background image

 

- 4 - 

FireSwitch108

Power Supply Specifications:

AC Input

120VAC, 60Hz, 4 .8A .

Output

Eight (8) regulated supervised NAC output circuits, 24VDC, 2 .5A maximum current .
10A max . total alarm current (configurable as Special Application Aux . ouputs) .
7A max . stand-by without battery backup . 1A max with battery backup including 
Aux . output . One (1) regulated aux . output rated at 24VDC @ 1A with battery backup 
(see stand-by specifications below) . 0.45A for Canadian applications. Total output 
current in alarm condition must not exceed 10A .

Battery

Use two (2) 12VDC/12AH or two (2) 12VDC/7AH or two (2) 12VDC/40AH
batteries connected in series .

Stand-by/Alarm
Current Consumption

180mA/200mA

EOL Resistor
(end of line)

Default 10K (10,000 Ohm), Altronix Model # AL-EOL10 .
(EOL10K-C for Canadian applications)

Ground fault 
maximum
test impedance

1,000 Ohm .

Maximum Loop
impedance

1 Ohm .

Stand-by Specifications:

Stand-by 
Batteries  

Stand-by/Alarm Aux. Current/Battery Back-up

24VDC/7AH

24 Hrs ./5 mins .

No auxiliary current (battery backed up)

24VDC/12AH

24 Hrs ./5 mins .

50mA auxiliary max . current (battery backed up)

24VDC/40AH

24 Hrs ./5 mins .

1A auxiliary max . current (battery backed up)

24VDC/40AH

24 Hrs ./30 mins . 0 .45A auxiliary max . current (battery backed up) for Canadian Applications

Note: Unit is equipped with one (1) 1A max. auxiliary output (0.45A for Canadian applications): “AUX” 

NAC outputs programmed for “AUX” with battery backup will remain battery backed up during power 

outage. For loads connected to “AUX” please, refer to battery “Stand-by Specifications” above for ratings. 

When loads are connected to the “AUX” output during alarm condition, and total current from AUX and 

remaining outputs may not exceed total alarm current for the particular FireSwitch model. AUX outputs 

are not supervised. 

To provide supervision use a UL Listed end of line relay or similar method.

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code NFPA 70/NFPA 72/ANSI/Canadian 
Electrical Code/CAN/ULC-S524/ULC-S527/ULC-S537, Signaling Code and with all local codes and authorities 
having jurisdiction . 

PRODUCT IS INTENDED FOR INDOOR DRY USE ONLY.
Carefully review:
 

Power Supply Specifications 

(pg. 3)

 

Stand-by Specifications 

(pg. 4)

 

Terminal Identification 

(pgs. 6-7)

 

LED Diagnostics 

(pg. 7)

 

Programming 

(pgs. 9-11)

 

Testing and Maintenance 

(pg. 11)

1 .  Mount the unit in desired location . Mark and predrill holes in the 
 

wall to line up with the top two keyholes in the enclosure . Install two 

 

upper fasteners and screws in the wall with the screw heads protruding . 

 

Place the enclosure’s upper keyholes over the two upper screws; level and secure . 

 

Mark the position of the lower two holes . Remove the enclosure . Drill the lower holes 

 

and install the two fasteners . Place the enclosure’s upper keyholes over the two upper screws . Install the 

 

two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 24) . 

 

Secure enclosure to earth ground (Fig. 1, pg. 4) .  

 

Small terminal block wire gauges range from 16 AWG to 22 AWG, all others range from 12 to 22 AWG .

2 .  Connect the line [L] and neutral [N] terminals to a separate unswitched 20A protected branch circuit 
 

(120VAC, 60Hz) dedicated to the Fire Alarm System . Connect ground to the ground lug (Fig. 1, pg. 4). 

 

Use 12 AWG wire .

line
neutral

ground

  L 

N

Fig. 1

Содержание FireSwitch 108

Страница 1: ...Rev 102919 More than just power TM Altronix Corp 140 58th St Brooklyn NY TM FireSwitch108 10A NAC Power Extender Installation Guide...

Страница 2: ...d Programming via Ethernet Port pg 12 Battery Calculation Worksheet pg 13 FireSwitch Applications General Information pg 14 Class A and Class B Connections pg 14 Combination CO and Fire Alarm Connecti...

Страница 3: ...rated at 1A regulated battery backed up 0 45A for Canadian applications Any NAC can be configured as an Aux output with or without battery back up special application only When set as Aux output the o...

Страница 4: ...When loads are connected to the AUX output during alarm condition and total current from AUX and remaining outputs may not exceed total alarm current for the particular FireSwitch model AUX outputs a...

Страница 5: ...tputs can be programmed as Class A NACs Class B NACs Aux power output s with battery backup or Aux power output s without battery backup Note Not all devices can use the sync feature Be sure to check...

Страница 6: ...ut 2 IN2 Output Configuration Chart pg 9 Maximum line impedance 1 Ohm NAC outputs that are programmed as AUX are Special Application IN1 IN1 IN2 IN2 Supervised These terminals connect to the 24VDC FAC...

Страница 7: ...TICE TO USERS INSTALLERS AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES This product is field configurable In order for the product to comply with the requirements in the Standard for Cont...

Страница 8: ...ated NAC Outputs Power Limited Aux Output Regulated 24VDC 1A Power Limited Non Supervised Class E 0 45A for Canadian applications AC Input Non Power Limited 120VAC 60Hz 4 8A AC and Battery Supervision...

Страница 9: ...7 OUT8 SYNC GF1 GF2 NC NO C EARTH NEGATIVE POSITIVE INP2 INP1 INP2 INP1 ETHERNET ON RIGHT LEFT UP DOWN PRESS DOWN FOR ENTER 24V AUX Programming To begin programming depress and hold down the joystick...

Страница 10: ...and Fire Alarm Connections on Pg 15 3e Reserved Reserved 1f Gentex Gentex is a registered trademark of Gentex Corporation Input 1 both horns and strobes This mode is designed to work with the Gentex...

Страница 11: ...ght to select AC BAT ALERT or to enable disable AC and BAT trouble and ALERT sounder d Use Up Down to select the appropriate End of Line Resistor value 2 2K 2 8K 3 9K 4 7K 5 1K 10K 22K 43K e Depress t...

Страница 12: ...Obtain an IP address automatically and then click OK e To specify IPv6 IP address settings click Obtain an IPv6 address automatically and then click OK For Windows 7 a Open Network Connections by clic...

Страница 13: ...mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 10A 10 000mA 0mA mA D Total alarm current A B C mA mA E Total current ratings converted to a...

Страница 14: ...OUT 4 3 OUT 5 OUT 6 4 OUT 7 OUT 8 Please make sure corresponding outputs are programmed appropriately One 1 Class A two 2 Class B Connections NEGATIVE POSITIVE INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4...

Страница 15: ...ilenced Programming and LCD Legend LCD Legend Description 1e Generates strobe sync signal 2e Generates T3 horn temporal pattern or T4 temporal pattern see above Horn settings for CO alarm Gentex Potte...

Страница 16: ...nix Model Max Per Circuit Max Per FireSwitch108 FireSwitch108 32 128 6 Synchronizing NAC Power Extender Using Built In Sync Protocol FireSwitch units include built in protocols to support Amseco Potte...

Страница 17: ...liance FireSwitch Logic Board Programmed for Following INP2 FACP Fire Alarm Control Panel No Notification Appliances Allowed 10K EOL INP1 RET1 INP2 RET2 OUT1 OUT2 OUT3 OUT4 NEGATIVE POSITIVE INP2 INP1...

Страница 18: ...le Supervision FireSwitch Logic Board Programmed for Following INP2 2c For this application set Dip Switches for INP2 to ON position on all units except the one triggered from FACP FireSwitch Logic Bo...

Страница 19: ...position When connecting INP1 to the sync output of FireSwitch unit for synchronization purposes set SW1 to the ON position and SW3 to the OFF position For INP2 to the sync output of FireSwitch unit f...

Страница 20: ...WGESG24 75PWLPR W UL SSPKA24 15 75PWW UL WGES24 75WRLP WWLP UL WGESR24 75PWLPR W UL SSPKA24 15 75AWR UL WGEC24 75WR WW UL WGECA24 75PWLPR W UL SSPKA24 15 75AWW UL WGEC24 75PWR PWW UL WGECB24 75PWLPR...

Страница 21: ...P UL SPSCRV UL SPSWH P UL SWK P UL P4R UL PC4R SP UL SPSCRVH UL SPSWK UL P2GRL P4R P UL PC4RH UL P2RL P2WL P2GWL P2RL P P2WL P P2RL SP P2WL SP P4RL P4WL SRL SWL SGRL SGWL SRL P SWL P SRL SP SWL CLR AL...

Страница 22: ...T90 24MCCH FR UL cUL LHSW AL UL cUL RSSA 24MCC NW UL CH90 24MCCH FW UL cUL ET 1010 R UL LHSW N UL cUL RSSA 24MCCH NW UL E50 241575W FW UL cUL ET 1010 W UL LSPSTR UL cUL RSSB 24MCC NW UL E50 24MCWH FR...

Страница 23: ...lists relays compatible with FireSwitch AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2...

Страница 24: ...MEMBER 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0...

Отзывы: