eFlow3NV Series Installation Guide

NEC Power-Limited Wiring Requirements for eFlow3NXV Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 

One such example of this is shown below. Your specific application may require different conduit knockouts to 

be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 

wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.

For Canadian installations use shielded wiring for all connections.

Note:

 Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 7a).

Fig. 7

Fig. 7a

Input

220VAC

50/60Hz

(non power-

limited)

Supervisory, Fire Alarm Interface

and Aux. output Connections

(power-limited)

DC Output

(power-

limited)

Power 

Distribution

(power-limited)

Optional UL 

Listed Battery 

Enclosure

(non power-

limited)

Battery

Connections

(non power-limited)

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Содержание eFlow3N4DV

Страница 1: ...VDC or 24VDC Four 4 Fused Outputs eFlow3N4DV eFlow3NX4DV 2A 12VDC or 24VDC Four 4 PTC Outputs Installation Guide Rev 3NVRP122713 More than just power TM Installing Company ________________ Service Rep...

Страница 2: ...DC Output Range V 24VDC Output Range V eFlow3NV 10 13 13 2 20 28 26 39 10 15 13 2 20 2 26 39 2A 2 1A 5A 250V 3A 32V 960 N A 1 P eFlow3NXV P eFlow3N4V 10 13 13 2 20 28 26 39 10 15 13 2 20 2 26 39 2A 2...

Страница 3: ...his helps avoiding potential damage 5 Connect devices to be powered a For eFlow3NV eFlow3NXV connect devices to terminals marked DC Fig 1h pg 5 b For other Power Distribution Models connect devices to...

Страница 4: ...pg 5 12 For Access Control Applications mount tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the...

Страница 5: ...energized when DC power is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by batte...

Страница 6: ...AT FAIL AC FAIL POWER SOURCE RED INDICATING LAMP Power Distribution Module s Fig 3a PD4 Power Distribution Board Fig 3b PD4CB Power Distribution Board LED F1 F2 F3 F4 1P 1N 2P 2N 3P 3N 4P 4N DC Output...

Страница 7: ...nd by Battery Optional Rechargeable Stand by Battery CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Us...

Страница 8: ...nal All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power suppl...

Страница 9: ...r mains Ground Lug CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 12AH Rechar...

Страница 10: ...onal All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supp...

Страница 11: ...35 6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10...

Страница 12: ...4 615 117 2mm 4 615 117 2mm 1 5 38 1mm 1 5 38 1mm 4 615 117 2mm 4 615 117 2mm 1 75 44 5mm 1 75 44 5mm 1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1...

Страница 13: ...TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W...

Страница 14: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 15: ...is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Mad...

Страница 16: ...65AH 2A 2A 1 5A 2A Over 4 Hours 2A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Trans...

Отзывы: