- 6 -
MaximalFEV Expandable Power Systems
Power Supply Board Terminal Identification:
Terminal
Legend
Function/Description
L, G, N
Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral .
Do not use the [G] terminal
+ DC –
Refer to MaximalFEV Series Configuration Chart, pg. 4.
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP .
Trigger inputs can be normally open, normally closed from an FACP output circuit .
NO, GND
RESET
FACP interface latching or non-latching .
+ AUX –
Auxiliary Power-Limited output rated @ 1A (unswitched) .
AC Fail
NC, C, NO
Indicates loss of AC power, e .g . connect to audible device or alarm panel .
Relay normally energized when AC power is present . Contact rating 1A @ 30VDC .
Bat Fail
NC, C, NO
Indicates low battery condition, e .g . connect to alarm panel . Relay normally energized when
DC power is present . Contact rating 1A @ 30VDC . A removed battery is reported within 5
minutes . Battery reconnection is reported within 1 minute .
– BAT +
Stand-by battery connections . Maximum charge current 1 .54A .
Power Supply Board Stand-by Battery Specifications
eFlow4NBV:
Battery
Access Control Applications Stand-by
7AH
30 Mins ./4A*
12AH
35 Mins ./4A*
40AH
Over 4 Hours/4A*
65AH
Over 4 Hours/4A*
eFlow6NBV:
Battery
Access Control Applications Stand-by
7AH
10 Mins ./6A
12AH
30 Mins ./6A*
40AH
Over 4 Hours/6A*
65AH
Over 4 Hours/6A*
eFlow102NBV:
Battery
Access Control Applications Stand-by
7AH
5 Mins ./10A
12AH
30 Mins ./10A*
40AH
Over 2 Hours/10A*
65AH
Over 4 Hours/10A*
eFlow104NBV:
Battery
Access Control Applications Stand-by
7AH
5 Mins ./10A
12AH
30 Mins ./10A*
40AH
Over 2 Hours/10A*
65AH
Over 4 Hours/10A*