background image

 

MaximalFEV Expandable Power Systems 

- 5 -

MaximalFEV Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, the Canadian 

Electric Code, Part I, Part II, and with all local codes and authorities having jurisdiction . 

Product is intended for indoor use only . 
 

Power Supply Board Terminal Identification 

(pg. 6)

 

Power Supply Stand-by Battery Specifications 

(pg. 6)

 

Power Supply Board LED Diagnostics 

(pg. 7)

 

Power Supply Board Output Voltage Settings 

(pg. 7)

1 .  Mount unit in desired location . Mark and predrill holes in the wall to line up with the top three keyholes in 

 

the enclosure . Install three upper fasteners and screws in the wall with the screw heads protruding . Place 

 

the enclosure’s upper keyholes over the three upper screws; level and secure . Mark the position of the 

 

lower three holes . Remove the enclosure . Drill the lower holes and install the three fasteners . Place the 

 

enclosure’s upper keyholes over the three upper screws . Install the three lower screws and make sure to 

 

tighten all screws (Enclosure Dimensions, pg. 11) .

2 .  Connect unswitched AC power (220VAC 50/60Hz) to terminals marked [L, N] (Fig. 2, pg. 8) . 

 

Use 14 AWG for larger for all power connections . Secure green wire lead to earth ground lug .

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. 

 

Shut branch circuit power before installing or servicing equipment.

  

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3 .  Select desired DC output voltage by setting SW1 to the appropriate position, (Maximal11FEV, Maximal13FEV,

 

Maximal33FEV, Maximal35FEV and Maximal37FEV) (Fig. 1a, pg. 7). Maximal55FEV power supplies are 

 

factory set at 12VDC . Maximal77FEV power supplies are factory set at 24VDC . Maximal75FEV power 

 

supplies are factory set at 12VDC and 24VDC (Power Supply Board Stand-by Battery Specifications, pg. 6).

4 .  Measure output voltage before connecting devices . This helps avoiding potential damage .

5 .  Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +] 

 

(Fig. 2, pg. 8) . For auxiliary device connection, this output will not be affected by Low Power Disconnect 

 

or Fire Alarm Interface . Connect device to the terminals marked [+ AUX –] (Fig. 2, pg. 8). 

 

Refer to page 3 for non power-limited applications.

6 .  For Access Control applications batteries are optional . When batteries are not used, a loss of AC will result 

 in the loss of output voltage . When the use of stand-by batteries is desired, they must be lead acid or gel type .

 

Connect battery to the terminals marked [– BAT + ] (Fig. 2, pg. 8) . Use two (2) 12VDC batteries connected 

 

in series for 24VDC operation (battery leads included) . Use batteries - Casil CL1270 (12V/7AH), CL12120 

 

(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of 

 

an appropriate rating .

7 .  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 2, pg. 8) supervisory

 

relay outputs .

8 .  To delay AC reporting for 2 hrs ., set DIP switch [AC Delay] to OFF position (Fig. 2, pg. 8) .

 

To delay AC reporting for 1 min ., set DIP switch [AC Delay] to ON position (Fig. 2, pg. 8) .

 

Note: Must be set to ON position for Burglar Alarm Applications .

9 .  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position . (Fig. 2, pg. 8) .

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position . (Fig. 2, pg. 8) .

10 .  Trigger terminals are end of a line resistor supervised (10k Ohms) . Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown (Fig. 2, pg. 8) .

11 .  Place a jumper for non-latching FACP . A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] (Fig. 2, pg. 8) .

12 .  For Access Control Applications: mount UL Listed tamper switch (Honeywell Model 112 or equivalent) at 

 

the top of the enclosure . Slide tamper switch bracket onto the edge or the enclosure approx . 2” from the 

 

right side (Fig. 2a, pg. 8) . Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device .

13 .  Please ensure that the cover is secured with the provided key lock .

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level (MaximalFEV Configuration Chart, pg. 4).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage at the battery terminals and at the board terminals marked [– BAT +] to 

 

ensure that there is no break in the battery connection wires .

Note: 

Maximum charge current 1 .54A .

Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary .

Содержание Maximal11FE

Страница 1: ...ly 2 12VDC or 24VDC 6A Maximal33FEV Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC or 24VDC 6A Maximal35FEV Power Supply 1 12VDC or 24VDC 6A Power Supply 2 12VDC 10A Maximal37FEV Power Supply 1...

Страница 2: ...FEV Installation Instructions pg 5 Maintenance pg 5 Power Supply Board Terminal Identification pg 6 Power Supply Board Stand by Battery Specifications pg 6 Power Supply Board LED Diagnostics pg 7 Powe...

Страница 3: ...l type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption Fire Alarm Disconnect Sup...

Страница 4: ...13 2 10 03 13 2 10 1 13 2 10 05 13 2 20 19 26 4 20 19 26 4 20 28 26 4 20 2 26 4 10 0 13 2 10 03 13 2 20 28 26 4 20 2 26 4 20 19 26 4 20 19 26 4 Maximal33FEV eFlow6NBV eFlow6NBV 6A 6A 2 2 4 2 5A 250V 1...

Страница 5: ...evice to the terminals marked AUX Fig 2 pg 8 Refer to page 3 for non power limited applications 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will r...

Страница 6: ...1A 30VDC Bat Fail NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 30VDC A removed battery is reported within 5 mi...

Страница 7: ...ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Power Supply Board Output...

Страница 8: ...positive terminal of the battery Connect black battery lead to terminal marked BAT and to the negative terminal of the battery Optional Rechargeable Stand by Battery Optional Rechargeable Stand by Ba...

Страница 9: ...ns must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods F...

Страница 10: ...10 MaximalFEV Expandable Power Systems Notes...

Страница 11: ...0 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1...

Страница 12: ...remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change outp...

Отзывы: