- 19 -
8. Using a Single FACP Output:
When only one FACP output is available, you may connect both Input1 and Input2 to it .
Wire [RET1+] and [RET1–] to [INP2+] and [INP2–] .
Both visual and audible notification appliances will be activated simultaneously (Fig. 13, pg. 19) .
Fig. 13
Dip Switches 1-4 Settings:
Dry contact INP1 configuration set SW1 and SW3 to the ON position .
Dry contact INP2 configuration set SW2 and SW4 to the ON position .
When connecting INP1 to the sync output of FireSwitch unit for synchronization purposes set SW1 to the ON
position and SW3 to the OFF position . For INP2 to the sync output of FireSwitch unit for synchronization pur-
poses set SW2 to the ON position and SW4 to the OFF position .
SW1
SW2
SW3
SW4
INP1 - Dry NC
ON
–
ON
–
INP2 - Dry NC
–
ON
–
ON
INP1 - Sync
ON
–
OFF
–
INP2 - Sync
–
ON
–
OFF
Control Circuit
No Notification Appliances Allowed
FireSwitch Logic Board
INP1
RET1
INP2
RET2
NEGA
TIV
E
POSITIV
E
To INP1
FACP
(Fire Alarm
Control Panel)
10K EOL or Next Device.
For Class A configuration
connect RET2 to FACP
+ SYNC
---
NC
GND
NC
NO
C
EA
RT