PRODUCT DESIGN

4

ASX18 models are available in 3 4 and 5 ton sizes and use
R-410A refrigerant. They are designed for 208/230 volt single
phase applications.

The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then dis-
charged out of the top of the cabinet.

These units are designed for free air discharge, so no addi-
tional resistance like duct work shall be attached.

The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type cop-
per. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal in-
stallation is factory installed in the condensing unit.ASX units
are charged for the matching evaporator coil and a 15 foot
refrigerant line set.

Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent.  It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.

ASX16 models use the Copeland Scroll "Ultratech" Series
compressors which are specifically designed for R-410A re-
frigerant.  There are a number of design characteristics which
are different from the traditional reciprocating and/or scroll
compressors.

"Ultratech" Series scroll compressors with Copeland

®

ComfortAlert diagnostics will not have a discharge thermo-
stat, some of the early model scroll compressors required
discharge thermostats.

"Ultratech" Series scroll compressors will not have a dis-
charge thermo-stat. Some of the early model scroll compres-
sors requireddischarge thermostats. Due to their design Scroll
compressors are inherently more tolerant of small quantities
of liquid refrigerant.

NOTE:  Even though the compressor section of a Scroll com-
pressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.

"Ultratech" Series scroll compressors use "POE" or
polyolester oil  which is 

NOT

 compatible with mineral oil based

lubricants like 3GS.  "POE"  oil must be used if additional oil
is required.

WARNING

To avoid possible injury, explosion or death, practice
safe handling of refrigerants.

Operating pressures and amp draws may differ from stan-
dard reciprocating and/or scroll compressors.  This informa-
tion may be found in the "Cooling Performance Data" sec-
tion.

This unit is for outdoor installation only. Refer to minimum
figure for clearances from the sides of the unit to full walls
and other objects.

NOTE:

 This unit cannot be completely enclosed. At least

one side must be unrestricted.

These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for ex-
ample, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.

DO 

NOT

 locate the unit:

* Directly under a vent termination for a gas appliance.

* Within 3 feet of a clothes drier vent

* Where the refreezing of defrost water would create

a hazard

* Where water may rise into the unit.

OK!

OK!

AA

AA

A

A

C

C

C

C

OK!

OK!

OK!

OK!

NOT

RECOMMENDED

AA

AA

AA

AA

AA

B

B

B

B

Model Type

A

B

C

AA

Residential

10"

10"

18"

20"

Light Commercial

12"

12"

18"

24"

Minimum Airflow Clearance

Model

Dimensions - W x D x H

ASX180361*

35½ x 35½ x 38¼

ASX180481*

35½ x 35½ x 38¼

ASX180601*

35½ x 35½ x 38¼

Содержание ASX 18 Series

Страница 1: ...2007 2009 2011 Goodman Company L P TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL AL This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or personal injury due to improper service proce dures or services performed by an unqualified person is a registered trademark o...

Страница 2: ...pting to install or repair this unit without such back ground may result in product damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a lice...

Страница 3: ... for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING WARNING To prevent the risk of property damage personal injury or death do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance WARNING WARNING The model nu...

Страница 4: ...rly model scroll compres sors requireddischarge thermostats Due to their design Scroll compressors are inherently more tolerant of small quantities of liquid refrigerant NOTE Even though the compressor section of a Scroll com pressor is more tolerant of liquid refrigerant continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure Ultrat...

Страница 5: ... to supply 3 4 to 7 8 adapters for suction line connections 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be adjusted per Installation Instructions Final Charge Procedure Installation of these units requires the specified TXV Kit to be installed on the indoor coil THE SPECIFIED TXV IS DETERMINED BY THE OUTDOORUNIT NOTTHEINDOORCOIL ASX180361 ASX180481 ASX1...

Страница 6: ... 2 25 9 28 0 30 1 24 6 25 3 27 4 29 4 24 0 24 7 26 7 28 7 22 8 23 4 25 4 27 2 21 1 21 7 23 5 25 2 S T 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43 0 99 0 89 0 67 0 43 Delta T 22 20 17 11 22 20 17 12 22 20 17 12 22 21 17 12 22 20 17 12 21 19 16 11 930 KW 1 30 1 33 1 38 1 43 1 41 1 45 1 50 1 55 1 51 1 55 1 60 1 66 1 60 1 63 1 69 1 75 1 67 1 71 1...

Страница 7: ... 7 3 7 1 7 2 7 5 7 8 7 5 7 7 7 9 8 2 HI PR 206 221 225 230 233 250 254 259 265 285 289 295 302 324 329 336 326 350 355 363 386 415 421 430 LO PR 122 125 137 146 125 129 141 150 129 133 146 155 133 137 150 159 135 140 153 162 139 143 156 166 MBh 26 7 27 2 28 5 30 4 26 0 26 6 27 8 29 7 25 4 25 9 27 1 29 0 24 8 25 3 26 5 28 3 23 6 24 0 25 2 26 8 21 8 22 3 23 3 24 9 S T 0 99 0 96 0 86 0 70 1 00 0 99 0...

Страница 8: ...5 4 38 3 41 1 33 5 34 5 37 4 40 1 32 7 33 7 36 4 39 1 31 1 32 0 34 6 37 2 28 8 29 6 32 1 34 4 S T 0 86 0 77 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 67 0 43 0 99 0 89 0 67 0 43 Delta T 21 19 16 11 21 20 16 11 21 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10 1325 KW 1 87 1 91 1 97 2 04 2 02 2 07 2 14 2 22 2 16 2 21 2 29 2 37 2 28 2 34 2 42 2 51 2 39 2 44 2 53...

Страница 9: ... 6 9 8 10 1 10 5 10 2 10 4 10 8 11 2 HI PR 212 227 231 236 239 257 261 267 272 292 297 303 310 333 338 345 348 375 380 388 390 420 426 435 LO PR 119 123 134 143 123 126 138 147 127 131 143 152 130 134 147 156 133 137 149 159 136 140 153 163 MBh 36 4 37 1 38 9 41 5 35 6 36 2 38 0 40 5 34 7 35 4 37 1 39 5 33 9 34 5 36 2 38 6 32 2 32 8 34 3 36 6 29 8 30 4 31 8 33 9 S T 0 99 0 96 0 87 0 70 1 00 0 99 0...

Страница 10: ...6 9 50 3 41 1 42 3 45 8 49 1 40 1 41 3 44 7 47 9 38 1 39 2 42 4 45 5 35 3 36 3 39 3 42 2 S T 0 83 0 74 0 56 0 36 0 86 0 77 0 58 0 37 0 88 0 79 0 59 0 38 0 91 0 81 0 61 0 39 0 94 0 84 0 64 0 41 0 95 0 85 0 64 0 41 Delta T 22 20 16 11 22 20 16 11 22 20 16 11 22 20 17 11 22 20 16 11 20 19 15 11 1520 KW 2 43 2 49 2 57 2 67 2 64 2 70 2 79 2 89 2 82 2 89 2 99 3 10 2 98 3 05 3 16 3 28 3 12 3 19 3 31 3 43...

Страница 11: ... 7 14 0 14 5 15 1 14 5 14 8 15 4 16 0 HI PR 222 238 242 247 243 262 265 271 285 306 311 318 325 349 354 362 365 393 398 407 422 454 460 470 LO PR 116 119 130 139 119 123 134 143 123 127 138 147 126 130 142 151 129 133 145 154 132 136 149 158 MBh 44 6 45 5 47 6 50 8 43 6 44 4 46 5 49 6 42 5 43 4 45 4 48 4 41 5 42 3 44 3 47 3 39 4 40 2 42 1 44 9 36 5 37 2 39 0 41 6 S T 0 95 0 92 0 83 0 67 0 98 0 95 ...

Страница 12: ...6 43 6 35 6 36 7 39 7 42 6 34 7 35 8 38 7 41 5 33 0 34 0 36 8 39 5 30 6 31 5 34 1 36 6 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 65 0 42 0 96 0 86 0 65 0 42 Delta T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11 1330 KW 2 09 2 14 2 21 2 28 2 26 2 31 2 39 2 48 2 41 2 47 2 56 2 65 2 55 2 61 2 70 2 80 2 66 2 73 2 82 2 92 2...

Страница 13: ...2 10 9 11 2 11 5 12 0 11 6 11 8 12 3 12 7 HI PR 216 232 235 241 244 262 266 272 278 298 303 309 316 340 345 352 341 367 372 380 405 435 441 451 LO PR 116 120 131 139 120 123 135 143 124 127 139 148 127 131 143 152 129 134 146 155 133 137 149 159 MBh 38 7 39 4 41 3 44 0 37 8 38 5 40 3 43 0 36 9 37 6 39 4 42 0 36 0 36 7 38 4 41 0 34 2 34 8 36 5 38 9 31 7 32 3 33 8 36 1 S T 0 96 0 93 0 84 0 68 1 00 0...

Страница 14: ... 3 53 4 57 3 46 8 48 1 52 1 55 9 45 6 47 0 50 8 54 6 43 3 44 6 48 3 51 8 40 1 41 3 44 7 48 0 S T 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 92 0 83 0 63 0 40 0 95 0 85 0 65 0 42 0 99 0 89 0 67 0 43 1 00 0 89 0 68 0 44 Delta T 20 18 15 10 20 19 15 10 20 19 15 11 20 19 15 11 20 18 15 10 19 17 14 10 1970 KW 2 87 2 94 3 03 3 13 3 10 3 17 3 27 3 38 3 30 3 37 3 48 3 60 3 47 3 55 3 67 3 80 3 62 3 70 3 83 ...

Страница 15: ...0 13 6 13 9 14 4 15 0 14 4 14 8 15 3 15 9 HI PR 223 240 243 249 252 271 275 281 287 308 313 320 327 351 356 364 367 395 401 409 411 442 449 459 LO PR 118 122 133 142 122 125 137 146 126 130 142 151 129 133 145 155 132 136 148 158 135 139 152 162 MBh 50 8 51 8 54 2 57 8 49 6 50 6 53 0 56 5 48 4 49 4 51 7 55 1 47 2 48 2 50 4 53 8 44 9 45 7 47 9 51 1 41 6 42 4 44 4 47 3 S T 1 00 0 97 0 87 0 71 1 00 1...

Страница 16: ... 8 64 8 69 5 56 7 58 4 63 2 67 8 55 3 57 0 61 7 66 2 52 6 54 1 58 6 62 9 48 7 50 1 54 3 58 3 S T 0 83 0 75 0 56 0 36 0 86 0 77 0 58 0 38 0 89 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96 0 86 0 65 0 42 Delta T 20 19 15 11 20 19 15 11 21 19 15 11 21 19 16 11 20 19 15 11 19 18 14 10 2250 KW 3 87 3 96 4 09 4 22 4 18 4 27 4 41 4 56 4 45 4 55 4 70 4 86 4 69 4 80 4 96 5 13 4 89 5 00 5 17 ...

Страница 17: ...0 20 2 20 8 21 5 22 3 21 4 22 0 22 7 23 6 HI PR 236 254 258 263 259 279 283 289 304 327 331 339 346 372 377 386 389 419 424 434 450 484 490 501 LO PR 113 116 127 135 116 120 131 139 120 124 135 144 123 127 139 148 126 130 142 151 129 133 145 155 MBh 61 6 62 8 65 8 70 2 60 2 61 3 64 2 68 5 58 7 59 9 62 7 66 9 57 3 58 4 61 2 65 3 54 4 55 5 58 1 62 0 50 4 51 4 53 8 57 4 S T 0 96 0 92 0 83 0 68 0 99 0...

Страница 18: ...2 963 90 43 763 31 174 12 589 3 048 95 43 223 31 277 11 945 3 133 100 42 142 31 073 11 069 3 205 105 41 061 30 839 10 222 3 278 110 39 549 29 828 9 721 3 340 115 38 036 28 806 9 229 3 402 95 40 052 30 965 9 087 3 025 TVA Conditions 95 OD DB 75 ID DB 63 ID WB ASX180601A CA F4961 6 TXV MBE2000 1 Design Subcooling AHRI 95 F Conditions 5 7 F the Serv Vlv Low Stage Outdoor Temp F Total Btuh Sensible Bt...

Страница 19: ...372 80 38 874 27 318 11 556 2 453 85 38 406 27 327 11 078 2 534 90 37 937 27 429 10 508 2 605 95 37 469 27 520 9 949 2 677 100 36 532 27 340 9 192 2 737 105 35 596 27 135 8 461 2 798 110 34 284 26 244 8 040 2 850 115 32 973 25 346 7 627 2 903 95 34 720 27 245 7 476 2 586 TVA Conditions 95 OD DB 75 ID DB 63 ID WB ASX180361A CA F4961 6 TXV MBE2000 1 Design Subcooling AHRI 95 F Conditions 5 7 F the S...

Страница 20: ...NT CODE C CONTACTOR CADM COMFORT ALERT MODULE CM OUTDOOR FAN MOTOR COMP COMPRESSOR CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVJB LOW VOLTAGE JUNCTION BOX RC COMPRESSOR RUN CAPACITOR SA START ASSIST SC START CAPACITOR FOR COMPRESSOR OPTIONAL SR START RELAY FOR COMPRESSOR OPTIONAL CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION OUTDOOR POWER SUPPLY ...

Страница 21: ... SCHEMATIC SHOWS THE LEGACY WIRING FROM THE FACTORY THE WIRES GO TO INDOOR T STAT AS SHOWN IN LEGACY INDOOR T STAT TO WIRE THE SYSTEM IN COMMUNICATING MODE THE INSTALLER HAS TO WORK THE WIRING AS SHOWN IN COMMUNICATING INDOOR T STAT REFER TO THE IO MANUAL LOCATED IN COMMUNICATING T STAT KIT FOR MORE DETAILS FROM OUTDOOR UNIT FROM OUTDOOR UNIT GND L1 L2 BK YL YL CM RES 2 5 1 SR SC OPTIONAL HARD STA...

Отзывы: