Altronix Maximal Скачать руководство пользователя страница 6

 

- 6 - 

Maximal11FV / Maximal33FV / Maximal55FV / Maximal77FV / Maximal75FV Access Power Controllers (Fused)

 

(a)  Normally Open [NO] input:

 

 

For non-latching hook-up refer to Fig. 6, pg. 12. For latching hook-up refer to Fig. 7, pg. 12.

 

(b) Normally Closed [NC] input:

 

 

For non-latching hook-up refer to Fig. 8, pg. 12. For latching hook-up refer to Fig. 9, pg. 12.

 

(c)  FACP Signaling Circuit input trigger:

 

 

Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals 

 

 

marked [+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced 

 

 

in an alarm condition). Jumper located next to TRG LED must be cut (Fig. 6, pg. 12)

9. 

FACP Dry form “C” output (Not evaluated by UL) (Fig. 2a, pg. 9):

 

FACP form “C” contacts can be use to trigger reporting or signaling devices. These contact switch

 

upon a fire alarm input trigger to the ACM8 boards.

10. 

Stand-by Battery Connections (Fig. 3, pg. 10):

 

For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 in 

the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

 

Connect battery to terminals marked [– BAT +] (Fig. 3, pg. 10). Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 

 

(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 and BAZR8 

 

batteries of an appropriate rating. 

11. 

Battery and AC Supervision outputs (Fig. 3, pg. 10):

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT Fail] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. 

 

Use 22 AWG to 18 AWG for AC Fail and Low/No Battery reporting.

12.  To delay AC reporting for 2 hrs., set dip switch [AC Delay] to OFF position (Fig. 3, pg. 10).
 

To delay AC reporting for 1 min., set dip switch [AC Delay] to ON position (Fig. 3, pg. 10).

13. 

Fire Alarm Disconnect (Fig. 3, pg. 10):

 

To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position.

 

To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position.

14. 

Installation of tamper switch (Not Included) (Fig. 3b, pg. 10):

 

Mount UL Listed tamper switch (Honeywell Model 112 or equivalent) at the top of the enclosure. Slide the 

 

tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 3b, pg. 10)

 

Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting 

 

device. To activate alarm signal open the door of the enclosure.

15. 

Multiple power supply inputs (Fig. 2, pg. 9):

 

When using an additional external power supply, jumpers J1 and J2 located on corresponding ACM8 board 

 

must be cut (Fig. 2c, 2d, pg. 9 and Fig. 5, pg. 12). Connect external access control power supply to the 

 

terminals marked [– C] (These terminals are paralleled to the [– Power +] terminals). When using 

 

DC power supplies, polarity must be observed. When using AC power supplies, polarity needs not to be 

 observed 

(Fig. 2d, pg. 9). All field wiring connections must be made employing suitable gauge CM or FPL 

 

jacketed wire (or equivalent substitute) (Fig. 4a, pg. 11).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup. Please 
follow the appropriate procedure below:
 

Normally Open Input: Placing a short between terminals marked [T] and [+ INP] will trigger the Fire 

  Alarm Disconnect. Remove the short to reset.
 

Normally Closed Input: Removing the wire from terminal marked [INP 

] will trigger the Fire Alarm 

  Disconnect. Replace the wire to terminal marked [INP 

] to reset.

 

FACP Signal Circuit Input: It is necessary to trigger the Fire Alarm System.

  In all of the above scenarios the green TRG LED of the ACM8s will illuminate. All outputs selected for 
  Fire Alarm Disconnect will activate releasing locking devices.
 

Note: All outputs [OUT 1] - [OUT 8] must be in a normal (de-energized) condition prior to testing. When the 

  unit is configured for Normally Open (Fig. 8, pg. 12) or Normally Closed (Fig. 10, pg. 12) latching operation, 
  it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch.
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper 
voltage level (refer to MaximalF series Configuration Chart, pg. 3).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage at 
the battery terminals and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery 
connection wires.
Note:  Maximum charge current is 1.54A. Expected battery life is 5 years; however, it is recommended to 
   

change batteries within 4 years or less if necessary.

Содержание Maximal

Страница 1: ...utputs Maximal55FV Power Supply 1 12VDC 9 3A Power Supply 2 12VDC 9 3A Sixteen 16 fuse protected outputs Maximal77FV Power Supply 1 24VDC 9 6A Power Supply 2 24VDC 9 6A Sixteen 16 fuse protected outpu...

Страница 2: ...enance pg 6 Power Supply Board LED Diagnostics pg 7 Access Power Controller LED Diagnostics pg 7 Power Supply Board Terminal Identification pg 7 Access Power Controller Terminal Identification pg 8 Po...

Страница 3: ...Power Supply 1 Power Supply 2 A Fuse Protected Outputs 220VAC 50 60 Hz Input current Current per ACM8 output A Power Supply Board Input Fuse Rating Power Supply Board Battery Fuse Rating ACM8 Board In...

Страница 4: ...ed 1A 28VDC eFlow Power Supply Charger provides common power for ACM8 board factory wiring and all connected access control devices field wiring ACM8 board main fuses are rated 10A Output fuses are ra...

Страница 5: ...consists of one 1 power supply board that is factory set at 12VDC and one 1 power supply board that is factory set at 24VDC 4 Measure the output voltage of the unit before connecting any devices to e...

Страница 6: ...edge of the enclosure approximately 2 from the right side Fig 3b pg 10 Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device To activate alarm s...

Страница 7: ...erminals L to hot N to neutral Do not use terminal marked G DC Factory connected to ACM8 board Trigger EOL Supervised Fire Alarm Interface trigger input from a short or FACP Trigger inputs can be norm...

Страница 8: ...2VDC 5 3A P S 2 10 0 13 2VDC 5 3A or P S 1 20 28 26 4VDC 5 6A P S 2 20 28 26 4VDC 5 6A or P S 1 10 0 13 2VDC 5 3A and P S 2 20 28 26 4VDC 5 6A Maximal55FV P S 1 10 03 13 2VDC 9 3A and P S 2 10 03 13 2...

Страница 9: ...UT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO...

Страница 10: ...largest batteries that can fit in this enclosure A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries Optional Rechargeable Stand by Battery Optional Rechargeable St...

Страница 11: ...onduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to...

Страница 12: ...AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG FACP NO C NC FACP INTERFACE JUMP...

Страница 13: ...Maximal11FV Maximal33FV Maximal55FV Maximal77FV Maximal75FV Access Power Controllers Fused 13 Notes...

Страница 14: ...14 Maximal11FV Maximal33FV Maximal55FV Maximal77FV Maximal75FV Access Power Controllers Fused Notes...

Страница 15: ...8 4 213 4mm 8 9 226 1mm 8 4 213 4mm 19 482 6mm 4 101 6mm 1 25 4mm 7 5 190 5mm 5 127mm 26 660 4mm 1 5 38 1mm 1 0 25 4mm 6 25 158 8mm 8 5 215 9mm 7 5 190 5mm 10 254mm 26 660 4mm 1 25 31 8mm 7 177 8mm 7...

Страница 16: ...the U S and Canada Local or remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service inpu...

Отзывы: