background image

 

AL842ADA220 Installation Guide 

- 3 -

Power Supply Specifications:

AC Input:

220VAC, 50/60Hz, 2.5A.

Output:

Four (4) regulated supervised NAC output circuits, 24VDC, 2.5A maximum current. 
One (1) aux. special application 24VDC power output circuit 1A, non-supervised. 
Total output current must not exceed current 8A in Alarm Condition.

Battery

Use two (2) 12VDC / 12AH or two (2) 12VDC / 7AH batteries 
connected in series.

Stand-by/Alarm
Current Consumption:

90mA/175mA

EOL Resistor (end of line):

2.2K (2200 Ohm), Altronix Model # AL-EOL22 (included).

Ground fault maximum
test impedance:

1000 Ohm.

Stand-by Specifications:

Stand-by  Batteries  

Stand-by Time Total

(A/Minutes)

Alarm Output 

Current

Aux. Output

24VDC/7AH

24 Hours

8A/5 minutes

24VDC/12AH (use two 12VDC batteries in series)

24 Hours

8A/5 minutes

50mA

24VDC/36AH

24 Hours

8A/5 minutes

1A

Note: Unit is equipped with two (2) 1A max. auxiliary outputs: “AUX1” will automatically disconnect when 
AC is lost. “AUX2” will remain battery backed up during power outage. For loads connected to “AUX2” 
please, refer to battery “Stand-by Specifications” above for ratings. When loads are connected to the 
“AUX1” and or “AUX2” outputs during alarm condition, the remaining outputs may not exceed 8A total 
alarm current (example: AUX1 = 1A, AUX2 = 1A, outputs up to 8A).

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 
local codes and authorities having jurisdiction.
Product is intended for indoor dry use only. 
 

Carefully review:

  Application Guide for AL642ADA220, AL842ADA220, AL1042ADA220
  Power Supply Specifications 

(pg. 3)

  Stand-by Specifications 

(pg. 3)

  Output Programming Selection Table 

(pg. 4)

  Sync Mode Selection Table 

(pg. 4)

  Terminal Identification Table 

(pgs. 5-6)

  LED Status Indication Table 

(pg. 6)

1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
 

(Enclosure Dimensions, pg. 12)

. Secure ground wire lead to earth ground lug 

(Fig. 1, pg. 3). 

Small terminal 

  block wire gauges range from 16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (220VAC, 50/60Hz)
  dedicated to the Fire Alarm System. 
3. Measure output voltage before connecting devices.This helps avoiding potential damage.
4. Connect battery to the terminals marked [+ BAT –] on the Power Supply Board (battery leads included). 
  Use two (2) 12VDC batteries connected in series. 
5. Set output selection switches marked [OUT1] through [OUT4] to follow corresponding Input [IN1] and 
  [IN2] and desired output signal type

 (Output Programming Selection Table, pg. 4).

6. Connect FACP output to the desired AL842LGK logic board inputs, and notification appliances to the 
  desired  AL842LGK logic board outputs 

(see 42 Application Guide).

Fig. 1

L       N

Line

Neutral

Ground Lug

Содержание AL642ADA220

Страница 1: ... see Application Guide for additional information Rev 072108 More than just power TM Installing Company _______________ Service Rep Name __________________________________ Address _____________________________________________ Phone __________________ ...

Страница 2: ...king range 198VAC 256VAC 50 60 Hz 2 5A Two 2 Class A Style Z or two 2 Class B Style W X Y FACP inputs Two 2 NC dry contact trigger inputs Output 24VDC voltage regulated power limited outputs 8A max total alarm current 2 5A max current per output Two auxiliary outputs rated at 1A each 1A continuous 1A AC disconnect Programmable supervised indicating circuit outputs Four 4 Class B Style W X Y or Fou...

Страница 3: ...n Guide for AL642ADA220 AL842ADA220 AL1042ADA220 Power Supply Specifications pg 3 Stand by Specifications pg 3 Output Programming Selection Table pg 4 Sync Mode Selection Table pg 4 Terminal Identification Table pgs 5 6 LED Status Indication Table pg 6 1 Mount the unit in the desired location Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure Install two uppe...

Страница 4: ... a means of synchronizing the Temporal coded horns synchronizing the flash timing of the strobe allowing audible notification appliances horns and visual notification appliances strobes to be silenced deactivated at the same time Gentex Sync Mode Gentex is a registered trademark of Gentex Corporation 1 2 3 4 This mode is designed to work with the Gentex series of horns strobes and horn strobes to ...

Страница 5: ...OUT3 OUT4 Supervised Notification appliances are connected to these regulated outputs see Application Guide pg 2 4 Each power limited output will supply 2 5A Total supply current is 8A see note below Outputs are controlled by designated Input 1 IN1 or Input 2 IN2 Output Programming Selection Table pg 4 Maximum line loss or voltage drop tested with 2 5V Loop 1 Loop 2 Loop 3 Loop 4 Used for Class A ...

Страница 6: ...onds Low battery condition will report at approximately 21VDC Battery presence detection will report with in 180 seconds after battery remains undetected missing or removed A restored battery will report within 30 seconds LED Diagnostics AL800ADA Power Supply Board Red DC Green AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery is supplying power OFF ON No D...

Страница 7: ... Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA Alarm mA 0mA mA C Notification Appliances Current must not exceed 8A 8000mA 0mA mA D Total alarm current mA mA E Total current ratings converted to amperes line D x 001 A A F Number of standby hours 24 for NFPA 72 Chapter 1 1 5 2 5 H G Multiply lines E and F Total stand by AH AH H Alarm sounding period in hours For example 5 minutes 0 0833 hours H I...

Страница 8: ... and IN2 Non Supervised Class E Factory Installed Board Interface Cable AC Magnetic Door Holder line ground neutral Unswitched 120VAC power mains supervised non power limited Supervised power limited Non supervised power limited Class E Non Supervised Class E Non Supervised Class E Compatible Special Application Devices See Compatibility List non power limited Stand by battery connection non power...

Страница 9: ...nect to the host control panel for local annunciation of the trouble condition Note If common trouble input terminals marked C FAULT NC are not used these terminals must be shorted connect jumper to remain inactive For optional hookups see Fig 2b Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output...

Страница 10: ...or 2112 24T D Photoelectric w 135 o Thermal 0 05 50 System Sensor 2112 24TSRB Photoelectric w 135 o Thermal Supervisory Relay 15 45 System Sensor 2312 24TB Photoelectric 0 12 50 System Sensor 2412 12 volt Photoelectric 0 12 77 System Sensor 2412AT 12 volt Photoelectric 0 12 58 System Sensor 2412TH 12 volt Photoelectric 0 12 77 System Sensor 2424 Photoelectric 0 10 41 System Sensor 2424TH Photoelec...

Страница 11: ...s compatible with AL642ADA220 AUX output and Outputs 1 8 when programmed as AUX Manufacturer Model Current mA Manufacturer Model Current mA System Sensor PR 1 15 System Sensor R 20T 40 PR 2 30 R 24T 40 PR 3 30 R 10E 23 EOLR 1 30 R 14E 23 R 10T 23 R 20E 40 R 14T 23 R 24E 40 ...

Страница 12: ...IAL842ADA220 H10U MEMBER 6 0 152 4mm 1 5 38 1mm 2 5 63 5mm 1 0 25 4mm 2 75 69 9mm 2 75 69 9mm 4 5 114 3mm 4 5 114 3mm 14 5 368 3mm 1 0 25 4mm 1 5 38 1mm 8 5 215 9mm 18 0 457 2mm 18 0 457 2mm 18 0 457 2mm 1 25 31 75mm 1 25 31 75mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 2 5 63 5mm 2 5 63 5mm 14 5 368 3mm 14 5 368 3mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm 1 0 25 4mm Enclosure Dimensions 1...

Отзывы: