Maximal3V / Maximal5V / Maximal7V Access Power Controllers (Fused)
- 15 -
Notes:
Страница 1: ...M Access Power Controllers Installation Guide Models Include Maximal3V 12VDC 5A or 24VDC 5 4A Sixteen 16 fuse protected outputs Maximal5V 12VDC 9A Sixteen 16 fuse protected outputs Maximal7V 24VDC 9 4...
Страница 2: ...wer Controller Terminal Identification pg 6 Power Supply Board Stand by Battery Specifications pg 6 Power Supply Board Output Voltage Settings pg 7 Access Power Controller Typical Application Diagram...
Страница 3: ...ated 5A 28VDC or VAC d Any combination of the above Sixteen 16 Access Control System trigger inputs Input trigger options a Sixteen 16 normally open NO dry trigger inputs b Sixteen 16 open collector i...
Страница 4: ...oper or high voltage will damage these devices 5 Output options Fig 2 pg 7 The unit will provide either sixteen 16 switched power outputs sixteen 16 dry form C outputs or any combination of both switc...
Страница 5: ...acing a short between terminals marked T and INP will trigger the Fire Alarm Disconnect Remove the short to reset Normally Closed Input Removing the wire from terminal marked INP will trigger the Fire...
Страница 6: ...Fig 4 pg 9 Access Power Controller Terminal Identification Terminal Legend Function Description Power 12VDC or 24VDC input from power supply board Control Not applicable TRIGGER INPUT 1 INPUT 8 IN GN...
Страница 7: ...his application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LE...
Страница 8: ...3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC...
Страница 9: ...4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N NC C N...
Страница 10: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...
Страница 11: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...
Страница 12: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...
Страница 13: ...E FACP Hook Up Diagrams Fig 8 Polarity reversal input from FACP signaling circuit output polarity is referenced in alarm condition N O TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 9 Normally Open Non...
Страница 14: ...rs Fused JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 11 Normally Closed Non Latching FACP trigger input N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG Fig 12 Normally Closed Latching FA...
Страница 15: ...Maximal3V Maximal5V Maximal7V Access Power Controllers Fused 15 Notes...
Страница 16: ...50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5...