eFlow3NV Series Installation Guide
- 9 -
NC C NO NC C NO
AC FAIL
BAT FAIL
TRIGGER
AC DC
AC1
EOL
NO
GND
SUPERVISED
RESET
+AUX-
- BAT
+-
DC
+
L G N
OFF - 24V
ON - 12V
ON
Battery & AC
Supervision Circuit
Battery
Connection
PD4/
PD4CB
1P 1N 2P 2N 3P 3N 4P 4N
P N
DC Output to Devices
(refer to Fig. 3a or 3b for board configuration, pg. 6)
Switch Detail
ON
1
Switch On - 12V
Switch Off - 24V
220VAC power mains
Ground Lug
CAUTION: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery.
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
12AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL listed external battery enclosure must be used if using 40AH or 65AH batteries.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Fig. 6 -
eFlow3NXV Configuration
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure