4 Turn the fan switch to the ON position The blower should begin ramping up immediately 5 Turn the fan switch to AUTO position The blower should be...

Страница 10: ...tc Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use NOTE The Cooling Start up Procedure is a recommended step as it serves as an system indi...

Страница 11: ...ity of the heat pump This phenomenon is a characteristic of a heat pump It is a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 4...

Страница 12: ...pressure As long as ESP is maintained the unit will deliver the proper air up to the maximum static pressure listed for the CFM required by the application i e home building etc In general 400 CFM per...

Страница 13: ...ll thermometer on liquid small line near liquid line access fitting with adequate contact and insulate for best possible reading 3 Check subcooling and superheat Two stage systems running on high stag...

Страница 14: ...before taking readings Do not adjust TXV more than 1 4 of a turn between readings ELECTRICAL ADJUSTMENTS This series of electric cooling and heat pump package equipment is designed to accept a field i...

Страница 15: ...ACT The unit s defrost terminating sensor must make good thermal contact with the outdoor coil tubing Poor contact may not terminate the unit s defrost cycle quickly enough to prevent the unit from cu...

Страница 16: ...16 APPENDIX...

Страница 17: ...grounded or open winding open internal overload b Wait at least 2 hours for overload to reset If still open replace the compressor c Low voltage connection c At compressor terminals voltage must be w...

Страница 18: ...al 1 225 D Plus 880 D Plus 880 D Plus 1 348 D Plus 1 348 C Minus 900 C Minus 900 C Minus 1 260 C Minus 1 260 C Normal 1 000 C Normal 1 000 C Normal 1 400 C Normal 1 400 C Plus 1 100 C Plus 1 100 C Plu...

Страница 19: ...D On On 700 A Off Off 1250 F B On Off 1100 C Off On 1000 D On On 800 A Off Off 1250 F B On Off 1100 C Off On 1000 D On On 800 A Off Off 1800 B On Off 1700 C Off On 1400 F D On On 1225 A Off Off 1800 F...

Страница 20: ...S 3 MIN 12 MIN 36 MIN FOR SERVICE 48 MIN 12 MIN 36 MIN FOR SERVICE NOTE Roof overhang should be no more than 36 BLOWER ACCESS PANEL 2 34 51 47 SUPPLY 1 3 8 A RETURN POWER WIRE ENTRANCE 4 1 8 2 1 8 6 1...

Страница 21: ...r rubbing and leaks Repair if necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Check all electrical connections and terminals Tighten as needed V...

Страница 22: ...Amps Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Blower Wheel RPM TEMPERATURES Outdoor Air Temperature Return Air Temperature Cooling Supply Air Temperature Discharge Cir...

Страница 23: ...23 THIS PAGE LEFT INTENTIONALLYBLANK...

Страница 24: ...24 Goodman Manufacturing Company L P 5151 San Felipe Suite 500 Houston TX 77056 www goodmanmfg com www amana hac com 2015 Goodman Manufacturing Company L P...

Отзывы: