background image

 

- 6 - 

FireSwitch108

6 .  Determine which NAC input will trigger the desired NAC output(s) .
7 .  Select output options (for Programming refer to pgs. 9-11).
 

Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with 

 

synchronization capability . For Class B outputs connect EOL (AL-EOL10) to the last device in each NAC 

 

Loop . For applications in Canada use EOL10K-C end of line resistors (to be ordered separately) . Form the 

 

leads to fit the terminals . Bend radius can not exceed 0 .125” . Do not bend closer than 0 .25” to the body of 

 

the resistor .

8 .  Connect desired 24VDC devices to regulated Aux . power output terminals marked [+ AUX – ] (Fig. 2, pg. 5) .
 

Output is Power-Limited . 0 .25” spacing from Non Power-Limited wiring must be provided . 

 

Use separate knockout .

9 .  Connect Digital Communicator or Local Annunciator to Common Trouble Output terminals marked 
 

[NC, NO, C] . Connection to triggering devices must be made within 20 ft . of distance and using conduit 

 

for wiring (Fig. 2, pg. 5).

10 .  Connect appropriate signaling notification devices to terminals marked [AC FAIL & BAT FAIL]  
 

supervisory relay outputs (Fig. 2, pg. 5) .

11 . Program FireSwitch utilizing on-board programming switch or via ethernet port (for Programming refer 
 

to pgs. 9-11). When using ethernet port, cable has to terminate within the same building .

12 . 

WARNING: emergency control or non fire equipment cannot be connected on same circuitry as 

 

fire alarm equipment .

Amount of Notification Appliances that can be Synchronized:

Altronix Model

Max. Per Circuit

Max. Per FireSwitch108

FireSwitch108

32

128

Terminal Identification Table:

Logic Board

Terminal Legend Function/Description
+ 24V IN –

24VDC input from power supply .

+ AUX –

This separate 1A max . auxiliary regulated output circuit is typically used to power 
approved devices. See attached list of devices (Appendix B, pg. 23) . 

OUT1 - OUT8
(Supervised)

Notification appliances are connected to these regulated outputs . Each power limited output 
will supply up to 2 .5A . Outputs are controlled by designated Input 1 [IN1] or Input 2 [IN2] 
(Output Configuration Chart, pg. 9).
 Maximum line impedance 1 Ohm . NAC outputs that 
are programmed as AUX are Special Application .

IN1 +, IN1 –
IN2 +, IN2 –
(Supervised)

These terminals connect to the 24VDC FACP notification appliance circuit outputs . Class A 
or Class B Input trigger voltage is 8-33VDC @ 6 .5mA min (12VDC or 24VDC @ 6 .5mA) . 
Terminal polarity is shown in alarm condition . During an alarm condition these inputs will 
cause the selected outputs chosen to drive notification appliances . The designated outputs are 
programmable [OUT1 through OUT8] (Output Configuration Chart, pg. 9). A trouble condi-
tion on an output loop will cause the corresponding input to trip the FACP by opening the 
FACP loop . An alarm condition will always override trouble to drive notification appliances .

RET1 +, RET1 –
RET2 +, RET2 –
(Supervised)

For Class A connections these terminal pairs return to FACP . For Class B connections use 
FACP EOL resistor to terminate at these terminals . Optionally, additional signaling circuit 
power supplies may be connected to these terminals . If this option is chosen, the EOL resis-
tor must be terminated at the last device . Up to twelve (12) units can be interconnected .

EARTH

Connects to the grounding lug of the enclosure (factory installed) .

C, NO, NC
(Common
trouble output)

These are dry contact trouble outputs that report any general loop/system trouble conditions . 
In addition, Factory set to report AC and Battery trouble . Feature can be optionally turned off . 
See Programming section, pg. 9-11. Typically used to trigger a digital communicator or other 
reporting devices (form “C” contact 1A / 28VDC, 0 .35 Power Factor) . Connection to trigger-
ing devices must be made within 20 ft . of distance and using conduit for wiring (Fig. 2, pg. 5) .

+ SYNC –

Designed to be connected to [+ INP1 –] or [+ INP2 –] of Altronix FireSwitch models only . 
Maximum of four (4) units can be interconnected, the distance between the units should 
not exceed 20 ft ., wiring to be in conduit, 20 AWG wire minimum . FireSwitch108 NAC 
power extenders must be located in the same room .

GF1
GF2

Dry normally open contact . It will close if ground fault is detected . Use to report ground 
fault condition to a host FACP . Can be wired between [+] or [–] coming from FACP and 
earth ground .

Содержание FireSwitch 108

Страница 1: ...Rev 102919 More than just power TM Altronix Corp 140 58th St Brooklyn NY TM FireSwitch108 10A NAC Power Extender Installation Guide...

Страница 2: ...d Programming via Ethernet Port pg 12 Battery Calculation Worksheet pg 13 FireSwitch Applications General Information pg 14 Class A and Class B Connections pg 14 Combination CO and Fire Alarm Connecti...

Страница 3: ...rated at 1A regulated battery backed up 0 45A for Canadian applications Any NAC can be configured as an Aux output with or without battery back up special application only When set as Aux output the o...

Страница 4: ...When loads are connected to the AUX output during alarm condition and total current from AUX and remaining outputs may not exceed total alarm current for the particular FireSwitch model AUX outputs a...

Страница 5: ...tputs can be programmed as Class A NACs Class B NACs Aux power output s with battery backup or Aux power output s without battery backup Note Not all devices can use the sync feature Be sure to check...

Страница 6: ...ut 2 IN2 Output Configuration Chart pg 9 Maximum line impedance 1 Ohm NAC outputs that are programmed as AUX are Special Application IN1 IN1 IN2 IN2 Supervised These terminals connect to the 24VDC FAC...

Страница 7: ...TICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product is field configurable In order for the product to comply with the requirements in the Standard for Cont...

Страница 8: ...ated NAC Outputs Power Limited Aux Output Regulated 24VDC 1A Power Limited Non Supervised Class E 0 45A for Canadian applications AC Input Non Power Limited 120VAC 60Hz 4 8A AC and Battery Supervision...

Страница 9: ...7 OUT8 SYNC GF1 GF2 NC NO C EARTH NEGATIVE POSITIVE INP2 INP1 INP2 INP1 ETHERNET ON RIGHT LEFT UP DOWN PRESS DOWN FOR ENTER 24V AUX Programming To begin programming depress and hold down the joystick...

Страница 10: ...and Fire Alarm Connections on Pg 15 3e Reserved Reserved 1f Gentex Gentex is a registered trademark of Gentex Corporation Input 1 both horns and strobes This mode is designed to work with the Gentex...

Страница 11: ...ght to select AC BAT ALERT or to enable disable AC and BAT trouble and ALERT sounder d Use Up Down to select the appropriate End of Line Resistor value 2 2K 2 8K 3 9K 4 7K 5 1K 10K 22K 43K e Depress t...

Страница 12: ...Obtain an IP address automatically and then click OK e To specify IPv6 IP address settings click Obtain an IPv6 address automatically and then click OK For Windows 7 a Open Network Connections by clic...

Страница 13: ...mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current A B C mA mA E Total current ratings converted to a...

Страница 14: ...OUT 4 3 OUT 5 OUT 6 4 OUT 7 OUT 8 Please make sure corresponding outputs are programmed appropriately One 1 Class A two 2 Class B Connections NEGATIVE POSITIVE INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4...

Страница 15: ...ilenced Programming and LCD Legend LCD Legend Description 1e Generates strobe sync signal 2e Generates T3 horn temporal pattern or T4 temporal pattern see above Horn settings for CO alarm Gentex Potte...

Страница 16: ...nix Model Max Per Circuit Max Per FireSwitch108 FireSwitch108 32 128 6 Synchronizing NAC Power Extender Using Built In Sync Protocol FireSwitch units include built in protocols to support Amseco Potte...

Страница 17: ...liance FireSwitch Logic Board Programmed for Following INP2 FACP Fire Alarm Control Panel No Notification Appliances Allowed 10K EOL INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4 NEGATIVE POSITIVE INP2 INP1...

Страница 18: ...le Supervision FireSwitch Logic Board Programmed for Following INP2 2c For this application set Dip Switches for INP2 to ON position on all units except the one triggered from FACP FireSwitch Logic Bo...

Страница 19: ...position When connecting INP1 to the sync output of FireSwitch unit for synchronization purposes set SW1 to the ON position and SW3 to the OFF position For INP2 to the sync output of FireSwitch unit f...

Страница 20: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...

Страница 21: ...P UL SPSCRV UL SPSWH P UL SWK P UL P4R UL PC4R SP UL SPSCRVH UL SPSWK UL P2GRL P4R P UL PC4RH UL P2RL P2WL P2GWL P2RL P P2WL P P2RL SP P2WL SP P4RL P4WL SRL SWL SGRL SGWL SRL P SWL P SRL SP SWL CLR AL...

Страница 22: ...T90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR...

Страница 23: ...lists relays compatible with FireSwitch AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2...

Страница 24: ...MEMBER 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0...

Отзывы: