- 3 -

3.  All units are factory set for 24VAC operation. 
 

For 28VAC operation adjust unit prior to applying power as follows: 

 

Remove wires marked [24V] and [28V] from terminals marked [P] and [S]. 

 

Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S].

 

Note: ALTV244ULCB3 set for 28VAC operation is not Class 2 Rated, not power-limited.

4.  Plug in 3-wire line cord (Figs. 1-5, pgs. 4-8)
 

Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided. Use separate knockouts.

5.  Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3, 
 

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

6.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

Terminals marked [1P - 4P] are of the same polarity.

 

CAUTION: Determine the maximum operating voltage of the equipment being powered before 

 

adjusting the output voltage.

7.  Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL3, 
 

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6)

8.

  Connect devices to the terminals marked [1P] - [1N] through [4P] - [4N] on PD4 or PD4CB board

 

(Figs. 1-5, pgs. 4-8), carefully observing polarity.

9.  Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL3, 
 

ALTV244ULX3 or ALTV244ULCB3 (Figs. 1-3, pgs. 4-6).

10.  Green LED will illuminate when power is present.
11.  Upon completion of the wiring, secure enclosure door with screws (supplied). 
 

Installation of a cam lock is optional.

 

Caution: Equipment to be installed/serviced by authorized/trained personnel only. 

 

Shut branch circuit power before installing/servicing equipment.

WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This 
installation should be made by qualified service personnel and should conform to the National Electrical 
Code and all local codes. Use 75˚C or higher rated UL insulated wiring for connecting the unit to the mains. 
Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL3 Reference Chart, pg. 2).

Terminal Identification:

PD4/PD4CB - Distribution Module

1P - 4P

AC output.

1N - 4N

AC output.

The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user 
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may 
be of sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of 
important operating and maintenance (servicing) instructions in the literature accompanying the 
appliance.

CAUTION: To reduce the risk of electric shock do not open 
enclosure. There are no user serviceable parts inside. Refer servicing 
to qualified service personnel.

Содержание ALTV244175UL3

Страница 1: ...AC 3 5A 85VA or 28VAC 3A 85VA Four 4 Fuse Protected Outputs Factory installed 3 wire line cord ALTV244175UL3 24VAC 7A 175VA or 28VAC 10A 300VA Four 4 Fuse Protected Outputs Factory installed 3 wire li...

Страница 2: ...e screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install...

Страница 3: ...ition for models ALTV244UL3 ALTV244ULX3 or ALTV244ULCB3 Figs 1 3 pgs 4 6 10 Green LED will illuminate when power is present 11 Upon completion of the wiring secure enclosure door with screws supplied...

Страница 4: ...er limited 1P 1N 2P 2N 3P 3N 4P 4N LED 3 5A 250V 3 5A 250V 3 5A 250V N P S MAIN FUSE Class 1 Outputs ON OFF 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 4P N for outputs...

Страница 5: ...power limited 1P 1N 2P 2N 3P 3N 4P 4N LED N P S MAIN FUSE ON OFF 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 4P N for outputs 2 through 4 24VAC configuration Class 2 Not...

Страница 6: ...ad Input 115VAC 50 60Hz non power limited Green Lead ground Class 1 Outputs 1P 1N 2P 2N 3P 3N 4P 4N LED 3 5A 250V 3 5A 250V 3 5A 250V N P S MAIN FUSE ON OFF Fig 3 ALTV244ULX3 N P S N P S 24VAC Output...

Страница 7: ...3 5A 250V N P S MAIN FUSE Class 1 Outputs 24VAC or 28VAC Output 1 Follow same procedure using terminals 2P N through 4P N for outputs 2 through 4 Black Lead White Lead Input 115VAC 50 60Hz non power l...

Страница 8: ...through 4P N for outputs 2 through 4 1P 1N 2P 2N 3P 3N 4P 4N LED N P S MAIN FUSE ON OFF 24VAC configuration Class 2 Not Wet Class 3 Wet 28VAC configuration Class 1 Black Lead White Lead Input 115VAC 5...

Страница 9: ...ALTV244UL3 Series 9 Notes...

Страница 10: ...5 133 35mm 6 05 153 67mm 6 05 153 67mm 3 5 88 9mm 3 5 88 9mm 7 25 184 15mm 2 50 8mm 2 50 8mm 8 125 206 375mm 0 6 15 24mm 1 25 4mm 1 25 4mm 0 6 15 24mm 0 6 15 24mm 1 125 28 575mm 0 6 15 24mm 3 625 184...

Страница 11: ...6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25...

Страница 12: ...Series D02R MEMBER 1 25 31 75mm 0 5 12 7mm 0 5 12 7mm 1 5 12 7mm 1 25 31 75mm 1 5 12 7mm 3 5 88 9mm 3 5 88 9mm 3 5 88 9mm 1 25 4mm 1 25 4mm 5 75 146 05mm 1 25 4mm 1 13 28 7mm 5 88 149 35mm 0 88 22 35m...

Отзывы: