Maximal3V / Maximal5V / Maximal7V Access Power Controllers (Fused)

Maximal Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local 

codes and authorities having jurisdiction . Product is intended for indoor use only . 

 

Power Supply Board LED Diagnostics 

(pg. 5)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 6)

 

Access Power Controller Terminal Identification 

(pg. 6)

 

Power Supply Board Stand-by Battery Specifications 

(pg. 6)

 

Power Supply Board Output Voltage Settings 

(pg. 7)

 

Access Power Controller Typical Application Diagram 

(pg. 7)

 

FACP Hook-up Diagrams 

(pgs. 13-14)

1 .  Mount unit in the desired location . Mark and predrill holes in the wall to line up with the top three keyholes 

 

in the enclosure . Install three upper fasteners and screws in the wall with the screw heads protruding . Place 

 

the enclosure’s upper keyholes over the three upper screws, level and secure . Mark the position of the lower 

 

three holes . Remove the enclosure . Drill the lower holes and install the three fasteners . Place the enclosure’s 

 

upper keyholes over the three upper screws . Install the three lower screws and make sure to tighten all screws 

 

(Enclosur Dimensions, pg. 16) .

2 .  Connect unswitched AC power (220VAC 50/60Hz) to the terminals marked [L, N] on power supply board . 

 

Green branch wire connects to earth (safety) ground lug . Use 14 AWG or larger for all power connections . 

  

Keep power-limited wiring separate from non power-limited wiring. Minimum 0.25” spacing must 

 

be provided (Figs. 5-7, pgs. 10-12).

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. Refer installation and servicing to 

 

qualified service personnel.

3 .  Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3V power 

 supply, 

(Figs. 1 and 1a, pg. 7). Maximal5V power supply is factory set at 12VDC and Maximal7V power 

 

supply is factory set at 24VDC .

4 .  Measure the output voltage of the unit before connecting any devices to ensure proper operation .

 

Improper or high voltage will damage these devices .

5 . 

Output options (Fig. 2, pg. 7):

 

The unit will provide either sixteen (16) switched power outputs, sixteen (16) dry form “C” outputs, or any

 

combination of both switched power and form “C” outputs .

 

(a)  Fail-Safe Switched Power outputs: 

 

 

For Fail-Safe operation connect the positive (+) input of the access control devices to terminal marked 

 

 

[NC] . Connect the negative (–) input of the access control devices to terminal marked [COM] .

 

(b) Fail-Secure Switched Power outputs:

 

 

For Fail-Secure operation connect the positive (+) input of the access control devices to terminal 

 

 

marked [NO] . Connect the negative (–) input of the access control devices to terminal marked [COM] .

 

(c)  Form “C” outputs:

 

 

When form “C” outputs are desired the corresponding output fuses (1-8) of each ACM8 board must 

 

 

be removed .  

6 . 

Auxiliary Power outputs (unswitched):

 

Connect access control devices that require constant power to terminals marked [C] positive (+) and [COM] 

 

negative (–) .

7 . 

Input trigger options (Fig. 2, pg. 7):

 

(a) Normally Open [NO] input trigger:

 

 

Inputs 1-8 are activated by normally open or open collector sink inputs .

 

 

Connect access control panel outputs, keypads, push buttons, REX PIRs, etc . to terminals marked [IN] 

 

 

and [GND] . 

 

(b) Open Collector Sink inputs:

 

 

Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the 

 

 

negative (–) to terminals marked [GND] .

8 . 

Fire Alarm Interface options (Figs. 8-12, pgs. 13-14)

 

A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity 

 

reversal input from an FACP signaling circuit will affect selected outputs . To enable FACP Disconnect for 

 

an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8 board . To disable FACP 

 

disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8 board .

 

(a)  Normally Open [NO] input:

 

 

For non-latching hook-up refer to Fig. 9, pg. 13 . For latching hook-up refer to Fig. 10, pg. 13 .

 

(b) Normally Closed [NC] input:

 

 

For non-latching hook-up refer to Fig. 11, pg. 14 . For latching hook-up refer to Fig. 12, pg. 14 .

 

(c)  FACP Signaling Circuit input trigger:

 

 

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked 

 

 

[+ INP –] . Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm 

 

 

condition) . Jumper located next to TRG LED must be cut (Fig. 2a, pg. 7, Fig. 8, pg. 13) . 

Содержание Maximal3V

Страница 1: ...M Access Power Controllers Installation Guide Models Include Maximal3V 12VDC 5A or 24VDC 5 4A Sixteen 16 fuse protected outputs Maximal5V 12VDC 9A Sixteen 16 fuse protected outputs Maximal7V 24VDC 9 4...

Страница 2: ...wer Controller Terminal Identification pg 6 Power Supply Board Stand by Battery Specifications pg 6 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram...

Страница 3: ...ated 5A 28VDC or VAC d Any combination of the above Sixteen 16 Access Control System trigger inputs Input trigger options a Sixteen 16 normally open NO dry trigger inputs b Sixteen 16 open collector i...

Страница 4: ...oper or high voltage will damage these devices 5 Output options Fig 2 pg 7 The unit will provide either sixteen 16 switched power outputs sixteen 16 dry form C outputs or any combination of both switc...

Страница 5: ...acing a short between terminals marked T and INP will trigger the Fire Alarm Disconnect Remove the short to reset Normally Closed Input Removing the wire from terminal marked INP will trigger the Fire...

Страница 6: ...Fig 4 pg 9 Access Power Controller Terminal Identification Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control Not applicable TRIGGER INPUT 1 INPUT 8 IN GN...

Страница 7: ...his application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LE...

Страница 8: ...3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC...

Страница 9: ...4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C N...

Страница 10: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Страница 11: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Страница 12: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Страница 13: ...E FACP Hook Up Diagrams Fig 8 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition N O TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 9 Normally Open Non...

Страница 14: ...rs Fused JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 11 Normally Closed Non Latching FACP trigger input N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG Fig 12 Normally Closed Latching FA...

Страница 15: ...Maximal3V Maximal5V Maximal7V Access Power Controllers Fused 15 Notes...

Страница 16: ...50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5...

Отзывы: