ASX180361* - ASX180601*
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device:
MUST
use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•
Always check the S & R plate for electrical data on the unit being installed.
•
Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•
Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•
Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•
Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
A
S
X
180
36
1
*
A
S
X
1
8
0
48
1*
AS
X
1
8
0
60
1*
Cooling Capacity, BTUH
36,000
48,000
60,000
Compressor
R.L. Amps
16.7
21.2
25.6
L.R. Amps
82.0
96.0
118.0
Low Pressure Switch
Open
22 + / - 7 PSIG
22 + / - 7 PSIG
22 + / - 7 PSIG
Close
50 + / - 7 PSIG
50 + / - 7 PSIG
50 + / - 7 PSIG
High Pressure Switch
Open
610 PSIG
610 PSIG
610 PSIG
Close
420 PSIG
420 PSIG
420 PSIG
Condenser Fan Motor
Horsepower
1/3
1/3
1/3
F.L. Amps
2.8
2.8
2.8
Liquid Line, Inches O.D.*
3/8"
3/8"
3/8"
Suction Line, Inches O.D.*
7/8"
1 1/8"
1 1/8"
Refrigerant Charge
187.0
262.0
262.0
Power Supply
208/230-60-1
208/230-60-1
208/230-60-1
Minimum Circuit Ampacity
(1)
23.7
29.3
34.8
Maximum Overcurrent Device
(2)
40
50
60
Electr ical Conduit Size
Power Supply (Inches)
1/2 or 3/4
1/2 or 3/4
1/2 or 3/4
Approximate Shipping Weight
270
320
330