background image

19

PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb tem-
perature.  .00 inches external static pressure
on coil of outdoor section.  Indoor air cubic feet
per minute (CFM) as listed in the Performance
Data Sheets:

If conditions vary from this, results will change
as follows:

1.

As indoor dry bulb temperatures in-

crease, a slight increase will occur in
indoor air temperature drop (Delta T).
Low and high side pressures and power
will not change.

2.

As indoor CFM decreases, a slight in-

crease will occur in indoor temperature
drop (Delta T).  A slight decrease will
occur in low and high side pressures
and power.

A properly operating unit should be within the
subcooling value shown in the Air Conditioning
Specifications.

A properly operating unit should be within plus
or minus 

3 degrees

 of the typical (Delta T) value

shown.

A properly operating unit should be within plus
or minus 

7 PSIG

 of the 

HI PR

 shown.

A properly operating unit should be within plus
or minus 

3 PSIG

 of the 

LO PR

 shown.

A properly operating unit should be within plus
or minus 

3 Amps

 of the typical value shown.

NOTE: Pressures are measured at the liquid
and suction service valve ports.

HIGH STAGE

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

39,342

27,300

12,043

2,372

80°

38,874

27,318

11,556

2,453

85°

38,406

27,327

11,078

2,534

90°

37,937

27,429

10,508

2,605

95°

37,469

27,520

9,949

2,677

100°

36,532

27,340

9,192

2,737

105°

35,596

27,135

8,461

2,798

110°

34,284

26,244

8,040

2,850

115°

32,973

25,346

7,627

2,903

95°

34,720

27,245

7,476

2,586

TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB

ASX180361A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5-7°F @ the Serv. Vlv. - 
High Stage

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

51,668

37,197

14,471

3,244

80°

51,053

37,221

13,831

3,349

85°

50,438

37,234

13,203

3,454

90°

49,823

37,373

12,450

3,547

95°

49,208

37,497

11,711

3,640

100°

47,977

37,252

10,725

3,718

105°

46,747

36,972

9,775

3,797

110°

45,025

35,759

9,266

3,865

115°

43,303

34,535

8,768

3,933

95°

45,598

37,122

8,476

2,586

TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB

ASX180481A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5- 7°F @ the Serv. Vlv. - 
High Stage

Outdoor

Temp. ° F.

Total 

Btuh

Sensible

Btuh

Latent

Btuh

Total

 Watts

75°

62,686

43,209

19,476

4,377

80°

61,939

43,238

18,702

4,520

85°

61,193

43,253

17,940

4,662

90°

60,447

43,414

17,033

4,788

95°

59,701

43,558

16,143

4,915

100°

58,208

43,274

14,934

5,022

105°

56,715

42,948

13,767

5,129

110°

54,626

41,539

13,087

5,221

115°

52,536

40,117

12,420

5,314

95°

55,321

43,122

12,199

4,755

TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB

ASX180601A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5-7°F @ the Serv. Vlv. - 
High Stage

ASX180361* - ASX180601*

Содержание ASX 18 Series

Страница 1: ...2007 2009 2011 Goodman Company L P TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANU TECHNICAL MANUAL AL AL AL AL This manual is to be used by qualified professionally trained HVAC technicians only Goodman does not assume any responsibility for property damage or personal injury due to improper service proce dures or services performed by an unqualified person is a registered trademark o...

Страница 2: ...pting to install or repair this unit without such back ground may result in product damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or service procedures If you install or perform service on this unit you assume responsibility for any personal injury or property damage which may result Many jurisdictions require a lice...

Страница 3: ... for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING WARNING To prevent the risk of property damage personal injury or death do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this appliance WARNING WARNING The model nu...

Страница 4: ...rly model scroll compres sors requireddischarge thermostats Due to their design Scroll compressors are inherently more tolerant of small quantities of liquid refrigerant NOTE Even though the compressor section of a Scroll com pressor is more tolerant of liquid refrigerant continued floodback or flooded start conditions may wash oil from the bearing surfaces causing premature bearing failure Ultrat...

Страница 5: ... to supply 3 4 to 7 8 adapters for suction line connections 3 ton unit Unit is charged with refrigerant for 15 of 3 8 liquid line System charge must be adjusted per Installation Instructions Final Charge Procedure Installation of these units requires the specified TXV Kit to be installed on the indoor coil THE SPECIFIED TXV IS DETERMINED BY THE OUTDOORUNIT NOTTHEINDOORCOIL ASX180361 ASX180481 ASX1...

Страница 6: ... 2 25 9 28 0 30 1 24 6 25 3 27 4 29 4 24 0 24 7 26 7 28 7 22 8 23 4 25 4 27 2 21 1 21 7 23 5 25 2 S T 0 86 0 77 0 58 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 66 0 43 0 99 0 89 0 67 0 43 Delta T 22 20 17 11 22 20 17 12 22 20 17 12 22 21 17 12 22 20 17 12 21 19 16 11 930 KW 1 30 1 33 1 38 1 43 1 41 1 45 1 50 1 55 1 51 1 55 1 60 1 66 1 60 1 63 1 69 1 75 1 67 1 71 1...

Страница 7: ... 7 3 7 1 7 2 7 5 7 8 7 5 7 7 7 9 8 2 HI PR 206 221 225 230 233 250 254 259 265 285 289 295 302 324 329 336 326 350 355 363 386 415 421 430 LO PR 122 125 137 146 125 129 141 150 129 133 146 155 133 137 150 159 135 140 153 162 139 143 156 166 MBh 26 7 27 2 28 5 30 4 26 0 26 6 27 8 29 7 25 4 25 9 27 1 29 0 24 8 25 3 26 5 28 3 23 6 24 0 25 2 26 8 21 8 22 3 23 3 24 9 S T 0 99 0 96 0 86 0 70 1 00 0 99 0...

Страница 8: ...5 4 38 3 41 1 33 5 34 5 37 4 40 1 32 7 33 7 36 4 39 1 31 1 32 0 34 6 37 2 28 8 29 6 32 1 34 4 S T 0 86 0 77 0 59 0 38 0 90 0 80 0 61 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 98 0 88 0 67 0 43 0 99 0 89 0 67 0 43 Delta T 21 19 16 11 21 20 16 11 21 20 16 11 22 20 16 11 21 20 16 11 20 18 15 10 1325 KW 1 87 1 91 1 97 2 04 2 02 2 07 2 14 2 22 2 16 2 21 2 29 2 37 2 28 2 34 2 42 2 51 2 39 2 44 2 53...

Страница 9: ... 6 9 8 10 1 10 5 10 2 10 4 10 8 11 2 HI PR 212 227 231 236 239 257 261 267 272 292 297 303 310 333 338 345 348 375 380 388 390 420 426 435 LO PR 119 123 134 143 123 126 138 147 127 131 143 152 130 134 147 156 133 137 149 159 136 140 153 163 MBh 36 4 37 1 38 9 41 5 35 6 36 2 38 0 40 5 34 7 35 4 37 1 39 5 33 9 34 5 36 2 38 6 32 2 32 8 34 3 36 6 29 8 30 4 31 8 33 9 S T 0 99 0 96 0 87 0 70 1 00 0 99 0...

Страница 10: ...6 9 50 3 41 1 42 3 45 8 49 1 40 1 41 3 44 7 47 9 38 1 39 2 42 4 45 5 35 3 36 3 39 3 42 2 S T 0 83 0 74 0 56 0 36 0 86 0 77 0 58 0 37 0 88 0 79 0 59 0 38 0 91 0 81 0 61 0 39 0 94 0 84 0 64 0 41 0 95 0 85 0 64 0 41 Delta T 22 20 16 11 22 20 16 11 22 20 16 11 22 20 17 11 22 20 16 11 20 19 15 11 1520 KW 2 43 2 49 2 57 2 67 2 64 2 70 2 79 2 89 2 82 2 89 2 99 3 10 2 98 3 05 3 16 3 28 3 12 3 19 3 31 3 43...

Страница 11: ... 7 14 0 14 5 15 1 14 5 14 8 15 4 16 0 HI PR 222 238 242 247 243 262 265 271 285 306 311 318 325 349 354 362 365 393 398 407 422 454 460 470 LO PR 116 119 130 139 119 123 134 143 123 127 138 147 126 130 142 151 129 133 145 154 132 136 149 158 MBh 44 6 45 5 47 6 50 8 43 6 44 4 46 5 49 6 42 5 43 4 45 4 48 4 41 5 42 3 44 3 47 3 39 4 40 2 42 1 44 9 36 5 37 2 39 0 41 6 S T 0 95 0 92 0 83 0 67 0 98 0 95 ...

Страница 12: ...6 43 6 35 6 36 7 39 7 42 6 34 7 35 8 38 7 41 5 33 0 34 0 36 8 39 5 30 6 31 5 34 1 36 6 S T 0 84 0 75 0 57 0 37 0 87 0 78 0 59 0 38 0 89 0 80 0 60 0 39 0 92 0 82 0 62 0 40 0 95 0 85 0 65 0 42 0 96 0 86 0 65 0 42 Delta T 22 20 16 11 22 20 17 11 22 20 17 11 22 20 17 12 22 20 16 11 20 19 15 11 1330 KW 2 09 2 14 2 21 2 28 2 26 2 31 2 39 2 48 2 41 2 47 2 56 2 65 2 55 2 61 2 70 2 80 2 66 2 73 2 82 2 92 2...

Страница 13: ...2 10 9 11 2 11 5 12 0 11 6 11 8 12 3 12 7 HI PR 216 232 235 241 244 262 266 272 278 298 303 309 316 340 345 352 341 367 372 380 405 435 441 451 LO PR 116 120 131 139 120 123 135 143 124 127 139 148 127 131 143 152 129 134 146 155 133 137 149 159 MBh 38 7 39 4 41 3 44 0 37 8 38 5 40 3 43 0 36 9 37 6 39 4 42 0 36 0 36 7 38 4 41 0 34 2 34 8 36 5 38 9 31 7 32 3 33 8 36 1 S T 0 96 0 93 0 84 0 68 1 00 0...

Страница 14: ... 3 53 4 57 3 46 8 48 1 52 1 55 9 45 6 47 0 50 8 54 6 43 3 44 6 48 3 51 8 40 1 41 3 44 7 48 0 S T 0 87 0 78 0 59 0 38 0 90 0 81 0 61 0 39 0 92 0 83 0 63 0 40 0 95 0 85 0 65 0 42 0 99 0 89 0 67 0 43 1 00 0 89 0 68 0 44 Delta T 20 18 15 10 20 19 15 10 20 19 15 11 20 19 15 11 20 18 15 10 19 17 14 10 1970 KW 2 87 2 94 3 03 3 13 3 10 3 17 3 27 3 38 3 30 3 37 3 48 3 60 3 47 3 55 3 67 3 80 3 62 3 70 3 83 ...

Страница 15: ...0 13 6 13 9 14 4 15 0 14 4 14 8 15 3 15 9 HI PR 223 240 243 249 252 271 275 281 287 308 313 320 327 351 356 364 367 395 401 409 411 442 449 459 LO PR 118 122 133 142 122 125 137 146 126 130 142 151 129 133 145 155 132 136 148 158 135 139 152 162 MBh 50 8 51 8 54 2 57 8 49 6 50 6 53 0 56 5 48 4 49 4 51 7 55 1 47 2 48 2 50 4 53 8 44 9 45 7 47 9 51 1 41 6 42 4 44 4 47 3 S T 1 00 0 97 0 87 0 71 1 00 1...

Страница 16: ... 8 64 8 69 5 56 7 58 4 63 2 67 8 55 3 57 0 61 7 66 2 52 6 54 1 58 6 62 9 48 7 50 1 54 3 58 3 S T 0 83 0 75 0 56 0 36 0 86 0 77 0 58 0 38 0 89 0 79 0 60 0 39 0 91 0 82 0 62 0 40 0 95 0 85 0 64 0 41 0 96 0 86 0 65 0 42 Delta T 20 19 15 11 20 19 15 11 21 19 15 11 21 19 16 11 20 19 15 11 19 18 14 10 2250 KW 3 87 3 96 4 09 4 22 4 18 4 27 4 41 4 56 4 45 4 55 4 70 4 86 4 69 4 80 4 96 5 13 4 89 5 00 5 17 ...

Страница 17: ...0 20 2 20 8 21 5 22 3 21 4 22 0 22 7 23 6 HI PR 236 254 258 263 259 279 283 289 304 327 331 339 346 372 377 386 389 419 424 434 450 484 490 501 LO PR 113 116 127 135 116 120 131 139 120 124 135 144 123 127 139 148 126 130 142 151 129 133 145 155 MBh 61 6 62 8 65 8 70 2 60 2 61 3 64 2 68 5 58 7 59 9 62 7 66 9 57 3 58 4 61 2 65 3 54 4 55 5 58 1 62 0 50 4 51 4 53 8 57 4 S T 0 96 0 92 0 83 0 68 0 99 0...

Страница 18: ...2 963 90 43 763 31 174 12 589 3 048 95 43 223 31 277 11 945 3 133 100 42 142 31 073 11 069 3 205 105 41 061 30 839 10 222 3 278 110 39 549 29 828 9 721 3 340 115 38 036 28 806 9 229 3 402 95 40 052 30 965 9 087 3 025 TVA Conditions 95 OD DB 75 ID DB 63 ID WB ASX180601A CA F4961 6 TXV MBE2000 1 Design Subcooling AHRI 95 F Conditions 5 7 F the Serv Vlv Low Stage Outdoor Temp F Total Btuh Sensible Bt...

Страница 19: ...372 80 38 874 27 318 11 556 2 453 85 38 406 27 327 11 078 2 534 90 37 937 27 429 10 508 2 605 95 37 469 27 520 9 949 2 677 100 36 532 27 340 9 192 2 737 105 35 596 27 135 8 461 2 798 110 34 284 26 244 8 040 2 850 115 32 973 25 346 7 627 2 903 95 34 720 27 245 7 476 2 586 TVA Conditions 95 OD DB 75 ID DB 63 ID WB ASX180361A CA F4961 6 TXV MBE2000 1 Design Subcooling AHRI 95 F Conditions 5 7 F the S...

Страница 20: ...NT CODE C CONTACTOR CADM COMFORT ALERT MODULE CM OUTDOOR FAN MOTOR COMP COMPRESSOR CS COMPRESSOR SOLENOID HPS HIGH PRESSURE SWITCH IO INTERNAL OVERLOAD LPS LOW PRESSURE SWITCH LVJB LOW VOLTAGE JUNCTION BOX RC COMPRESSOR RUN CAPACITOR SA START ASSIST SC START CAPACITOR FOR COMPRESSOR OPTIONAL SR START RELAY FOR COMPRESSOR OPTIONAL CONTROLS SHOWN WITH THERMOSTAT IN OFF POSITION OUTDOOR POWER SUPPLY ...

Страница 21: ... SCHEMATIC SHOWS THE LEGACY WIRING FROM THE FACTORY THE WIRES GO TO INDOOR T STAT AS SHOWN IN LEGACY INDOOR T STAT TO WIRE THE SYSTEM IN COMMUNICATING MODE THE INSTALLER HAS TO WORK THE WIRING AS SHOWN IN COMMUNICATING INDOOR T STAT REFER TO THE IO MANUAL LOCATED IN COMMUNICATING T STAT KIT FOR MORE DETAILS FROM OUTDOOR UNIT FROM OUTDOOR UNIT GND L1 L2 BK YL YL CM RES 2 5 1 SR SC OPTIONAL HARD STA...

Отзывы: