AL600X220 Series 

- 5 -

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Terminal Identification:

Power Supply Board

Terminal Legend Function/Description
L, G, N

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral, G to ground.

+ DC ---

12VDC / 24VDC @ 6 amp continuous non power-limited output.

AC Fail
NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp  @ 28VDC. AC or brownout fail is 
reported within 1 minute of event. To delay reporting of up to 6 hrs., cut “AC delay” jumper and 
reset power to unit.

Bat Fail
NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC 
power is present. Contact rating 1 amp  @ 28VDC. A removed battery is reported within
5 minutes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

+ BAT ---

Stand-by battery connections. Maximum charge current 0.7 amp.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Terminal Legend

 Function/Description

PD4/PD4CB

PD8/PD8CB

1P to 4P

1P to 8P

  Positive DC power outputs.

  1N to 4N

 1N to 8N

  Negative DC power outputs.

Содержание AL600X220 Series

Страница 1: ...put AL600PD4220 AL600PD4CB220 Four 4 Fused Outputs Four 4 PTC Outputs AL600PD8220 AL600PD8CB220 Eight 8 Fused Outputs Eight 8 PTC Outputs AL600XPD16220 AL600XPD16CB220 Sixteen 16 Fused Outputs Sixteen...

Страница 2: ...g 1b pg 3 24VDC SW1 OPEN Fig 1b pg 3 Stand by Specifications total current shown Output 4 hr of Stand by 5 Minutes of Alarm 24 hr of Stand by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 12...

Страница 3: ...d Earth Ground 12VDC operation For 12VDC operation only a single battery is needed Connect red battery lead to terminal marked BAT and to the positive terminal of the battery Connect black battery lea...

Страница 4: ...onnect device s to be powered a For AL600X R 220 Power Supply connect devices to terminals marked DC Fig 1 pg 3 b For other Power Distribution Models connect devices to be powered to terminal pairs 1...

Страница 5: ...wnout fail is reported within 1 minute of event To delay reporting of up to 6 hrs cut AC delay jumper and reset power to unit Bat Fail NC C NO Indicates low battery condition e g connect to alarm pane...

Страница 6: ...ED F1 F2 F3 F4 POWER OUTPUTS 1P 1N 2P 2N 3P 3N 4P 4N DC Output to devices 1P 4P Power Outputs 1N 4N Common Outputs From Power Supply Board Factory Installed Fig 2b PD4CB N COMMON POWER OUTPUTS P FUSED...

Страница 7: ...5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm Enclo...

Страница 8: ...B220 AL600XPD8220 AL600XPD8CB220 AL600XPD16220 and AL600XPD16CB220 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm...

Отзывы: