Alula RE114 Скачать руководство пользователя страница 3

again, within 4 minutes of the Alarm 

re-sounding, will get the Alarm to 

compensate for chamber contamination. 

This will normally resolve the problem.

If the Alarm re-sounds for a third time, 

the Alarm is excessively contaminated 

and must be replaced. If it is not 

convenient to replace it immediately, 

pressing the test button within 4 

minutes of it going into alarm (for the 

third time) will silence the Alarm for 8 

hours – however it will give two short 

beeps (second apart) every 10 minutes 

to remind the user it has been disabled. 

If the contamination clears the Alarm will 

return to normal operation.

(Note: this does not reduce the users 

fire protection, as a Smoke Alarm in 

continuous alarm due to a fault, is 

useless and must be silenced – by taking 

the Alarm down or as described here. 

This procedure has the added benefits 

that the user is reminded every 10 

minutes by two short beeps that the 

Alarm needs to be replaced and that if 

the problem clears the Alarm will return 

to detecting fire).

1.2.3. Faulty Smoke Chamber

In the unlikely event of the smoke 

sensing chamber becoming defective, 

the Alarm will give 2 short beeps with 2 

yellow LED flashes every 48 seconds. The 

Alarm must then be replaced.

If it is not convenient to replace it 

immediately, pressing the test button will 

silence the beeps and stop the yellow 

LED flashing for 12 hours. This can be 

repeated as required.

2.  Location and Positioning

 

 

 

Introduction

Congratulations on purchasing a Smoke  

Alarm. You can easily install these Alarms 

throughout the property on escape 

routes, on each storey, in corridors and in 

closed rooms to give warning of fire.

Heat Alarms can be installed in kitchens 

and other areas where Smoke Alarms are 

unsuitable.

NATIONAL FIRE PROTECTION 

ASSOCIATION REQUIRED PROTECTION

Smoke Detection. Where required by 

applicable laws, codes, or standards 

for the specified occupancy, approved 

single- and multiple-station Smoke 

Alarms shall be installed as follows: 

(1) In all sleeping rooms and guest rooms

(2) Outside of each separate dwelling 

unit sleeping area within 6.4 m (21 ft) 

of any door to a sleeping room, the 

distance measured along a path of travel

(3) On every level of a dwelling unit, 

including basements

(4) On every level of a residential board 

and care occupancy (small facility), 

including basements and excluding crawl 

spaces and unfinished attics

(5) In the living area(s) of a guest suite

(6) In the living area(s) of a residential 

board and care occupancy (small facility)

Are More Smoke Alarms Desirable? The 

required number of smoke detectors 

might not provide reliable early warning 

protection for those areas separated 

by a door from the areas protected 

by the required smoke detectors. For 

this reason, it is recommended that 

the householder consider the use of 

additional smoke detectors for those 

areas for increased protection. The 

additional areas include the basement, 

bedrooms, dining room, furnace room, 

utility room, and hallways not protected 

by the required smoke detectors. 

The installation of smoke detectors in 

kitchens, attics (finished or unfinished), or 

garages is not normally recommended, 

as these locations occasionally 

experience conditions that can result in 

improper operation.

The equipment should be wired and 

installed in accordance with National 

Fire Protection Association’s Standard 

72, Chapter 11 and National Electric 

Code, NFPA 70, Chapter 3. (National 

Fire Protection Association, Batterymarch 

Park, Quincy, MA 02269).

For Canadian installations wiring 

methods shall be in accordance with 

CSA C22.1, Canadian Electrical Code, 

Part I, Safety Standard for Electrical 

Installations.  Testing and maintenance 

procedures shall be in accordance 

with CAN/ULC-S552, Standard for 

the Maintenance and Testing of 

Smoke-Alarms.

IMPORTANT!

Specific requirements for Smoke Alarm 

installation vary from state to state 

and from region to region. Check with 

your local Fire Department for current 

requirements in your area.

SMOKE ALARMS 

Sufficient smoke must enter your 

Smoke Alarm before it will respond. 

Your Smoke Alarm needs to be within 

6.4 metres (21ft) of the fire to respond 

quickly. Smoke Alarms also need to be 

in positions where they can be heard 

throughout the property, so they can 

wake you and your family in time for 

everyone to escape. A single Smoke 

Alarm will give some protection if it 

is properly installed, but most homes 

will require two or more (preferably 

interconnected) to ensure that a reliable 

early warning is given. For recommended 

protection you should put individual 

3

Содержание RE114

Страница 1: ...isted onto the smoke alarm 4 Remove the mounting plate and refer to Sections 2 and 6 for positioning and installation 5 After mounting plate is installed restore the smoke alarm onto the mounting plat...

Страница 2: ...s every 48 sec 2 Beeps End of Life Off 3 Flashes every 48 sec 3 Beeps Silence Sounding Alarm Press Release Button 1 Flash every 8 sec Off Off for 10 mins Silence End of Life indication up to 30 days P...

Страница 3: ...every level of a dwelling unit including basements 4 On every level of a residential board and care occupancy small facility including basements and excluding crawl spaces and unfinished attics 5 In t...

Страница 4: ...Smoke Alarms must be mounted away from corners Keep at least 305mm 12 from walls and corners see Figure 3 Additionally mount the unit at least 305mm 12 from any light fitting or decorative object whic...

Страница 5: ...ry replacement Locate the Alarm at least 1m 39 from dimmer controlled lights and wiring as some dimmers can cause interference Locate Alarm at least 1 5m 59 and route wiring at least 1m away from fluo...

Страница 6: ...press the test hush button Do not attempt to recharge or burn the battery as it may explode If it is necessary to remove the battery for separate disposal handle carefully to avoid possible eye damag...

Страница 7: ...the alarm sound or to those who may be incapable of safely evacuating the area unassisted Limitations of Heat Alarms There are various situations where a Heat Alarm may not be effective Fires where th...

Страница 8: ...essary it is possible to further secure the Alarm by using a No 2 or No 4 2 to 3mm 1 8 diameter not supplied self tapping screw 6 to 8mm 1 4 long see Figure 7d to firmly lock the Alarm and its mountin...

Страница 9: ...ith a damp cloth and dry thoroughly WARNING Do not paint your Alarm Other than the maintenance and stop sounding shortly after the button is released Repeat this procedure for all other Alarms in the...

Страница 10: ...e chamber base 8 Fit a new chamber top and clip in place by turning clock wise 15 degrees 9 Insert the thermistor PCB into the sockets and ensure the thermistor is perpendicular to the chamber see fig...

Страница 11: ...s check the replace by date marked on the side of the unit Before the Alarm is safely discarded remove from the mounting plate disconnect the batteries Do not put the Alarm into a fire The Alarm shoul...

Страница 12: ...any interference including interference that may cause undesired operation of the device Le pr sent appareil est conforme aux cnr d Industrie Canada applicables aux appareils radio exempts de licence...

Отзывы: