AMALGAMATED INSTRUMENT LC-CL Series Скачать руководство пользователя страница 16

changes or to move on to the next setpoint. Note: this easy access also functions in the same manner for
the PI control setpoint (relay and/or analog PI output) if PI control is available. The instrument must
be set in the manner described below to allow the easy access facility to work:

1. The

R.INP

function must be set to

SPAC

or the

ACCS

function must be set to

EASY

.

2. At least one alarm must have a setpoint, nothing will happen if all the alarm setpoints are set to

OFF

.

3. The

SPAC

function must be set to allow access to the relays required e.g. if set to

A1-2

then the

easy access will work only with alarm relays 1 and 2 even if more relays are fitted.

4. The instrument must be in normal measure mode i.e. if the instrument is powered up so that it is

in

CAL

mode then the easy access will not function. If in doubt remove power from the instrument,

wait for a few seconds then apply power again.

5. If the easy access facility is used then the only way to view or alter any other function settings is

to power up via

CAL

mode i.e. there is no entry to

FUNC

mode functions unless the instrument is

powered up in

CAL

mode.

4.1

Alarm relay 1 low setpoint

Display:

A1Lo

Range:

Any display value or

OFF

Default Value:

OFF

Displays and sets the low setpoint value for alarm relay 1. Use this low setpoint function if a relay
operation is required when the display value becomes equal to or less than the low setpoint value. To set
a low alarm value go to the

A1Lo

function and use the

^

or

v

push buttons to set the value required

then press

F

to accept this value. The low alarm setpoint may be disabled by pressing the

^

and

v

push buttons simultaneously. When the alarm is disabled the display will indicate

OFF

. If the relay is

allocated both a low and high setpoint then the relay will activate when the value displayed moves outside
the band set by the low and high setpoints. The value at which the relay will reset is controlled by the

A1HY

function.

Example:

If

A1Lo

is set to

10

then relay 1 will activate when the display value is 10 or less.

16 of

44

LDRSMANADD-2.3-0

Содержание LC-CL Series

Страница 1: ...lay Arithmetic and Wind Speed Direction Addendum AMALGAMATED INSTRUMENT CO PTY LTD ACN 001 589 439 Unit 5 28 Leighton Place Hornsby Telephone 61 2 9476 2244 e mail sales aicpl com au NSW 2077 Australi...

Страница 2: ...allation 4 3 Function tables Arithmetic mode 10 4 Arithmetic and Wind Speed Direction mode functions 15 5 Arithmetic function examples 40 6 Function table Wind Speed and Direction mode 41 7 Wind speed...

Страница 3: ...o 20 0 seconds The instruments polled for arithmetic operation must be of the same manufacture as this instrument To operate in this mode the COdE function must be set to ARth Wind speed and direction...

Страница 4: ...is manual to confirm proper selection of voltage polarity and input type before applying power to the instrument When power is applied the instrument will cycle through a display sequence indicating t...

Страница 5: ...olated DC supply E IN Optional isolated dc board for use with 100mm 200mm led displays and 100mm electromagnetic displays only CASE EARTH Input DC 12 24V Output DC to display board 2 5 100mm and 200mm...

Страница 6: ...ge instruments use a different transformer Do not use a low voltage transformer for 240V or 110V or vice versa 110VAC 42VAC 32 TO 36VAC 24VAC ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE ACTIVE NEUTRAL NEUTRAL...

Страница 7: ...g RS232 to a 9 or 25 pin D type connector the standard connections are as follows 9 pin Tx pin 3 Rx pin 2 GND pin 5 25 pin Tx pin 2 Rx pin 3 GND pin 7 See note below regarding Tx and Rx crossing when...

Страница 8: ...ith connections on terminal P2 The relays are single pole single throw types and are rated at 5A 240VAC into a resistive load The relay contacts are voltage free and may be programmed for normally ope...

Страница 9: ...S MMW 005 wind speed and direction sensor The WS MMW 005 can be connected as either RS232 or RS485 not serial current loop use the connection type which matches the input type of the display LDRSMANAD...

Страница 10: ...e delay for alarm relay 1 0 0 to 999 9 0 0 4 9 19 A2rt Reset time delay for alarm relay 2 0 0 to 999 9 0 0 4 10 19 A1n o or A1n c Alarm relay 1 action to normally open or normally closed A1n o or A1n...

Страница 11: ...to t8 P1 4 31 24 Ch7 Addr Channel 7 address P1 to P8 or S1 to S8 or t1 to t8 P1 4 32 24 Ch8 Addr Channel 8 address P1 to P8 or S1 to S8 or t1 to t8 P1 4 33 24 Ch1 dCPt Channel 1 decimal point 0 0 1 et...

Страница 12: ...32767 1 4 53 28 EA5 EA5 value for arithmetic formula 32727 to 32767 1 4 54 28 Eb5 Eb5 value for arithmetic formula 32727 to 32767 0 4 55 28 EC5 EC5 value for arithmetic formula 32727 to 32767 1 4 56 2...

Страница 13: ...70 32 OP6 Arithmetic operation between channel 7 and previous operation Add Sub Prod diU High Lo SINE or COS Add 4 71 32 OP7 Arithmetic operation between channel 8 and previous operation Add Sub Prod...

Страница 14: ...ss mode OFF EASY NONE or ALL OFF 4 85 36 SPAC Setpoint access mode Optional A1 A1 2 etc A1 4 86 36 A1 Alarm relay 1 operation channel ch0 to ch8 ch0 4 91 38 A2 Alarm relay 2 operation channel ch0 to c...

Страница 15: ...now indicate followed by the first function 2 Within 2 seconds of releasing the button press then release the and buttons together The display will now indicate followed by the first function FUNC FU...

Страница 16: ...used then the only way to view or alter any other function settings is to power up via CAL mode i e there is no entry to FUNC mode functions unless the instrument is powered up in CAL mode 4 1 Alarm r...

Страница 17: ...high setpoint then the relay will activate when the value displayed moves outside the band set by the low and high setpoints The value at which the relay will reset is controlled by the A1HY function...

Страница 18: ...isplay value falls to 20 0 or below and will reset when the display value goes above 30 0 i e at 30 1 or above The hysteresis units are expressed in displayed engineering units Example If A1Hi is set...

Страница 19: ...A1rt is set to 10 0 seconds then the resetting of alarm relay 1 will be delayed by 10 seconds 4 10 Alarm relay 2 reset time Display A2rt Range 0 0 to 999 9 Default Value 0 0 Displays and sets the alar...

Страница 20: ...o 50 then Alarm 1 will activate at 1000 and alarm 2 will activate at 1050 i e 1000 50 If Alarm 2 had been set at 50 then alarm 2 would activate at 950 i e 1000 50 4 14 Display brightness Display brGt...

Страница 21: ...The high brightness level sets the maximum brightness which the automatic brightness control can achieve with 63 being the highest intensity 4 18 Automatic display brightness adjustment low level Dis...

Страница 22: ...ay may take to reach its final value when the input is changed similarly the relay operation and any output options will be slowed down when the filter setting is increased To set the digital filter v...

Страница 23: ...ndary values are available for that instrument The primary value is the main display value for that instrument e g For a conductivity instrument the conductivity would be the primary value and the tem...

Страница 24: ...26 for further information 4 32 Channel 7 address Display Ch7 Addr Range P1 to P8 or S1 to S8 or t1 to t8 Default Value P1 Seen only when Code function is set to SCAN or Arth Scan address for channel...

Страница 25: ...s and sets the decimal point for input channel 2 See function 4 34 for further details 4 38 Channel 5 decimal point Display Ch5 dCPt Range 0 0 1 etc Default Value 0 Seen only in CodE Arth mode Display...

Страница 26: ...Ch2 Eb2 EC2 Add Sub Prod diU hIGh Lo SinE Cos C SUb EA3 Ch3 Eb3 EC3 etc for the remaining active channels Note A and C are whole numbers b has the same decimal place setting as its associated channel...

Страница 27: ...isplays and sets the EA3 value to be used in the arithmetic formula See function 4 42 for further details 4 49 Channel 3 Eb3 value for arithmetic formula Display Eb3 Range 32727 to 32767 Default Value...

Страница 28: ...e EA5 value to be used in the arithmetic formula See function 4 42 for further details 4 55 Channel 5 Eb5 value for arithmetic formula Display Eb5 Range 32727 to 32767 Default Value 0 Seen only in Cod...

Страница 29: ...e EA7 value to be used in the arithmetic formula See function 4 42 for further details 4 61 Channel 7 Eb7 value for arithmetic formula Display Eb7 Range 32727 to 32767 Default Value 0 Seen only in Cod...

Страница 30: ...formula Sub channel 1 formula minus channel 2 formula Prod channel 1 formula times channel 2 formula diU channel 1 formula divided by channel 2 formula High highest of channel 1 formula or channel 2...

Страница 31: ...and OP2 times channel 4 formula diU mathematical result of OP1 and OP2 divided by channel 4 formula High highest of mathematical result of OP1 and OP2 or channel 4 formula Lo lowest of mathematical r...

Страница 32: ...formula Lo lowest of mathematical result of OP1 and OP2 and OP3 and OP4 or channel 6 formula Sine mathematical result of OP1 and OP2 and OP3 and OP4 times the sine of the angle represented by channel...

Страница 33: ...nd OP6 or channel 8 formula Lo lowest of mathematical result of OP1 and OP2 and OP3 and OP4 and OP5 and OP6 or channel 8 formula Sine mathematical result of OP1 and OP2 and OP3 and OP4 and OP5 and OP6...

Страница 34: ...and sets the polarity selection for the display of the engineering value for channel 3 See function 4 74 for further information 4 77 Channel 4 polarity Display Ch4 Range both POS or NEG Default Value...

Страница 35: ...e new mode ARTH mode Arithmetic mode In this mode the display can accept inputs from up to 8 external sources and combine them arithmetically using a flexible formula see the EA1 formula for details o...

Страница 36: ...to gain access to alarm and calibration functions If set to ALL then access to all functions including calibration functions can be gained via FUNC mode 4 86 Setpoint access mode Display SPAC Range A1...

Страница 37: ...function is set to UAL Remote input function When these remote input terminals are short circuited via a switch relay keyswitch etc the instrument will perform the selected remote input function A me...

Страница 38: ...brightness control The remote input can be used to change the display brightness When this mode is selected the display brightness can be switched via the remote input terminals between the brightnes...

Страница 39: ...for 8 data bits plus 1 stop bit or 7 bit for 7 data bits plus 1 stop bit This must be set to match the number of data bits of the sending device 4 97 Serial communications type Display SER 1 tYPE Rang...

Страница 40: ...est of the 3 inputs Channel 1 input is to be multiplied 2 3 Program EA1 2 Eb1 0 EC1 3 EA2 1 Eb2 0 EC2 1 EA3 1 Eb3 0 EC3 1 OP1 HiGH OP2 HiGH 2 Ch1 0 3 HIGH 1 Ch2 0 1 HIGH 1 Ch3 0 1 Example 3 To multipl...

Страница 41: ...9 0 0 4 8 19 A1rt Reset time delay for alarm relay 1 0 0 to 999 9 0 0 4 9 19 A2rt Reset time delay for alarm relay 2 0 0 to 999 9 0 0 4 10 19 A1n o or A1n c Alarm relay 1 action to normally open or n...

Страница 42: ...input external input one function NONE P HLd d HLd Hi Lo HiLo tARE ZERO SP Ac No Ac or duLL NONE 4 90 37 ACCS Access mode OFF EASY NONE or ALL OFF 4 85 36 SPAC Setpoint access mode Optional A1 A1 2 e...

Страница 43: ...t to 4800 with no parity PrtY function and 8 data bits dAtA function The display can be set to show wind speed wind direction or to toggle using or v button or automatically alternate the display betw...

Страница 44: ...SO N 14 0E 9 57 39 d 100 64 SI O 15 0F 58 3A e 101 65 DLE P 16 10 59 3B f 102 66 DC1 Q 17 11 60 3C g 103 67 DC2 R 18 12 61 3D h 104 68 DC3 S 19 13 62 3E i 105 69 DC4 T 20 14 63 3F j 106 6A NAK U 21 15...

Отзывы: