background image

SYSTEM OPERATION

7

Cooling

The refrigerant used in the system is R-410A. It is a clear, 

colorless, non-toxic and non-irritating liquid. R-410A is a 

50:50 blend of R-32 and R-125. The boiling point at atmo-

spheric pressure is -62.9°F.

A few of the important principles that make the refrigeration 

cycle possible are: heat always flows from a warmer to a 

cooler body. Under lower pressure, a refrigerant will absorb 

heat and vaporize at a low temperature. The vapors may 

be drawn off and condensed at a higher pressure and 

temperature to be used again.

The indoor evaporator coil functions to cool and dehumidify 

the air conditioned spaces through the evaporative process 

taking place within the coil tubes.

NOTE: The pressures and temperatures shown in 

the refrigerant cycle illustrations on the following 

pages are for demonstration purposes only. Actual 

temperatures and pressures are to be obtained from 

the "Expanded Performance Chart".

Liquid refrigerant at condensing pressure and 

temperatures, (270 psig and 122°F), leaves the outdoor 

condensing coil through the drier and is metered into the 

indoor coil through the metering device. As the cool, low 

pressure, saturated refrigerant enters the tubes of the 

indoor coil, a portion of the liquid immediately vaporizes. 

It continues to soak up heat and vaporizes as it proceeds 

through the coil, cooling the indoor coil down to about 48°F.

Heat is continually being transferred to the cool fins and 

tubes of the indoor evaporator coil by the warm system air. 

This warming process causes the refrigerant to boil. The 

heat removed from the air is carried off by the vapor.

As the vapor passes through the last tubes of the coil, it 

becomes superheated. That is, it absorbs more heat than 

is necessary to vaporize it. This is assurance that only 

dry gas will reach the compressor. Liquid reaching the 

compressor can weaken or break compressor valves.

The compressor increases the pressure of the gas, thus 

adding more heat, and discharges hot, high pressure 

super-heated gas into the outdoor condenser coil.

In the condenser coil, the hot refrigerant gas, being 

warmer than the outdoor air, first loses its superheat by 

heat transferred from the gas through the tubes and fins 

of the coil. The refrigerant now becomes saturated, part 

liquid, part vapor and then continues to give up heat until 

it condenses to a liquid alone. Once the vapor is fully 

liquefied, it continues to give up heat which subcools the 

liquid, and it is ready to repeat the cycle.

Cooling Cycle

Cooling Only Models

When the contacts of the room thermostat close, making 

terminals R to Y and R to G, the low voltage circuit to the 

contactor is completed starting the compressor and outdoor 

fan motor. The EEM indoor blower motor is energized at 

the cool speed when the compressor contactor energizes.

When the thermostat is satisfied, breaking the circuit 

between R to Y and R to G, the compressor and outdoor 

fan motor will stop. The indoor blower will stop after the fan 

off delay.

If the room thermostat fan selector switch should be set 

to the “on” position then the indoor blower would run 

continuous rather than cycling with the compressor.  

Heat Pump Models

Any time the room thermostat is switched to cool, the O 

terminal is energized. This energizes the 24 volt coil on the 

reversing valve and switches it to the cooling position.

When the contacts of the room thermostat close, this 

closes the circuit from R to Y and R to G in the unit.

This energizes the compressor contactor and will energize 

the indoor blower on models equipped with the EEM motor. 

When the thermostat is satisfied, it opens its contacts 

breaking the low voltage circuit causing the compressor 

contactor to open and indoor fan to stop after the 

programmed 60 second off delay on units with the EEM 

motor. 

If the room thermostat fan selector switch should be set 

to the “on” position then the indoor blower would run 

continuous rather than cycling with the compressor.  

Heating Cycle

Cooling Only Units

NOTE: The following only applies if the cooling only 

unit has an approved electric heat kit installed for 

heating. If auxiliary electric heaters should be used, 

they may be controlled by outdoor thermostats (OT18-

60A or OT/EHR18-60A).

A/GPC EEM Equipped Model Units

With the thermostat set to the heat position and a call 

for heat, R to W will be energized. This will energize the 

electric heat contactor(s)/sequencer(s) and the EEM indoor 

blower motor. When the normally open contacts of the 

heat contactor(s)/sequencer(s) close, this will energize the 

electric resistance heat.

Содержание A/GPC 14

Страница 1: ...mproper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install adjust service or repair the equipment specified in this manual without proper tr...

Страница 2: ...es seek medical help immediately Always follow EPA regulations Never burn refrigerant as poisonous gas will be produced WARNING To avoid possible injury explosion or death practice safe handling of re...

Страница 3: ...PRODUCT IDENTIFICATION 3 NOMENCLATURE The model number is used for positive identification of component parts used in manufacturing Please use this number when requesting service or parts information...

Страница 4: ...PRODUCT IDENTIFICATION 4 NOMENCLATURE The model number is used for positive identification of component parts used in manufacturing Please use this number when requesting service or parts information...

Страница 5: ...e Heat Pump 14 SEER R410A Multiposition heating cooling units Initial release of single phase models GPH14 24 60 M41AA Goodman Brand Package Heat Pump 14 SEER R410A Multiposition heating cooling units...

Страница 6: ...s Release of models with access box removed APH1660M41AA Amana Brand Package Heat Pump up to 16 SEER R410A Multiposition heating cooling units Converting light commercial 6 ton unit to 5 ton residenti...

Страница 7: ...the gas through the tubes and fins of the coil The refrigerant now becomes saturated part liquid part vapor and then continues to give up heat until it condenses to a liquid alone Once the vapor is fu...

Страница 8: ...60A or OT EHR18 60A Emergency Heat Mode Heat Pumps NOTE The following only applies if the unit has an approved electric heat kit installed for auxiliary heating A GPH EEM Equipped Models Only With the...

Страница 9: ...RATION 9 Indoor Coil Accumulator Outdoor Coil Reversing Valve Energized Indoor Coil Accumulator Outdoor Coil Reversing Valve De Energized Typical Heat Pump System in Cooling Typical Heat Pump System i...

Страница 10: ...MOTOR FAILURE DO NOT OIL 4 Manually rotate the outdoor fan and indoor blower to be sure they run freely 5 Inspect the control panel wiring compressor connections and all other component wiring to be s...

Страница 11: ...tion and loose connections 2 Use an ohmmeter to check continuity of any suspected open wires 3 If any wires must be replaced replace with comparable gauge and insulation thickness Checking Thermostat...

Страница 12: ...alling Multiple power sources may be present Failure to do so may cause property damage personal injury or death 1 Remove the leads from the holding coil 2 Using an ohmmeter test across the coil termi...

Страница 13: ...ents are not required on Scroll compressor equipped units due to a non replaceable check valve located in the discharge line of the compressor However hard start kits are available and may improve low...

Страница 14: ...OHM resistor before handling Using a hookup as shown below take the amperage and voltage readings and use them in the formula Capacitance MFD 2650 X Amperage Voltage Testing Capacitance Checking Fan...

Страница 15: ...flow Because of the sophisticated electronics within the ECM motor some technicians are intimated by the ECM motor however these fears are unfounded GE Regal Beloit offers two ECM motor testers and wi...

Страница 16: ...may be open Allow motor to cool and retest 16 pin connector 5 pin connector 3 pin motor connector Checking Compressor WARNING Hermetic compressor electrical terminal venting can be dangerous When insu...

Страница 17: ...ontinuous replace the compressor NOTE If an open compressor is indicated allow ample time for the internal overload to reset before replacing compressor Ground Test If fuse circuit breaker ground faul...

Страница 18: ...olded plug lead to either of the two female connectors in the plug One of the connectors should read close to zero ohms while the other should read infinity Repeat with other wire The same female conn...

Страница 19: ...sition part of the discharge gas from the compressor is directed back to the suction side resulting in excessively high suction pressure An increase in the suction line temperature through the reversi...

Страница 20: ...heaters may be added in the quantities shown in the spec sheet for each model unit to provide electric resistance heating Under no condition shall more heaters than the quantity shown be installed WA...

Страница 21: ...xygen high pressure air or flammable gases for leak testing of a refrigeration system WARNING To avoid possible explosion the line from the nitrogen cylinder must include a pressure regulator and a pr...

Страница 22: ...utes 3 Evacuate the system to 500 microns and hold for 60 minutes 4 If the pressure rises to 1000 microns or less and remains steady the system is considered leak free proceed to start up Charging WAR...

Страница 23: ...tact and the pressure of the refrigerant in the coil This regulation of the flow prevents the return of liquid refrigerant to the compressor The illustration below shows typical heatpump TXV check val...

Страница 24: ...60 8 6 162 0 57 0 264 0 87 4 366 0 110 4 468 0 129 0 600 0 149 0 62 10 0 164 0 57 7 266 0 87 9 368 0 110 8 470 0 129 3 604 0 149 5 64 11 3 166 0 58 4 268 0 88 4 370 0 111 2 472 0 129 7 608 0 150 1 66...

Страница 25: ...88 86 84 82 80 78 308 90 88 86 84 82 80 317 92 90 88 86 84 82 326 94 92 90 88 86 84 335 96 94 92 90 88 86 345 98 96 94 92 90 88 354 100 98 96 94 92 90 364 102 100 98 96 94 92 374 104 102 100 98 96 94...

Страница 26: ...143 B Corresponding Temp F 50 C Thermometer on Suction Line 61 F To obtain the degrees temperature of superheat subtract 50 0 from 61 0 F The difference is 11 Superheat The 11 Superheat would fall in...

Страница 27: ...is complete Subcooling Sat Liquid Temp Liquid Line Temp Heat Pump Heating Cycle The proper method of charging a heat pump in the heat mode is by weighing the charge according to the total charge list...

Страница 28: ...ill valves 2 Start the system and allow the pressures to stabilize 3 Stop the system and check the time it takes for the high and low pressure gauge readings to equalize If it takes more than seven 7...

Страница 29: ...o burned residue and contaminates 1 Remove compressor discharge line strainer 2 Remove the liquid line drier and expansion valve 3 Purge all remaining components with dry nitrogen or carbon dioxide un...

Страница 30: ...if so desired 4 Consult proper table for quantity of air If the external static pressure exceeds the minimum or maximum allowable statics check for closed dampers dirty filters undersized or poorly l...

Страница 31: ...JUNCTION BOX BL W2 C R Y O W1 G E TYPICAL HP ROOM THERMOSTAT 1 2 OUTDOOR THERMOSTAT CLOSE ON TEMPERATURE FALL PACKAGE UNIT LOW VOLTAGE JUNCTION BOX BLUE BROWN WHITE ORANGE GREEN YELLOW RED SEE NOTE 1...

Страница 32: ...Y G R BL BL BR W BR W 3 BL Y PACKAGE SYSTEM WIRING DIAGRAM HEAT PUMPS ONLY TWO STAGE ELECTRIC HEAT ABOVE 10 kW For outdoor temperatures below 0 F with 50 or higher relative humidity set outdoor therm...

Страница 33: ...ONE 1 ELEMENT ROWS TWO 2 ELEMENT ROWS FL M1 M2 FL FL M1 M2 M3 M4 5 KW 10 KW L1 BK BK L2 L1 L2 R Y M1 M2 BK R Y R R1 M4 R BK M3 HTR3 TL HTR2 HTR1 TL TL PU M2 R2 Y M1 BL W BR BL R BK R BK TL HTR1 BK HT...

Страница 34: ...EX 3597706 500 48926 002 ORANGE 1 X 78 GROUND 1 X 50 COLOR CODES FOR PLUG 1 8 O ORANGE GROUND G GREEN WIRE LENGTHS FOR PLUG 1 9 8 7 3 2 1 G Y2 TSTAT Y1 CONTACTOR COMMON Y1 TSTAT O 6 5 4 CC1 Y Y2 CONTA...

Страница 35: ...VE BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER 4 START ASSIST FACTOR EQUIPPED WHEN REQUIRED 5 USE COPPER CONDUCTORS ONLY USE N E C CLASS 2 WIRE 6 CRANKCASE HEATER OPTIONAL 7 DOUBLE POLE CO...

Страница 36: ...5 C USE COPPER CONDUCTO R ONLY 2 TO CHANGE EVAPORATOR MOTOR SPEED MOVE YELLOW AN D WHITE LEADS FROM EM 2 AND 3 TO 4 AND 5 IF BO TH LEADS ARE ENERGIZED THE HIGHER SPEED SETTING IS USED 3 FOR 208 VOLT T...

Страница 37: ...WHITE LEADS FROM EM 2 AND 3 TO 4 AND 5 IF BO TH LEADS ARE ENERGIZED THE HIGHER SPEED SETTING IS USED 3 FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK W IRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER...

Страница 38: ...FROM VSTB AND TO THERMOSTAT R SEE INSTALLATION INSTRUCTIONS FOR DETAILS CUT HUM JUMPER ON VSTB SEE UNIT RATING PLATE FOR TYPE AND SIZE OF OVER CURRENT PROTECTION 208 230 1 60 0140G03222 A COM P ON E...

Страница 39: ...RD RED 4 DFT BR BK BK CNT Y1 TR 0 H R O GR Y1 C 2 2 C 3 BR SUPPLY VOLTAGE WH O RD Y1 BL SEE NOTE 7 BOX GR GR GREEN RD PU GR GR 240 C T3 24V OR BL CCR WH C 6 STAT W WH PLF2 WH C EM WH W Y2 SEE NOTE 5...

Страница 40: ...3 TO 4 AND 5 IF BOTH LEADS ARE ENERGIZ ED THE HIGHER SPEED SETTING IS USED 3 FOR 208 VOL T TR ANSFORM ER OPERATION MOVE BLACK W IRE FROM TERMINAL 3 TO TERMINAL 2 ON TRANSF ORM ER 4 START ASSIS T FACTO...

Страница 41: ...1 BL SEE NOTE 7 BOX GR GR GREEN RD GR GR 240 C T3 24V OR BL CCR C 6 WH PLF2 C EM WH SEE NOTE 5 REPLACE JUMPER WITH SMOKE FIRE DETECTOR 5 RD T2 LPS PLF 1 R BK C 2 R PS1 S N HPS BL LINE VOLTAGE 1 2 C NO...

Страница 42: ...ontact us Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page GOODMAN BRA...

Отзывы: