background image

System Diagnosis

©2004 Maytag Services

16023324   Rev. 0

27

the high side (condenser) of the system.

• Only partial frosting of evaporator instead of even

frosting of entire coil.

NOTE 1

:

  Usually the first thing that is noticed by the

user is a rise in temperature foods.  Although
temperatures will rise in both the freezer section
and the food compartment, the frozen meats
and vegetables will not thaw immediately.  The
customer doesn't associate the problem with
the freezer section and will first notice that milk
and other food beverages are not cold enough.

Under some circumstances, such as in the case of
forced air meatkeeper model with a slight shortage of
refrigerant, freezing in the food compartment may be
experienced due to the additional running time.  With a
refrigerant leak, however, it always gets worse and as
the refrigerant charge decreases the temperature will
continue to rise.

With a shortage of refrigerant the capillary line will not
have a full column of liquid.  As a result, there is a
noticeable hissing sound in the evaporator.  This should
not be mistaken for the regular refrigerant boiling
sounds that would be considered normal.

Symptoms of a Restriction

Always remember refrigeration (cooling) occurs on the
low pressure side of a partial restriction (obviously a
total restriction will completely stop the circulation of
refrigerant and no cooling will take place).

Physically feel the refrigeration lines when a restriction
is suspected.  The most common place for a restriction
is at the drier-filter or at the capillary tube inlet or outlet.
If the restriction is not total there will be a temperature
difference at the point of restriction, the area on the
evaporator side will be cooler.  In many cases frost and/
or condensation will be present.  A longer time is
required for the system to equalize.

Any kinked line will cause a restriction so the entire
system should be visually checked.

A slight restriction will give the same indications as a
refrigerant shortage with lower than normal back
pressure, head pressure, and wattage, warmer product
temperatures.

NOTE 2: 

 If a total restriction is on the discharge side of

the compressor, higher than normal head
pressures and wattages would result.  This is
true only while the low side is being pumped out
and if the restriction was between the
compressor and the first half of the condenser.

To diagnose for a restriction versus a refrigerant
shortage, discharge the system, replace the drier-filter,
evacuate and recharge with the specified refrigerant
charge.  If the unit performs normally three  possibilities
exist:  1) refrigerant loss, 2) partially restricted drier-
filter, and 3) moisture in system.

If the unit performs as it previously did you may have a
restricted capillary line or condenser or kinked line.
Find the point of restriction and correct it.

A restriction reduces the flow rate of the refrigerant and
consequently reduces the rate of heat removal.
Complete restriction may be caused by moisture, solid
contaminants in the system, or a poorly soldered joint.
Moisture freezes at the evaporator inlet end of the
capillary tube or solid contaminants collect in the drier-
filter.  The wattage drops because the compressor is not
circulating the usual amount of refrigerant.

As far as pressure readings are concerned, if the
restriction, such as a kinked line or a joint soldered shut
is anywhere on the low side, the suction pressure would
probably be in a vacuum while the head pressure will be
near normal.  If the restriction is on the high side, the
suction pressure, again, will probably be in a vacuum
while the head pressure will be higher than normal
during the pump out period described earlier.  In either
case, it will take longer than the normal ten minutes or
so for the head pressure to equalize with the low side
after the compressor stops.

Symptoms of Air in System

This can result from a low side leak or improper
servicing.  If a leak should occur on the low side, the
temperature control would not be satisfied; thus,
continuous running of the compressor would result.  The
compressor would eventually pump the low side into a
vacuum drawing air and moisture into the system.  Air
and R134A do not mix so the air pressure would be
added to the normal head pressure, resulting in higher
than normal head pressures.

One way to determine if air is in the system is to read
the head pressure gauge with the product off and
evaporator and condenser at the same temperature and
then take the temperature on the condenser outlet tube.
This temperature should be within 3° or 4° F. of what the
Pressure-Temperature Relation chart shows for the
given idle head pressure.  If the temperature of the
condenser outlet is considerably lower than the idle
head pressure of the gauge this would indicate there is
air in the system.

Thorough leak checking is necessary.  Correct the
source of the leak.  Do not attempt to purge off the air
because this could result in the system being
undercharged.  It is best to discharge, replace drier,
evacuate and recharge with the specified refrigerant
charge.

Содержание AB1924PEK Series

Страница 1: ...but is not limited to the following Amana AB1924PEK AB2026PEK AB2225PEK AB2226PEK AB2526PEK G32026PEK G32526PEK GB1924PEK GB2225PEK GB2526PEK Service This manual is to be used by qualified appliance t...

Страница 2: ...REPAIRS WARNING To avoid risk of severe personal injury or death disconnect power before working servicing on appliance to avoid electrical shock To locate an authorized servicer please consult your t...

Страница 3: ...Freezer Drawer 29 Refrigerator Compartment Light Bulb 29 Light Bulb Assembly 29 Light Bulb Sockets 30 PC Control Board 30 Light Switch 30 Temp Assure Damper control 30 Fresh Food Thermistor 30 Water...

Страница 4: ...rom 25 C to 32 C Saturated gas is drawn off through suction line where superheated gas enters compressor To raise temperature of gas suction line is placed in heat exchange with capillary Temperature...

Страница 5: ...est 1 Disconnect power to refrigerator 2 Discharge capacitor if present by shorting terminals through a resistor 3 Remove compressor leads and use an ohmmeter set on highest scale 4 Touch one lead to...

Страница 6: ...enser It is very important that adequate air flow over condenser is maintained Condenser is air cooled by condenser fan motor If efficiency of heat transfer from condenser to surrounding air is impair...

Страница 7: ...terminal 2 1 Disconnect power to the refrigerator 2 Remove relay cover and disconnect leads 3 Check resistance across terminals 2 and 3 with an ohmmeter Normal 3 to 12 ohms Shorted 0 ohms Open infini...

Страница 8: ...NO terminals Closed Drier Drier is placed at post condenser loop outlet and passes liquefied refrigerant to capillary Desiccant 20 8 x 12 4AXH 7 M S Grams Drier must be changed every time the system...

Страница 9: ...ttmeter 2 Turn into defrost mode Wattmeter should read specified watts according to Technical Data Sheet 3 When defrost thermostat reaches specified temperature 15 C see Technical Data Sheet thermosta...

Страница 10: ...HFC134a and ester oil system Equipment must be exclusively used for HFC134a Exclusive use of equipment only applies to italic items Evacuation pump Check with vacuum pump supplier to verify equipment...

Страница 11: ...mpressor Run lead on test cord attaches to M terminal on compressor Service Procedures C R S Fuses Capacitor Compressor Switch To AC supply Attaching Capacitor for Compressor Test 5 Connect a known go...

Страница 12: ...Refrigerant leaks are best detected with halide or electronic leak detectors Testing Systems Containing a Refrigerant Charge 1 Stop unit operation turn refrigerator off 2 Holding leak detector explor...

Страница 13: ...n normal head pressure and wattage while low side is being pumped out Testing for Restrictions To determine if a restriction exists 1 Attach gauge and manifold between suction and discharge sides of s...

Страница 14: ...and F closed open all other valves and start vacuum pump Vacuum Pump 6 cm Copper Tubing Compressor Compressor Process Tube Charging Hose Thermistor Vacuum Gauge Low Side Gauge E Valve B D Valve High...

Страница 15: ...ess tube 5 Start compressor and draw remaining refrigerant from charging hoses and manifold into compressor through compressor process tube 6 To check high side pinch off drier process tube Close valv...

Страница 16: ...e Procedures HFC134a Service Information HFC134a is alternative refrigerant for CFC12 HFC134a has an ozone depletion potential ODP factor of 0 0 and a global warming potential GWP factor of 0 27 HFC13...

Страница 17: ...rate minimum of 20 minutes after thermocouples are installed Turn control to colder to obtain required on time Wattage reading must be recorded in conjunction with temperature test to confirm proper o...

Страница 18: ...efrigerant Flow Bottom Mount Refrigerant Flow Diagram EVAPORATOR COMPRESSOR DISCHARGE TUBE CONDENSER CAPILLARY TUBE SUCTION TUBE DRYER PRO CESS TUBE POST CONDENSER TUBE Note Capillary Tube and Suction...

Страница 19: ...Flow Diagram CRISPER AIR SUPPLY PORT EVAPORATOR FAN ASSEMBLY EVAPORATOR EVAPORATOR COVER FREEZER RETURN AIR THOUGH LOUVERS AT BOTTOM OF EVAPORATOR COVER FREEZER AIR SUPPLY GRILLE REFRIGERATOR RETURN A...

Страница 20: ...20 16023324 Rev 0 2004 Maytag Services Two Way Bottom Mount Machine Compartment Air Flow Diagram Machine Compartment Air Flow Condenser Condenser Fan Assembly Compressor...

Страница 21: ...2004 Maytag Services 16023324 Rev 0 21 One Way Bottom Mount Machine Compartment Air Flow Diagram Machine Compartment Air Flow...

Страница 22: ...ezer door top Freezer door bottom CLASSIFICATION OF CONDENSATION 1 Haze or fog 2 Beading 3 Beads or small drops 4 Drops running together No sweat on side when compressor is running Conditions after 4...

Страница 23: ...tion Overloading of shelves Consumer education Warm or hot foods placed in cabinet Consumer education Cold control set too warm Set control to colder setting Poor door seal Level cabinet Adjust hinges...

Страница 24: ...ystem Refrigerant overcharge Check for overcharge Evacuate and recharge system Unit runs continuously Air in system Check for low side leak Repair evacuate and recharge system Unit runs continuously T...

Страница 25: ...r for continuity If open replace overload NOTE Ensure overload compressor are below trip temperature before testing Faulty compressor motor capacitor some compressors do not require motor capacitor Ch...

Страница 26: ...st system the refrigerant will flood out and cause the suction line to frost or sweat The cause of this problem should be corrected rather than to purge refrigerant from the sytem Running the freezer...

Страница 27: ...ge the system replace the drier filter evacuate and recharge with the specified refrigerant charge If the unit performs normally three possibilities exist 1 refrigerant loss 2 partially restricted dri...

Страница 28: ...he ambient temperature raises Refrigerators installed in ambient temperatures lower than 60 F will not perform as well because the pressures within the system are generally reduced and unbalanced This...

Страница 29: ...ims b Remove toe grille by pulling it directly away from unit and pop plastic cover off bottom door hinge Grille and cover are fragile keep both parts safe from harm c Remove bottom hinge pin and all...

Страница 30: ...Mid Level Electronic Model Light Switch 1 After following procedure on removing light bulb assembly 2 Disconnect wires from light switch 3 Squeeze tab to release light switch from light assembly 4 Re...

Страница 31: ...eased 5 Remove light bulb 6 Squeeze tab holding light housing in place to release housing and remove 7 Disconnect wires to socket 8 Squeeze tab on back side of housing to release socket Light Switch 1...

Страница 32: ...t of plastic clips that hold it to back wall of unit Then roll bottom of evaporator forward and up exposing evaporator heater in its location amid fins at bottom of evaporator 6 Taking care to notice...

Страница 33: ...aight away from unit 2 Raise front of refrigerator at least 101 6mm off the deck and block it up 3 Unscrew leveling bolt until wheel is free of leveling bolt 4 Tip wheel assembly down until wheel asse...

Страница 34: ...ad screws on bottom of cabinet 5 Carefully lower basepan taking care not to kink tubing to compresser or condenser 6 Remove hex screws holding condenser fan shroud to basepan 7 Lift shroud up and out...

Страница 35: ...ram Code the control will not save the new code but will flash the old code and this will be displayed The unit will NOT run with a Program Code of 00 8 Once the Program Code has been saved the Progra...

Страница 36: ...the display will return to a normal operating display with set point values 4 Freezer Refrigerator 4 8 Close the Refrigerator door s You are in the defrost mode Note Forced Defrost mode can be exited...

Страница 37: ...roper defrost function You can observe defrost heat and voltages while the test is activated 1 Freezer Refrigerator O DEFROST THERMOSTAT OPEN 1 Freezer Refrigerator S DEFROST THERMOSTAT SHORTED CLOSED...

Страница 38: ...hort result for a test on the Fresh Food Thermistor circuit as show below The test is activated and de activated via the Refrigerator Up key and must be de activated to move to another test selection...

Страница 39: ...Service Test 7 FF Performance Adjustment This test will allow adjustment of the control performance points Each step will incrementally change the Refrigerator performance warmer towards 1 or colder...

Отзывы: