NetWaySP4PX Installation Guide
- 3 -
Overview:
Altronix NetWaySP4PX Media Converter with Integral Power, provides four (4) 1Gb SFP ports and four (4) ports
for up to 120W per port (480W total) to be transmitted over single/multi-mode fiber or composite cable (powered)
cable (fiber + copper combined) to NetWay Spectrum PoE Hardened Switches.
Features:
Agency Listings:
•
CE
European Conformity.
Input:
• 115VAC, 60Hz, 5.5A or 230VAC, 50/60Hz, 3A
(auto-ranging).
Power:
• Four (4) 56VDC non power-limited outputs
up to 120W max. full power per port.
Total power: 480W.
• IEEE 802.3af, IEEE 802.3at and
IEEE 802.3bt compliant.
• Short circuit protection.
SFP Ports:
• Four (4) Gigabit SFP/Fiber ports.
• Use with SFP module 1000Base-X (1Gb),
compliant to Class 1 laser product (not included).
Ethernet/Data:
• Four (4) ports to switch.
• Wire type: 4-pair CAT5e and higher.
• Connectivity: RJ45, auto-crossover.
• Speed: 10/100/1000Mbps.
• Distance: up to 100m.
Environmental:
•
Refer to Environmental Conditions on page 6.
Battery Backup:
• Built-in battery charger
(optional rack mount battery enclosure - RE2)
.
• Automatic switchover to stand-by battery when
AC fails.
Compatible PoE Hardened Switches
and Accessories:
NetWaySP1BTWPN:
3-port (802.3bt) PoE Hardened
Switch with (1) SFP port.
NetWaySP3WPN:
3-port PoE Hardened Switch
with (1) SFP port.
NetWay4EWPN:
4-port PoE Hardened Switch
with (1) SFP port.
NetWaySP4WPN:
4-port PoE Hardened Switch
with (2) SFP ports.
NetWaySP4BTWPN:
4-port (802.3bt) PoE Hardened
Switch with (2) SFP ports.
NetWaySP8WPN:
8-port PoE Hardened Switch
with (2) SFP ports.
RE2:
Rack Mount Battery Enclosure
accommodates up to four (4)
12VDC/7AH
batteries
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical
Code (ANSI/NFPA70), local codes, and the authorities having
jurisdiction. NetWaySP4PX is not intended to be connected to
outside plant leads. These products are for indoor use only and
must be installed within the protected premises.
NetWaySP4PX must be installed in a restricted access area.
If battery bracket is removed, must be installed in a restricted
access area
(Fig. 1b, pg. 3)
.
The outputs are of a non-limited power source.
For non-limited power sources, additional protective circuitry and/or an appropriate fire enclosure for the products
supplied by this device are required.
1. Attach mounting brackets to the unit for rack or wall mount installation
(Fig. 4 or 5, pg. 8)
.
Affix rubber pads to the unit for shelf installation
(Fig. 6, pg. 8)
.
2. Secure the unit in a rack or on a wall, or place unit on a shelf as desired.
Note:
The following factors should be taken into consideration when installing these rack mount units:
a. The unit is to be installed in a space where the maximum ambient temperature does not exceed
104ºF
(40ºC).
b. Take care to ensure that there is sufficient air flow around the unit and that obstructions do not impede it.
c. When mounting units in a rack, take care to avoid uneven loading which can cause a hazardous condition.
3. Plug the grounded AC line cord (included) into the IEC 320 connector of the unit
(Fig. 2f, pg. 4)
. Plug unit
into a reliable earth grounded socket. When using multiple units, the sum of the individual name plate ratings
should not exceed the supply circuit rating.
Do not connect to a receptacle controlled by a switch.
Fig. 1a
Fig. 1b