AL600X220 Series

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 
codes and authorities having jurisdiction. Product is intended for indoor use only.
1.  Mount the unit in a desired locationMark and predrill holes in the wall to line up with the top two keyholes in the    
  enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s    
  upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the    
  enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper keyholes over the two upper    
  screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 6-7).
2.  The power supply is pre-wired to the ground (chassis). Connect main incoming ground to the provided green   

 

  grounding conductor lead. Connect unswitched AC power (220VAC, 50/60 Hz to terminals marked [L, G, N]
  (Fig. 1, pg. 3). Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to
  18 AWG for power-limited circuits (AC Fail/Low Battery reporting).
  Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, DC Output,  

 

  Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 
  There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3.  Set the unit to the desired DC output voltage by setting SW1 (Fig. 1b, pg. 3) to the appropriate position 
  (Power Supply Voltage Output Selections Chart, pg. 2).
4.  Measure output voltage before connecting any devices to ensure proper operation. Improper or high voltage will  

 

  damage these devices. When servicing the unit, AC mains should be removed.
5.  Connect device(s) to be powered:
  a.  For AL600X(R)220 Power Supply, connect devices to terminals marked [+ DC -] (Fig. 1, pg. 3).
  b.  For other Power Distribution Models, connect devices to be powered to terminal pairs 1 to 4 marked  
    [1P & 1N through 4P & 4N] (Fig. 2a & 2b, pg. 5) or 1 to 8 marked [1P & 1N through 8P & 8N] (Fig. 3a & 3b,    
    pg. 5
), carefully observing polarity. 
6.  For Access Control applications, batteries are optional. When batteries are not used, a loss of AC will result in the  

 

  loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
7.  Connect appropriate signaling notification devices to terminals marked [AC FAIL & BAT FAIL] (Fig. 1, pg. 3),  

 

  supervisory relay outputs.
 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay should be utilized 

  to visually indicate that AC power is on. To delay report for 6 hours, cut “AC Delay” jumper (Fig. 1a, pg. 3).
8.  Please ensure that the cover is secured with the provided Key Lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(refer to Power Supply Voltage Output Specifications chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at
battery terminal and at the board terminals marked [+ BAT --- ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharge is 0.7 amp.
Note: Expected battery life is 5 years, however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Power Supply Board

Red (DC) Green (AC)

Red (BAT)

Status

ON

ON

ON

Normal operating condition.

ON

OFF

ON

Loss of AC, Stand-by battery supplying power.

OFF

ON

OFF

No DC output, Battery Trouble

OFF

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

ON

ON

OFF

Battery missing / Low

Содержание AL600X220 Series

Страница 1: ...put AL600PD4220 AL600PD4CB220 Four 4 Fused Outputs Four 4 PTC Outputs AL600PD8220 AL600PD8CB220 Eight 8 Fused Outputs Eight 8 PTC Outputs AL600XPD16220 AL600XPD16CB220 Sixteen 16 Fused Outputs Sixteen...

Страница 2: ...g 1b pg 3 24VDC SW1 OPEN Fig 1b pg 3 Stand by Specifications total current shown Output 4 hr of Stand by 5 Minutes of Alarm 24 hr of Stand by 5 Minutes of Alarm 60 hr of Stand by 5 Minutes of Alarm 12...

Страница 3: ...d Earth Ground 12VDC operation For 12VDC operation only a single battery is needed Connect red battery lead to terminal marked BAT and to the positive terminal of the battery Connect black battery lea...

Страница 4: ...onnect device s to be powered a For AL600X R 220 Power Supply connect devices to terminals marked DC Fig 1 pg 3 b For other Power Distribution Models connect devices to be powered to terminal pairs 1...

Страница 5: ...wnout fail is reported within 1 minute of event To delay reporting of up to 6 hrs cut AC delay jumper and reset power to unit Bat Fail NC C NO Indicates low battery condition e g connect to alarm pane...

Страница 6: ...ED F1 F2 F3 F4 POWER OUTPUTS 1P 1N 2P 2N 3P 3N 4P 4N DC Output to devices 1P 4P Power Outputs 1N 4N Common Outputs From Power Supply Board Factory Installed Fig 2b PD4CB N COMMON POWER OUTPUTS P FUSED...

Страница 7: ...5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm Enclo...

Страница 8: ...B220 AL600XPD8220 AL600XPD8CB220 AL600XPD16220 and AL600XPD16CB220 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm...

Отзывы: