Electrical Considerations
The UPS shall be installed by a qualified technician and wired in accordance with
local and national electrical codes.
The following information is for recommendation only.
Standard Load
VA Rating
F (Hz)
Panel
Breaker Size
Input Output
Voltage Current
Voltage Current
1000VA/700W
1000VA (110)
50/60
15A
80-138Vac
12A max
120V
8.3A
1000VA/700W
1000VA (220)
50/60
15A
160-276Vac
6A max 208/220 4.8A/4.55A
1500VA/1050W 1500VA (110)
50/60
15A
80-138Vac
18A max
120V
12.5A
1500VA/1050W 1500VA (220)
50/60
15A
160-276Vac
9A max 208/220
6.2A
Table 4.2.1
Electrical information for proper installation, breaker and cable ratings