19
PERFORMANCE DATA
PERFORMANCE TEST
All data based upon listed indoor dry bulb tem-
perature. .00 inches external static pressure
on coil of outdoor section. Indoor air cubic feet
per minute (CFM) as listed in the Performance
Data Sheets:
If conditions vary from this, results will change
as follows:
1.
As indoor dry bulb temperatures in-
crease, a slight increase will occur in
indoor air temperature drop (Delta T).
Low and high side pressures and power
will not change.
2.
As indoor CFM decreases, a slight in-
crease will occur in indoor temperature
drop (Delta T). A slight decrease will
occur in low and high side pressures
and power.
A properly operating unit should be within the
subcooling value shown in the Air Conditioning
Specifications.
A properly operating unit should be within plus
or minus
3 degrees
of the typical (Delta T) value
shown.
A properly operating unit should be within plus
or minus
7 PSIG
of the
HI PR
shown.
A properly operating unit should be within plus
or minus
3 PSIG
of the
LO PR
shown.
A properly operating unit should be within plus
or minus
3 Amps
of the typical value shown.
NOTE: Pressures are measured at the liquid
and suction service valve ports.
HIGH STAGE
Outdoor
Temp. ° F.
Total
Btuh
Sensible
Btuh
Latent
Btuh
Total
Watts
75°
39,342
27,300
12,043
2,372
80°
38,874
27,318
11,556
2,453
85°
38,406
27,327
11,078
2,534
90°
37,937
27,429
10,508
2,605
95°
37,469
27,520
9,949
2,677
100°
36,532
27,340
9,192
2,737
105°
35,596
27,135
8,461
2,798
110°
34,284
26,244
8,040
2,850
115°
32,973
25,346
7,627
2,903
95°
34,720
27,245
7,476
2,586
TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB
ASX180361A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5-7°F @ the Serv. Vlv. -
High Stage
Outdoor
Temp. ° F.
Total
Btuh
Sensible
Btuh
Latent
Btuh
Total
Watts
75°
51,668
37,197
14,471
3,244
80°
51,053
37,221
13,831
3,349
85°
50,438
37,234
13,203
3,454
90°
49,823
37,373
12,450
3,547
95°
49,208
37,497
11,711
3,640
100°
47,977
37,252
10,725
3,718
105°
46,747
36,972
9,775
3,797
110°
45,025
35,759
9,266
3,865
115°
43,303
34,535
8,768
3,933
95°
45,598
37,122
8,476
2,586
TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB
ASX180481A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5- 7°F @ the Serv. Vlv. -
High Stage
Outdoor
Temp. ° F.
Total
Btuh
Sensible
Btuh
Latent
Btuh
Total
Watts
75°
62,686
43,209
19,476
4,377
80°
61,939
43,238
18,702
4,520
85°
61,193
43,253
17,940
4,662
90°
60,447
43,414
17,033
4,788
95°
59,701
43,558
16,143
4,915
100°
58,208
43,274
14,934
5,022
105°
56,715
42,948
13,767
5,129
110°
54,626
41,539
13,087
5,221
115°
52,536
40,117
12,420
5,314
95°
55,321
43,122
12,199
4,755
TVA Conditions @ 95° OD DB, 75° ID DB, 63° ID WB
ASX180601A* / CA*F4961*6** + TXV / MBE2000**-1**,
Design Subcooling @ AHRI 95°F Conditions, 5-7°F @ the Serv. Vlv. -
High Stage
ASX180361* - ASX180601*