DSC Panel Reporting Codes
Event
Report Code
AC Fail/Restore
301
Panel Low Battery/Low Battery Restore
302
Opening/Closing Report
400
Cancel Report
406
Zone Alarm
See below
Keypad Fire Panic
110
Keypad Aux Panic
100
Keypad Police Panic
120
Duress
121
Periodic Test Transmission
602
Periodic Test With Trouble Transmission
608
Table of all events reported by the IGM when connected to a DSC panel.
Zone Alarm Reporting
• Automatic Contact ID is not supported.
• Manually programmed reporting codes are only supported for alarms on zones 1-64
([320] - [324]) and for alarms on the PGM2/Aux input ([329] option 4) which is reported
as zone number 99.
• If Report Codes have not been manually programmed for zone alarms, zone alarm
reporting codes default to the following.
* Any zone alarm (zones 1-64): Code 1130 (Burglary)
* PGM2/Aux input (zone 99, likely a 2-wire Smoke): Code 1110 (Fire)