- 2 -
AL600X220 Series
Overview:
The AL600X220 is a power supply that converts a nominal 220VAC (working range 198VAC-256VAC), 50/60Hz input
to a 12VDC or 24VDC regulating output (see specifications below). The AL600X220 is the base power supply unit for
the multi-output power supply/charger series: AL600PD4220, AL600PD4CB220, AL600PD8220, AL600PD8CB220,
AL600XPD16220, AL600XPD16CB220 (Refer to AL600X220 Series Power Supply Configuration Reference Chart below).
AL600X220 Series Power Supply Configuration Reference Chart:
Altronix
Model Number
Accessory
Power
Distribution
Module(s)
Number
of
Output(s)
Fused
Outputs
PTC
Outputs
Output
Rating (amp)
per Output
AL600X220
--------
1
--------
--------
6
AL600PD4220
PD4
4
x
--------
3.5
AL600PD4CB220
PD4CB
4
--------
x
2.5
AL600PD8220
PD8
8
x
--------
3.5
AL600PD8CB220
PD8CB
8
--------
x
2.5
AL600XPD16220
Two (2) PD8
16
x
--------
3.5
AL600XPD16CB220
Two (2) PD8CB
16
--------
x
2.5
Do not exceed total output rating of 6 amp per unit.
AL600X220, AL600PD4220, AL600PD4CB220, AL600PD8220 and AL600PD8CB220 are available in larger enclosure.
Add X to model, e.g. AL600XX220 or AL600XPD4220.
Specifications:
Power Supply Output Specifications:
Output Switch Position
12VDC SW1 - CLOSED (Fig. 1b, pg. 3)
24VDC SW1 - OPEN (Fig. 1b, pg. 3)
Stand-by Specifications
(total current shown)
:
Output
4 hr. of Stand-by &
5 Minutes of Alarm
24 hr. of Stand-by &
5 Minutes of Alarm
60 hr. of Stand-by &
5 Minutes of Alarm
12VDC / 40AH Battery
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
24VDC / 12AH Battery
--------
Stand-by = 200mA
Alarm = 6.0 amp
--------
24VDC / 40AH Battery
Stand-by = 6.0 amp
Alarm = 6.0 amp
Stand-by = 1.0 amp
Alarm = 6.0 amp
Stand-by = 300mA
Alarm = 6.0 amp
Input:
• Input 220VAC (working range 198VAC - 256VAC),
50/60Hz, 1.2 amp.
Output:
• 12VDC or 24VDC selectable output(s).
• 6 amp continuous supply current at 12VDC or 24VDC.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.7 amp.
Battery Backup
(cont’d)
:
• Zero voltage drop when switched over to
battery backup.
Supervision:
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
• Battery presence supervision (form “C” contacts).
Additional Features:
• AC input, DC output and BAT trouble LED indicators.
• Power supply, enclosure, cam lock and battery leads.
• All models are available in a red enclosure
(add an “R” suffix to the part # e.g. AL600PD8220R).
OPEN SWITCH
CLOSED SWITCH